Plan Review Details - Permit 00080502
Plan Review Stops For Permit 00080502
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-09-18 Cont ID  
Sent By hpiskura Date 2000-09-18 Time 07:59 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-25 Cont ID  
Sent By dpalmer Date 2000-10-25 Time 00:58 Rev Time 0.00
Received By dpalmer Date 2000-10-25 Time 00:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-29 Cont ID  
Sent By dpalmer Date 2000-08-29 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2000-08-29 Time 19:50 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE 450-13-B OF THE NEC
 FOR THE INSTALLATION REQ`MENTS OF TRANS-
 -FORMER.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS TO
 INCLUDE SQ FT
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-18 Cont ID  
Sent By mcarsill Date 2000-09-18 Time 11:13 Rev Time 0.00
Received By mcarsill Date 2000-09-18 Time 11:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-11 Cont ID  
Sent By mcarsill Date 2000-08-11 Time 08:10 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00ON AUGUST 10, 2000, WRITER SPOKE BY
 TELEPHONE TO SONG AND ASSOCIATES. A
 LETTER WAS REQUESTED ON THE FLAME SPREAD
 RATINGS FOR THE INTERIOR FINISHES
 PLANNED FOR USE. ALSO INFORMATION ON
 THE MAXIMUM AMOUNT OF OCCUPANTS USING
 THE SPACE IS NEEDED. THE CODE ALLOWS
 A SINGLE MEANS OF EGRESS IF OCCUPANT
 LOADS ARE LESS THAN 100 BUSINESS OR
 LESS THAN 50 IF ASSEMBLY. WRITER ALSO
 ADVISED THAT IF ANY REMODEL WORK IS
 NECESSARY TO THE EXISTING FIRE SPRINKLER
 SYSTEM, THEN A PLAN AND PERMIT IS
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-14 Cont ID  
Sent By cthirben Date 2000-08-14 Time 14:30 Rev Time 1.00
Received By cthirben Date 2000-08-14 Time 14:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-11-16 Cont ID  
Sent By jleech Date 2000-11-16 Time 14:23 Rev Time 0.50
Received By jleech Date 2000-11-16 Time 14:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-10-28 Cont ID  
Sent By tlarge Date 2000-10-28 Time 04:53 Rev Time 0.00
Received By tlarge Date 2000-10-28 Time 04:56 Sent To  
Notes
2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.15.PROVISIONS SHALL BE MADE
 FOR PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING PER FACBC SEC.4.1.3.(10)(A).
  
 2)SUBMIT REVISED SANITARY AND WATER
 RISER DIAGRAMS SHOWING DRINKING FOUNTAIN
 CONNECTIONS.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-14 Cont ID  
Sent By pschmitz Date 2000-10-14 Time 11:22 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLBG PLAN REVIEW RESUBMIT
 (1) APPR AS REVISED. PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-14 Cont ID  
Sent By tlarge Date 2000-08-20 Time 09:20 Rev Time 0.33
Received By pschmitz Date 2000-08-20 Time 09:05 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD BASED ON SQ.FEET
 OF HABITABLE FLOOR SPACE.SEE SPC SEC.
 407.1.3. FOR ALLOWED DEDUCTIBLE AREAS.
 ADDITIONAL PLBG.FIXTURES MAY BE REQD.
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SECS.4.1.3,4.15.PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 3)SINK IN LOUNGE SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.MAX.HEIGHT OF CABINET
 SHALL BE 34"AT CLEAR FLOOR ACCESS AREA.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.