| Plan Review Stops For Permit 00080487 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-21 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-21 |
Time |
10:32 |
Rev Time |
0.50 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-20 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-20 |
Time |
07:41 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-20 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT FIRE SPRINKLER PLANS AND PERMIT | | | APPLICATION. | | | ######################################## | | | PROVISO | | | WINDOWS AND DOOR SYSTEM BY OTHERS SEE | | | PERMIT # 00090839 | | | | | | BOTH SIDE OF FIRE SEPERATION WALL SHALL | | | BE COMPLETED PRIOR TO C.O. BEING ISSUED | | | AWNING AND SIGNS TO BE UNDER SEPERATE | | | PERMITS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2000-08-21 |
Time |
11:37 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | 1.PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT WINDOWS AND DOORS FOR STORE- | | | FRONTS/METRO DADE COUNTY OR SBCCI. | | | 2.SUBMIT FIRE SPRINKLER PLANS AND PERMIT | | | APPLICATION. | | | 3.SIGNS UNDER SEPERATE PERMIT. | | | 4.HURICANE SHUTTERS UNDER SEPERATE | | | PERMIT. | | | 5.DEMIZING WALL MUST BE COMPLETED PRIOR | | | TO C.O. BEING ISSUED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-10-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-24 |
Time |
22:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-24 |
Time |
22:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-19 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-19 |
Time |
17:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-22 |
Time |
07:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-22 |
Time |
07:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE LOAD SHOWN | | | FOR TRANSFORMER AT PANEL "HV" EXCEEDS | | | 80% OF LOADING ALLOWED FOR 20A BRKR. | | | PLEASE CHECK 450-3-B FOR MAX RATING | | | ALLOWED. | | | | | | 2)NOTE: PLEASE SHOW LOAD FOR TRACK LIGHT | | | -ING PER 220-12-B. | | | | | | 3)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON FLOOR PLAN (E-1) PLEASE CORRELATE | | | THIS WITH PANEL SCHEDULES SHOWN ON E-2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-21 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-21 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-21 |
Time |
14:42 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-21 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. PLAN SHOWS SPACE TO BE NEGATIVE 65CFM | | | FLORIDA ENERGY CODE 410.1 NOTES BUILDING | | | PRESSURIZATION SHOULD BE EITHER NEUTRAL | | | OR POSITIVE TO PREVENT INFILTRATION OF | | | EXCESS LATENT LOAD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-19 |
Time |
20:41 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-09-19 |
Time |
20:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-19 |
Time |
06:20 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-19 |
Time |
06:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)NOTE SQ.FEET OF SPACE ON PLANS TO | | | ENSURE COMPLIANCE W/SPC TABLE 407 FOR | | | PLBG.FIXTURES. | | | | | | 2)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.BOTTLED WATER IS NOT ACCEPT- | | | ABLE IN LIEU OF FOUNTAIN. | | | | | | 3)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3(10)(A).4.15.PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 4)A FLOOR DRAIN IS REQD.IN THE TOILET | | | ROOM PER SPC SEC.409.4.1.1. | | | | | | 5)MOUNTING HEIGHTS OF HANDICAP FIXTURES | | | SHALL COMPLY W/FACBC OCT.1997 EDITION. |
|
|