| Plan Review Stops For Permit 00080483 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2000-10-24 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-24 |
Time |
10:17 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-24 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION 10/19/00 | | | 1. DOES NOT COMPLY WITH FLORIDA HANDICAP | | | CODE SECTION 4.13.7 & FIG 26 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-12 |
Time |
14:49 |
Rev Time |
0.50 |
| Received By |
drunnels |
Date |
2000-09-12 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************NOTE*************** | | | STOREFRONT UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-07 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-07 |
Time |
08:12 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-07 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.FIRE SPRINKLER CONTRACTOR MUST MAKE | | | APPLICATION FOR PERMIT. | | | | | | **************NOTE********************* | | | STOREFRONT TO BE ISSUED UNDER SEPERATE | | | PERMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-24 |
Time |
13:57 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-24 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.PROVIDE PRODUCT FOR IMPACT RESISTANT | | | WINDOWS AND DOORS FOR STOREFRONT/METRO | | | DADE COUNTY OR SBCCI | | | 2.SUBMIT FIRE SPRINKLER PLANS AND PERMIT | | | APPLICATION | | | 3.FLORIDA ENERGY SHEETS MUST BE COMPLETE | | | PAGE 2,ALSO MUST BE SIGNED BY OWNER | | | OR OWNER AGENT | | | 4.DEMIZING WALL MUST BE COMPLETED PRIOR | | | TO C.O. BEING ISSUED |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-10-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-24 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-24 |
Time |
18:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-12 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-12 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-22 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-22 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT***************** | | | | | | 1)NOTE: PLEASE SHOW BRANCH CIRCUIT #`S | | | ON PLAN FOR EMERGENCY LIGHTING. | | | | | | 2)NOTE: PLEASE SHOW TRACK LIGHTING IN | | | CALCULATION PER 220-12-B | | | | | | 3)NOTE: PLEASE SEE THAT LOAD SHOWN FOR | | | TRANSFORMER ON PANEL "HV" IS SHOWN | | | EXCEEDING THE ALLOWED 80% OF OCP DEVICE. | | | PLEASE SEE 450-3-BFOR MAX OCP. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-21 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-21 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) MIRROR LOCATED NEAR EXIT DOOR. | | | "MIRRORS SHALL NOT BE PLACED IN OR | | | ADJACENT TO ANY EXIT IN SUCH A MANNER | | | AS TO CONFUSE THE DIRECTION OF EXIT" | | | RE:NFPA 101, 1985 EDITION, SECTION | | | 5-5.2.2 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-06 |
Time |
10:20 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-09-06 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-21 |
Time |
14:36 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-08-21 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-06 |
Time |
18:47 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-09-06 |
Time |
18:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-19 |
Time |
06:44 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-19 |
Time |
06:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.BOTTLED WATER IS NOT ACCEPT- | | | ABLE IN LIEU OF D.F. | | | | | | 2)DRINKING FOUNTAIN SHALL BE ACCESSIBLE | | | AND COMPLY W/4.1.3,4.15.PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 3)SUBMIT SQ.FOOTAGE OF SPACE TO ENSURE | | | COMPLIANCE W/SPC TABLE 407 FOR PLBG. | | | FIXTURES. | | | | | | 4)FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOM PER SPC 409.4.1.1 | | | | | | 5)MOUNTING HEIGHTS OF PLUMBING FIXTUTRES | | | SHALL COMPLY W/FACBC OCT.1997 EDITION. | | | (SEE LAV.,MIRROR). | | | | | | 6)GRAB BAR BEHIND W.C.SHALL BE 36" MIN. | | | FACBC SEC.4.16.4. |
|
|