Plan Review Details - Permit 00080483
Plan Review Stops For Permit 00080483
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2000-10-24 Cont ID  
Sent By drunnels Date 2000-10-24 Time 10:17 Rev Time 1.00
Received By drunnels Date 2000-10-24 Time 10:16 Sent To  
Notes
2001-01-08 00:00:00REVISION 10/19/00
 1. DOES NOT COMPLY WITH FLORIDA HANDICAP
 CODE SECTION 4.13.7 & FIG 26

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-12 Cont ID  
Sent By drunnels Date 2000-09-12 Time 14:49 Rev Time 0.50
Received By drunnels Date 2000-09-12 Time 14:47 Sent To  
Notes
2001-01-08 00:00:00****************NOTE***************
 STOREFRONT UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-07 Cont ID  
Sent By drunnels Date 2000-09-07 Time 08:12 Rev Time 1.00
Received By drunnels Date 2000-09-07 Time 08:12 Sent To  
Notes
2001-01-08 00:00:001.FIRE SPRINKLER CONTRACTOR MUST MAKE
 APPLICATION FOR PERMIT.
  
 **************NOTE*********************
 STOREFRONT TO BE ISSUED UNDER SEPERATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-24 Cont ID  
Sent By drunnels Date 2000-08-24 Time 13:57 Rev Time 1.00
Received By drunnels Date 2000-08-24 Time 13:57 Sent To  
Notes
2001-01-08 00:00:001.PROVIDE PRODUCT FOR IMPACT RESISTANT
 WINDOWS AND DOORS FOR STOREFRONT/METRO
 DADE COUNTY OR SBCCI
 2.SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION
 3.FLORIDA ENERGY SHEETS MUST BE COMPLETE
 PAGE 2,ALSO MUST BE SIGNED BY OWNER
 OR OWNER AGENT
 4.DEMIZING WALL MUST BE COMPLETED PRIOR
 TO C.O. BEING ISSUED

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-24 Cont ID  
Sent By dpalmer Date 2000-10-24 Time 18:04 Rev Time 0.00
Received By dpalmer Date 2000-10-24 Time 18:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 14:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-22 Cont ID  
Sent By dpalmer Date 2000-08-22 Time 07:49 Rev Time 0.00
Received By dpalmer Date 2000-08-22 Time 07:49 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT*****************
  
 1)NOTE: PLEASE SHOW BRANCH CIRCUIT #`S
 ON PLAN FOR EMERGENCY LIGHTING.
  
 2)NOTE: PLEASE SHOW TRACK LIGHTING IN
 CALCULATION PER 220-12-B
  
 3)NOTE: PLEASE SEE THAT LOAD SHOWN FOR
 TRANSFORMER ON PANEL "HV" IS SHOWN
 EXCEEDING THE ALLOWED 80% OF OCP DEVICE.
 PLEASE SEE 450-3-BFOR MAX OCP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH.
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-21 Cont ID  
Sent By mcarsill Date 2000-08-21 Time 09:24 Rev Time 0.00
Received By mcarsill Date 2000-08-21 Time 09:23 Sent To  
Notes
2001-01-08 00:00:001) MIRROR LOCATED NEAR EXIT DOOR.
 "MIRRORS SHALL NOT BE PLACED IN OR
 ADJACENT TO ANY EXIT IN SUCH A MANNER
 AS TO CONFUSE THE DIRECTION OF EXIT"
 RE:NFPA 101, 1985 EDITION, SECTION
 5-5.2.2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-06 Cont ID  
Sent By ndenmark Date 2000-09-06 Time 10:20 Rev Time 0.25
Received By ndenmark Date 2000-09-06 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-21 Cont ID  
Sent By ndenmark Date 2000-08-21 Time 14:36 Rev Time 0.25
Received By ndenmark Date 2000-08-21 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-06 Cont ID  
Sent By tlarge Date 2000-09-06 Time 18:47 Rev Time 0.50
Received By tlarge Date 2000-09-06 Time 18:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-19 Cont ID  
Sent By tlarge Date 2000-08-19 Time 06:44 Rev Time 0.50
Received By tlarge Date 2000-08-19 Time 06:30 Sent To  
Notes
2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.BOTTLED WATER IS NOT ACCEPT-
 ABLE IN LIEU OF D.F.
  
 2)DRINKING FOUNTAIN SHALL BE ACCESSIBLE
 AND COMPLY W/4.1.3,4.15.PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 3)SUBMIT SQ.FOOTAGE OF SPACE TO ENSURE
 COMPLIANCE W/SPC TABLE 407 FOR PLBG.
 FIXTURES.
  
 4)FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOM PER SPC 409.4.1.1
  
 5)MOUNTING HEIGHTS OF PLUMBING FIXTUTRES
 SHALL COMPLY W/FACBC OCT.1997 EDITION.
 (SEE LAV.,MIRROR).
  
 6)GRAB BAR BEHIND W.C.SHALL BE 36" MIN.
 FACBC SEC.4.16.4.