| Plan Review Stops For Permit 00080391 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-09-29 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-29 |
Time |
15:13 |
Rev Time |
0.50 |
| Received By |
drunnels |
Date |
2000-09-29 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-27 |
Time |
10:49 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-27 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. SUBMIT FIRE SPRINKLER PLANS AND | | | PERMIT APPLICATION. | | | | | | | | | | | | | | | | | | **************** PROVISO *************** | | | SIGNS TO BE UNDER SEPERATE PERMIT | | | STORE FRONT ISSUED UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-11 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-11 |
Time |
09:09 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-11 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.SUBMIT FIRE SPRINKLER PLANS AND | | | APPLICATION FOR PERMIT | | | 2.SUBMIT PRODUCT APPROVAL FOR WINDOWS | | | AND DOOR GLAZING FOR STOREFRONT.METRO | | | DADE OR SBCCI/ STOREFRONT CAN BE ISSUED | | | UNDER SEPERATE PERMIT | | | 3. NEW PLANS MUST BE STAMPED APPROVED | | | BY CITY PLACE | | | | | | *************** PROVISO **************** | | | SIGNS TO BE UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-16 |
Time |
12:17 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-16 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | 1.SUBMIT PRODUCT APPROVAL FOR WINDOW & | | | DOOR GLAZING FOR STOREFRONT. METRO DADE | | | COUNTY OR SBCCI. | | | 2. SUBMIT FIRE SPRINKLER PLANS AND | | | APPLICATION. FIRE SPRINKLER PERMIT TO BE | | | ISSUED PRIOR TO BUILDING PERMIT BEING | | | ISSUED. | | | 3.SIGN TO BE UNDER SEPERATE PERMIT. | | | 4. TITLE SHEET-LIFE SAFETY DATA-THERE IS | | | A REFERENCE TO THE UBC FOR FIRE | | | RETARDANT WOOD FRAMING & BLOCKING- | | | CORRECT TO MATCH SECTION IN SBC. | | | 5. SUBMIT DETAIL ON DEMIZING WALLS | | | PROVIDE UL ASSEMBLY NUMBER FOR FIRE | | | SEPERATION PER TABLE 704.1 SBC-BOTH | | | SIDES MUST BE COMPLETED. | | | 6. SHEET A8.0 DETAILS-NOT IN PLANS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-27 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-27 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-12 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-12 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE FIRST SET OF REVIEW | | | NOTES. NOT ALL NOTES WERE ADDRESSED. | | | NOTE,2,3,4,7. | | | PLEASE CALL IF THERE ARE ANY QUESTIONS | | | OR CLARIFICATION NEEDED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-15 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-15 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW ADDITIONAL EXIT | | | LIGHT REQ`D OUTSIDE STORAGE ROOM | | | | | | 2)NOTE:PLEASE HAVE THE '99' NEC REF.ON | | | COVER SHEET ALONG WITH THE LOCAL CITY | | | OF WEST APLM BEACH AMENDMENTS. | | | | | | 3)NOTE: PLEASE SEE 210-62 FOR SHOW | | | WINDOW RECEPT REQ`MENTS. | | | | | | | | | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. (LIGHTING/SIGNAGE/ETC). | | | | | | 5)NOTE: PLEASE SUBMIT MORE DETAIL ON | | | THE LOAD CALCULATIONS. SQ.FT ETC | | | | | | 6)NOTE: PLEASEGIVE CLARIFICATION ON | | | SPACE 36 FOR DIMMING SYSTEM. 5400VA AT | | | 120V?? AT 125% FOR CONTINUOUS LOAD. | | | BREAKER SIZE TO BE SHOWN AS MIN. REQ`D. | | | | | | 7)NOTE: PLEASE SEE REQ`MENTS OF 220-12B | | | FOR TRACK LIGHITNG. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-09-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-29 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-29 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-12 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-12 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISHES ON WALLS AND | | | CEILINGS TO BE CLASS A OR B. | | | 2) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON PLANS. | | | 3) THIS OFFICE RECOMMENDS THAT DOOR | | | DO4, SWING IN THE DIRECTION OF EXIT | | | TRAVEL. | | | 4) NO FIRE SPRINKLER PLANS PROVIDED | | | WITH DRAWINGS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-16 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | | SHOULD READ 1985 LIFE SAFETY CODE | | | INSTEAD OF 1991 LIFE SAFETY CODE. | | | 2) NO FIRE SPRINKLER DRAWINGS SUBMITTED | | | WITH PLANS. | | | 3) ALTHOUGH THE TENANT SPACE OCCUPANT | | | LOAD IS LESS THAN 50 AND THE REAR EXIT | | | DOOR IS NOT REQUIRED TO SWING IN THE | | | DIRECTION OF EXIT TRAVEL, DOES | | | ANYTHING STOP IT FROM SWINGING OUT. | | | 4) NO FIRE ALARM DEVICES SHOWN ON | | | PLANS. HOW IS THE BASE BUILDING | | | FIRE ALARM SYSTEM HEARD. | | | 5) CLEARLY DEMONSTRATE ALL EMERGENCY | | | LIGHTING FIXTURES IN SPACE. | | | 6) AN ADDITIONAL EXIT SIGN IS NEEDED | | | TO DIRECT PERSONS TO REAR EXIT DOOR | | | LOCATION. | | | 7) EXITING THROUGH STOCKROOM PERMITTED | | | ONLY IF THE FOLLOWING CONDITIONS EXIST, | | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | | IS ALLOWED THROUGH STOCKROOM, DOOR TO | | | STOCKROOM CANNOT BE LOCKED, AN AISLE OF | | | AT LEAST 44" TO BE PROVIDED AND | | | MAINTAINED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-14 |
Time |
10:25 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-09-14 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-22 |
Time |
12:51 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-08-22 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************DENIED***************** | | | | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | TO BE TIED TO BLDG FIRE ALARM OR HORN | | | AND STROBE FOR NOTIFICATION PER NFPA | | | 90A 4-4.4 | | | NOTE: NO COMBUSTIBLES ALLOWED IN RETURN | | | AIR PLENUM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-27 |
Time |
10:15 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-09-27 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-12 |
Time |
16:58 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-09-12 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | 1)CONDENSATE DRAIN SHALL CONNECT TO | | | COMMON SYSTEM,NOT LAVATORY.SMC SEC.304.8 | | | | | | 2)INSTANTANEOUS WATER HEATER SHALL NOT | | | INFRINGE ON THE CLEAR FLOOR SPACE UNDER | | | LAVATORY PER FACBC SEC.4.19.2 & FIG.31. | | | | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-25 |
Time |
07:42 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)HANDICAP ACCESSIBLE TOILET ROOMS/REST- | | | ROOMS SHALL BE INDELIBY POSTED FOR THE | | | INTENDED USE,BE ON AN ACCESSIBLE ROUTE | | | AND BE AVAILABLE TO PATRONS WITHOUT | | | RESTRICTION DURING NORMAL OPERATING | | | HOURS.THE ACCESSIBLE ROUTE SHALL BE | | | SHOWN ON THE PLANS.FACBC SECS.4.1,4.2, | | | 4.3.,SPC 407.2.2. | | | | | | 2)CONDENSATE DRAIN SHALL CONNECT TO THE | | | COMMON SYSTEM,NOT TO THE LAV.DRAIN. | | | SMC SEC.304.8.3. | | | | | | 3)SUBMIT WATER RISER DIAGRAM FOR REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 4)TANKLESS WATER HEATER SHALL BE NOT | | | INFRINGE ON THE REQUIRED CLEAR FLOOR | | | SPACE AND KNEE AND TOE CLEARANCES PER | | | FACBC SECS.4.19.2,4.19.3,FIG.#31,32. |
|
|