Plan Review Details - Permit 00080391
Plan Review Stops For Permit 00080391
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-09-29 Cont ID  
Sent By drunnels Date 2000-09-29 Time 15:13 Rev Time 0.50
Received By drunnels Date 2000-09-29 Time 15:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-09-27 Cont ID  
Sent By drunnels Date 2000-09-27 Time 10:49 Rev Time 1.00
Received By drunnels Date 2000-09-27 Time 10:49 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION.
  
  
  
  
  
 **************** PROVISO ***************
 SIGNS TO BE UNDER SEPERATE PERMIT
 STORE FRONT ISSUED UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-11 Cont ID  
Sent By drunnels Date 2000-09-11 Time 09:09 Rev Time 1.00
Received By drunnels Date 2000-09-11 Time 09:09 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION FOR PERMIT
 2.SUBMIT PRODUCT APPROVAL FOR WINDOWS
 AND DOOR GLAZING FOR STOREFRONT.METRO
 DADE OR SBCCI/ STOREFRONT CAN BE ISSUED
 UNDER SEPERATE PERMIT
 3. NEW PLANS MUST BE STAMPED APPROVED
 BY CITY PLACE
  
 *************** PROVISO ****************
 SIGNS TO BE UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-16 Cont ID  
Sent By drunnels Date 2000-08-16 Time 12:17 Rev Time 1.00
Received By drunnels Date 2000-08-16 Time 12:16 Sent To  
Notes
2001-01-08 00:00:00 
  
 1.SUBMIT PRODUCT APPROVAL FOR WINDOW &
 DOOR GLAZING FOR STOREFRONT. METRO DADE
 COUNTY OR SBCCI.
 2. SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION. FIRE SPRINKLER PERMIT TO BE
 ISSUED PRIOR TO BUILDING PERMIT BEING
 ISSUED.
 3.SIGN TO BE UNDER SEPERATE PERMIT.
 4. TITLE SHEET-LIFE SAFETY DATA-THERE IS
 A REFERENCE TO THE UBC FOR FIRE
 RETARDANT WOOD FRAMING & BLOCKING-
 CORRECT TO MATCH SECTION IN SBC.
 5. SUBMIT DETAIL ON DEMIZING WALLS
 PROVIDE UL ASSEMBLY NUMBER FOR FIRE
 SEPERATION PER TABLE 704.1 SBC-BOTH
 SIDES MUST BE COMPLETED.
 6. SHEET A8.0 DETAILS-NOT IN PLANS

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-27 Cont ID  
Sent By dpalmer Date 2000-09-27 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2000-09-27 Time 12:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 14:06 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE FIRST SET OF REVIEW
 NOTES. NOT ALL NOTES WERE ADDRESSED.
 NOTE,2,3,4,7.
 PLEASE CALL IF THERE ARE ANY QUESTIONS
 OR CLARIFICATION NEEDED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 16:24 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW ADDITIONAL EXIT
 LIGHT REQ`D OUTSIDE STORAGE ROOM
  
 2)NOTE:PLEASE HAVE THE '99' NEC REF.ON
 COVER SHEET ALONG WITH THE LOCAL CITY
 OF WEST APLM BEACH AMENDMENTS.
  
 3)NOTE: PLEASE SEE 210-62 FOR SHOW
 WINDOW RECEPT REQ`MENTS.
  
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. (LIGHTING/SIGNAGE/ETC).
  
 5)NOTE: PLEASE SUBMIT MORE DETAIL ON
 THE LOAD CALCULATIONS. SQ.FT ETC
  
 6)NOTE: PLEASEGIVE CLARIFICATION ON
 SPACE 36 FOR DIMMING SYSTEM. 5400VA AT
 120V?? AT 125% FOR CONTINUOUS LOAD.
 BREAKER SIZE TO BE SHOWN AS MIN. REQ`D.
  
 7)NOTE: PLEASE SEE REQ`MENTS OF 220-12B
 FOR TRACK LIGHITNG.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-09-29 Cont ID  
Sent By mcarsill Date 2000-09-29 Time 15:20 Rev Time 0.00
Received By mcarsill Date 2000-09-29 Time 15:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-09-12 Cont ID  
Sent By mcarsill Date 2000-09-12 Time 15:20 Rev Time 0.00
Received By mcarsill Date 2000-09-12 Time 15:19 Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISHES ON WALLS AND
 CEILINGS TO BE CLASS A OR B.
 2) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS.
 3) THIS OFFICE RECOMMENDS THAT DOOR
 DO4, SWING IN THE DIRECTION OF EXIT
 TRAVEL.
 4) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-16 Cont ID  
Sent By mcarsill Date 2000-08-16 Time 13:19 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 SHOULD READ 1985 LIFE SAFETY CODE
 INSTEAD OF 1991 LIFE SAFETY CODE.
 2) NO FIRE SPRINKLER DRAWINGS SUBMITTED
 WITH PLANS.
 3) ALTHOUGH THE TENANT SPACE OCCUPANT
 LOAD IS LESS THAN 50 AND THE REAR EXIT
 DOOR IS NOT REQUIRED TO SWING IN THE
 DIRECTION OF EXIT TRAVEL, DOES
 ANYTHING STOP IT FROM SWINGING OUT.
 4) NO FIRE ALARM DEVICES SHOWN ON
 PLANS. HOW IS THE BASE BUILDING
 FIRE ALARM SYSTEM HEARD.
 5) CLEARLY DEMONSTRATE ALL EMERGENCY
 LIGHTING FIXTURES IN SPACE.
 6) AN ADDITIONAL EXIT SIGN IS NEEDED
 TO DIRECT PERSONS TO REAR EXIT DOOR
 LOCATION.
 7) EXITING THROUGH STOCKROOM PERMITTED
 ONLY IF THE FOLLOWING CONDITIONS EXIST,
 NOT MORE THAN 50 PERCENT OF EXIT ACCESS
 IS ALLOWED THROUGH STOCKROOM, DOOR TO
 STOCKROOM CANNOT BE LOCKED, AN AISLE OF
 AT LEAST 44" TO BE PROVIDED AND
 MAINTAINED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-14 Cont ID  
Sent By ndenmark Date 2000-09-14 Time 10:25 Rev Time 0.33
Received By ndenmark Date 2000-09-14 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-22 Cont ID  
Sent By ndenmark Date 2000-08-22 Time 12:51 Rev Time 0.50
Received By ndenmark Date 2000-08-22 Time 12:51 Sent To  
Notes
2001-01-08 00:00:00****************DENIED*****************
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TIED TO BLDG FIRE ALARM OR HORN
 AND STROBE FOR NOTIFICATION PER NFPA
 90A 4-4.4
 NOTE: NO COMBUSTIBLES ALLOWED IN RETURN
 AIR PLENUM

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-09-27 Cont ID  
Sent By tlarge Date 2000-09-27 Time 10:15 Rev Time 0.50
Received By tlarge Date 2000-09-27 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By tlarge Date 2000-09-12 Time 16:58 Rev Time 0.65
Received By tlarge Date 2000-09-12 Time 16:18 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 1)CONDENSATE DRAIN SHALL CONNECT TO
 COMMON SYSTEM,NOT LAVATORY.SMC SEC.304.8
  
 2)INSTANTANEOUS WATER HEATER SHALL NOT
 INFRINGE ON THE CLEAR FLOOR SPACE UNDER
 LAVATORY PER FACBC SEC.4.19.2 & FIG.31.
  
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-25 Cont ID  
Sent By tlarge Date 2000-08-25 Time 07:42 Rev Time 0.75
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:001)HANDICAP ACCESSIBLE TOILET ROOMS/REST-
 ROOMS SHALL BE INDELIBY POSTED FOR THE
 INTENDED USE,BE ON AN ACCESSIBLE ROUTE
 AND BE AVAILABLE TO PATRONS WITHOUT
 RESTRICTION DURING NORMAL OPERATING
 HOURS.THE ACCESSIBLE ROUTE SHALL BE
 SHOWN ON THE PLANS.FACBC SECS.4.1,4.2,
 4.3.,SPC 407.2.2.
  
 2)CONDENSATE DRAIN SHALL CONNECT TO THE
 COMMON SYSTEM,NOT TO THE LAV.DRAIN.
 SMC SEC.304.8.3.
  
 3)SUBMIT WATER RISER DIAGRAM FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 4)TANKLESS WATER HEATER SHALL BE NOT
 INFRINGE ON THE REQUIRED CLEAR FLOOR
 SPACE AND KNEE AND TOE CLEARANCES PER
 FACBC SECS.4.19.2,4.19.3,FIG.#31,32.