Plan Review Details - Permit 00080356
Plan Review Stops For Permit 00080356
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-22 Cont ID  
Sent By drunnels Date 2000-09-22 Time 10:11 Rev Time 1.00
Received By drunnels Date 2000-09-22 Time 10:11 Sent To  
Notes
2001-01-08 00:00:00PROVISO
 SIGNS AND AWNINGS UNDER REQUIRES
 SEPERATE PERMITS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-20 Cont ID  
Sent By drunnels Date 2000-09-20 Time 14:29 Rev Time 1.00
Received By drunnels Date 2000-09-20 Time 14:29 Sent To  
Notes
2001-01-08 00:00:001. OWNER/AGENT MUST SIGN FLORIDA ENERGY
 SHEETS.
 2.SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION.
  
 ************** PROVISO *****************
 SIGNS AND AWNINGS REQUIRE SEPERATE
 PERMITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-18 Cont ID  
Sent By drunnels Date 2000-08-18 Time 09:00 Rev Time 1.00
Received By drunnels Date 2000-08-16 Time 14:58 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
 1.OWNER/AGENT MUST SIGN FLORIDA ENERGY
 SHEETS.
 2.SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION FOR PERMIT.
 3.SUBMIT PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR WINDOWS AND DOORS
 ON STOREFRONT. METRO DADE COUNTY / SBCCI
 4.DEMIZING WALL SHALL BE COMPLETED ON
 BOTH SIDES.
 5.SIGNS UNDER SEPERATE PERMIT.
 6.AWNING TO BE UNDER SEPERATE PERMIT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-24 Cont ID  
Sent By dpalmer Date 2000-10-24 Time 18:04 Rev Time 0.00
Received By dpalmer Date 2000-10-24 Time 18:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-20 Cont ID  
Sent By dpalmer Date 2000-09-20 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2000-09-20 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-22 Cont ID  
Sent By dpalmer Date 2000-08-22 Time 07:20 Rev Time 0.00
Received By dpalmer Date 2000-08-22 Time 07:20 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW EXIT LIGHTING REQ`D
 AT REAR OF STORE.GOING INTO STORAGE AND
 EXIT TO REAR.
  
 2)NOTE: PLEASE SHOW DIMMER BANK LOCATION
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372
  
 PLANS WOULD HAVE PASSED WITH PROVISO
 BUT WERE COMING BACK FOR OTHER COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-20 Cont ID  
Sent By mcarsill Date 2000-09-20 Time 10:51 Rev Time 0.00
Received By mcarsill Date 2000-09-20 Time 10:50 Sent To  
Notes
2001-01-08 00:00:001) FIRE SPRINKLER SYSTEM INSTALLATION
 REQUIRES SEPARATE PLANS AND PERMITS.
 PLAN DOES SHOW FIRE SPRINKLER HEAD
 LAYOUT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-15 Cont ID  
Sent By mcarsill Date 2000-08-15 Time 16:19 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) FABRIC AWNING TO BE FIRE RETARDANT.
 2) PROVIDE FIRE ALARM SYSTEM PLANS AND
 PERMIT FOR FIRE ALARM EQUIPMENT SHOWN
 ON DRAWINGS.
 3) INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL BE CLASS A OR B. ON 8.15.00,
 WRITER SPOKE TO BOB FLOOD OF REG
 REFERENCE THE PLANS.
 4) TRAVEL DISTANCE PERMITTED UNDER THE
 PREVAILING FIRE CODE ALLOWS FOR ONLY
 150 FEET IF SPRINKLERS ARE PRESENT. THIS
 IS MORE STRINGENT THAN THE 250 FEET
 REFERENCED.
 5) TWO ADDITIONAL EXIT SIGNS NEEDED TO
 DIRECT PERSONS TO REAR EXIT.
 6) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST, NOT
 MORE THAN 50 PERCENT OF EXIT ACCESS IS
 PROVIDED THROUGH STOCKROOM, DOOR
 LEADING TO STOCKROOM CANNOT BE SUBJECT
 TO LOCKING, AN AISLE OF AT LEAST 44"
 BE PROVIDED, AND THIS AISLE IS TO
 BE MAINTAINED.
 7) PORTABLE FIRE EXTINGUISHERS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-16 Cont ID  
Sent By cthirben Date 2000-08-16 Time 13:36 Rev Time 1.00
Received By cthirben Date 2000-08-16 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-20 Cont ID  
Sent By tlarge Date 2000-09-20 Time 17:48 Rev Time 0.50
Received By tlarge Date 2000-09-20 Time 17:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 16:21 Rev Time 0.50
Received By tlarge Date 2000-08-17 Time 15:49 Sent To  
Notes
2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 2)A H.C.ACCESSIBLE DRESSING ROOM SHALL
 BE PROVIDED PER FACBC SEC.4.1.3.(21) AND
 COMPLY W/FACBC SEC.4.35. .
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.