Plan Review Details - Permit 00080304
Plan Review Stops For Permit 00080304
Review Stop FS  
Rev No 1 Status P Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-09 Time 18:27 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) ENTIRE SPACE TO BE PROTECTED BY
 FIRE SPRINKLERS. THIS INCLUDES ALL
 ELECTRICAL, MECHANICAL, AND SERVICE
 ROOMS.
 2) WATER CURTAIN PROVIDED TO PROTECT
 ESCALATOR OPENING TO COMPLY WITH
 NFPA 13 REQUIREMENTS. SPRINKLER HEADS
 TO BE NO MORE THAN SIX FEET APART.
 3) FIRE SPRINKLER PROTECTION REQUIRED
 UNDERNEATH ESCALATOR.
 4) NO FIRE SPRINKLER HEAD SHOWN IN
 ELEVATOR MACHINE ROOM.
 5) FIRE SPRINKLER SYSTEM INSTALLATION
 TO COMPLY WITH NFPA 13.