| Plan Review Stops For Permit 00080302 |
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-21 |
Time |
06:20 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-08-21 |
Time |
06:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-08 |
Time |
07:54 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-08-08 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FLOOR DRAINS ARE NOT PROPERLY VENTED. | | | CONNECT SEPARATELY TO THE VENTED BUILD- | | | DRAIN.SPC SEC.901.2.,908.2,TABLE 908.1. | | | | | | 2)A GATE VALVE IS REQD.ON THE DISCHARGE | | | PIPING OF THE SUMP PER SPC SEC.717.2. | | | | | | 3)SUMP SHALL BE VENTED PER SPC SEC.717.6 | | | | | | 4)CONNECTION TO THE BUILDING DRAINAGE | | | SYSTEM SHALL COMPLY W/SPC SEC.717.11. | | | | | | 5)PUMP SHALL BE LISTED AND COMPLY W/SPC | | | 303.1,303.3,303.5. | | | | | | 6)A MAIN STACK MIN.OF 3"IS REQD.PER SPC | | | 904.3. |
|
|
|