Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By tlarge Date 2000-08-21 Time 06:20 Rev Time 0.33
Received By tlarge Date 2000-08-21 Time 06:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By tlarge Date 2000-08-08 Time 07:54 Rev Time 0.75
Received By tlarge Date 2000-08-08 Time 06:21 Sent To  
Notes
2001-01-08 00:00:00FLOOR DRAINS ARE NOT PROPERLY VENTED.
 CONNECT SEPARATELY TO THE VENTED BUILD-
 DRAIN.SPC SEC.901.2.,908.2,TABLE 908.1.
  
 2)A GATE VALVE IS REQD.ON THE DISCHARGE
 PIPING OF THE SUMP PER SPC SEC.717.2.
  
 3)SUMP SHALL BE VENTED PER SPC SEC.717.6
  
 4)CONNECTION TO THE BUILDING DRAINAGE
 SYSTEM SHALL COMPLY W/SPC SEC.717.11.
  
 5)PUMP SHALL BE LISTED AND COMPLY W/SPC
 303.1,303.3,303.5.
  
 6)A MAIN STACK MIN.OF 3"IS REQD.PER SPC
 904.3.