| Plan Review Stops For Permit 00080291 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-11-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-09 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-09 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************NOTE ******************* | | | | | | 1)NOTE: PLANS STILL NEED TO BE REVISED | | | BEFORE FINAL FOR OTHER NOTES FROM FIRST | | | REVIEW. | | | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-06 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-06 |
Time |
07:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************* PROVISO ***************** | | | | | | | | | SEE ORIG NOTES, PLEASE SUBMIT AND SHOW | | | ALL INFORMATION REQUESTED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-09-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-14 |
Time |
21:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-14 |
Time |
21:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | NEW EQUIPMENT BEING INSTALLED. MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9. 215-5 | | | | | | 2)NOTE: PLEASE INCLUDE NEW BLDG. STEEL | | | AS PART OF THE GROUNDING ELECTRODE | | | SYSTEM. 250-50 | | | | | | 3)NOTE: PLEASE NOTE THAT MORE THAN 50% | | | OF NEW BLDG.SMOKE DETECTORS WILL BE | | | REQ`D INSIDE AND OUTSIDE EXISTING SLEEP- | | | -ING ROOMS. PER NFPA-72 2-2.1.1.1 ,97 | | | BLDG. CODE AND FL. STATUES. | | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | | OUTSIDE ALL NEW SLEEPING ROOMS. | | | | | | 4)NOTE: PLEASE NOTE THAT ALL EXISTING | | | BATHS AND KITCHEN COUNTERSPACE, AND | | | GARAGE OUTLETS WILL NEED TO MEET 210-8 | | | OF THE NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLANS WOULD HAVE PASSED WITH A | | | PROVISO BUT WERE COMING BACK FOR | | | BLDG COMMENTS. IF THERE ARE ANY QUESTION | | | -S PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-01-31 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-01-31 |
Time |
16:58 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2001-01-31 |
Time |
16:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-09-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-09-16 |
Time |
07:25 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-09-16 |
Time |
07:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-09-14 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-09-14 |
Time |
16:28 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-09-14 |
Time |
21:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT REVISED SANITARY RISER PRIOR TO | | | PLBG.INSPECTION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-10-13 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-10-13 |
Time |
12:47 |
Rev Time |
2.00 |
| Received By |
fknapp |
Date |
2000-10-13 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | **************PROVISO******************* | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COMPLETE COPIES OF | | | SBCCI OR METRO DADE PRODUCT APPROVAL | | | FOR NEW EXTERIOR DOORS. | | | | | | 2)PROVIDE PRODUCT APPROVAL FOR ROOF | | | COVERING UNDER SEPARATE PERMIT. | | | | | | 3)PROVIDE STORM PANEL INFORMATION UNDER | | | SEPARATE PERMIT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-09-14 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-09-14 |
Time |
16:19 |
Rev Time |
4.00 |
| Received By |
fknapp |
Date |
2000-09-14 |
Time |
09:33 |
Sent To |
P |
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | *************BUILDING UNSAT************* | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COMPLETE COPIES OF | | | SBCCI OR METRO DADE PRODUCT APPROVALS | | | FOR: | | | ALL NEW EXTERIOR DOORS AND WINDOWS | | | MULLIONS | | | ROOF COVERING | | | STORM PANELS WITH INSTALLATION | | | SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS TO BE USED. | | | | | | 2)PROVIDE OWNER/AGENT SIGNATURE ON | | | ENERGY CALCULATIONS. | | | | | | 3)PROVIDE EGRESS WINDOW IN MASTER BR | | | THAT COMPLIES WITH 1997 SBC 1005.4 | | | | | | 4)BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH CO.,THE PERMIT PLANS STAMPED BY | | | THEM AND THE RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-08-10 |
Time |
12:04 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|