Plan Review Details - Permit 00080288
Plan Review Stops For Permit 00080288
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-10-17 Cont ID  
Sent By dpalmer Date 2000-10-17 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2000-10-17 Time 20:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-22 Cont ID  
Sent By dpalmer Date 2000-08-22 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2000-08-22 Time 12:46 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT*****************
  
 1)NOTE: PLEASE HAVE BLDG. STEEL AS PART
 OF THE GROUNDING ELECTRODE SYSTEM PER
 250-50
  
 2)NOTE: PLEASE SEE THAT PANEL "A" IS NOT
 COMPLETE. WIRE/KVA/BRKR ETC.
  
 3)NOTE: PLEASE SHOW CLARIFICATION ON
 HOW MANY A/C SYSTEMS ARE GOING TO BE
 INSTALLED. PANEL SCHEDULES SHOW 3 UNITS
 AND PLANS SHOW 4 UNITS??
 ADJUST LOAD CALCULATIONS.
  
 4)NOTE: PLEASE SEE PANEL "B" PLEASE
 NOTE THAT ALL WIRE SIZES MUST BE SUFF.
 FOR LOADS SHOWN. 310-16
  
 5)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3
  
 6)NOTE: PLEASE SEE 210-52-C-3 FOR
 KITCHEN ISLAND RECPECTS.
  
 7)NOTE: PLEASE SEE 210-52 FOR OUTLET
 SPACING.
  
 8)NOTE: PLEASE BATH BY FRONT ENTRANCE
 FOR OUTLET IN BATH TO BE INSTALLED
 NEXT TO SINK PER 210-52D
  
 9)NOTE: PLEASE SHOW OUTLETS IN ALL BATHS
 AS GFI/GFI PROTECTED.PER 210-8
  
 10)NOTE: PLEASE SHOW AND GIVE MORE
 DETAIL ON ROOM NEXT TO GARAGE. ROOM IS
 SHOWN BUT NOT LABELED. NO ELECTRICAL
 SHOWN FOR LIGHTING OR GFI.???
  
 11)NOTE: PLANS CAN NOT BE ACCEPTED WITH
 CHANGES HAND DRAWN IN UNLESS EACH
 CHANGE IS SIGNED AND DATED BY ARCH.OR
 ENG. OF RECORD. THIS IS A STATE STATUE.
  
 12)NOTE: THE AIC RATING OF 22,000IS
 SHOWN. IS THIS FOR MAIN DISCONNECTS? OR
 IS THIS FOR PANELS ALSO? PLEASE HAVE THE
 AIC RATINGS LISTED ON EACH PANEL SCHED-
 -ULE AND DISCONNECT ALONG WITH INFORMAT-
 -ION FOR PANEL SPECS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-16 Cont ID  
Sent By cthirben Date 2000-08-16 Time 15:55 Rev Time 1.00
Received By cthirben Date 2000-08-16 Time 15:55 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 *PROVIDE ADDITIONAL INFORMATION ON THE
 EXHAUST FANS FOR THE BATHROOMS...
 *INDICATE VENTILATION FOR THE GAS WATER
 HEATER AND CLOTHES DRYER.....
 *INDICATE THE SIZES OF THE CONDENSATE
 AND REFRIDGERATED LINES TO THE UNITS....

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-11-02 Cont ID  
Sent By tlarge Date 2000-11-02 Time 09:57 Rev Time 0.25
Received By tlarge Date 2000-11-02 Time 09:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-20 Cont ID  
Sent By tlarge Date 2000-10-20 Time 19:28 Rev Time 0.65
Received By tlarge Date 2000-10-20 Time 19:28 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 1)SUBMIT MANUF.DATA ON STEAM GENERATOR.
 UNIT SHALL BE LISTED.SPC SEC.303.5,
 503.3.
  
 2)SUBMIT REVISED SANITARY RISER PRIOR TO
 PLUMBING INSPECTION.COUNTYWIDE AMENDMENT
 TO SPC SEC.104.2.1.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-11 Cont ID  
Sent By tlarge Date 2000-08-11 Time 06:14 Rev Time 0.33
Received By tlarge Date 2000-08-11 Time 06:04 Sent To  
Notes
2001-01-08 00:00:00SUBMIT REVISED SANITARY RISER THAT
 COMPLIES W/SPC IN ALL RESPECTS.THERE ARE
 TOO MANY VIOLATIONS ON THE SANITARY
 RISER TO LIST.
  
 2)GAS WATER HEATER SHALL COMPLY W/SGC
 SEC.402.4 FOR COMBUSTION AIR REQS.& SGC
 SEC.402.7 FOR INSTALLATION REQS.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2000-12-06 Cont ID  
Sent By jgomez Date 2000-12-06 Time 18:42 Rev Time 0.33
Received By jgomez Date 2000-12-06 Time 18:42 Sent To  
Notes
2001-01-08 00:00:00STRUCTURAL REVIEW APPROVED.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-11-13 Cont ID  
Sent By jgomez Date 2000-11-13 Time 10:47 Rev Time 0.50
Received By jgomez Date 2000-11-13 Time 10:47 Sent To  
Notes
2001-01-08 00:00:00REVISION OF FOOTINGS AND ROOF FRAMING.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-10-19 Cont ID  
Sent By jgomez Date 2000-10-19 Time 10:55 Rev Time 3.00
Received By jgomez Date 2000-10-19 Time 10:55 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FRAMING DETAILS FOR
 THE THREE ARCHED WINDOWS MULLED
 TOGETHER BY THE BREAKFAST AREA. SEE
 EXTERIOR ELEVATIONS.
 2-SPECIFY SAFETY GLASS BY MASTER BATHRM
 SEC. 2405.2 SBC 1997.
 3-REVISE SIZE AND AMOUNT OF CEILING FANS
 SEE ELECTRICAL PLAN AND TABLE 6-6 OF
 FLORIDA ENERGY EFFICIENCY CODE FOR
 BUILDING CONSTRUCTION. 1997 EDITION.
 4-PROVIDE COMPLETE SPECIFICATIONS/DETAIL
 FOR CEILING CONSTRUCTION AT PORTE
 COCHERE, ENTRY AND REAR PORCHES.
 NOTE: INCLUDE FASTENER TYPES AND
 SPACING.
 SECTION 2504 SBC 1997.
 5-PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR SCREEN ENCLOSURE IN
 COVERED PATIO BY MASTER BEDROOM, UNDER
 A SEPARATE PERMIT.
 NOTE: INCLUDE SCREENED CEILING AREA.
 6-PROVIDE UL LISTING AND COMPLETE
 COMPLETE SPECIFICATIONS FOR STEAM
 GENERATOR.
 7-PROVIDE COMPLETE FRAMING DETAILS/
 SECTIONS AND SPECIFICATIONS FOR
 CONSTRUCTION OF KNEE WALLS AND CUPOLAS
 SECTION 104.2.2 CITY AMENDMENTS.
 8-PROVIDE COMPLETE SECTION/DETAIL FOR
 ATTACHMENT OF WINDOWS TO STEEL COLUMN
 IN MASTER BATHROOM. SECTION 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 9-ROOF FRAMING PLAN:
 -PROVIDE A CLEAR ANCHOR SCHEDULE FOR
 WOOD TO WOOD CONNECTIONS AND KEY PLAN.
 -CLARIFY WHAT TYPEOF CONNECTORS ARE
 THE RT20 AND RT22?. ARE THEY CUSTOM
 MADE?. (UNABLE TO FIND THEM IN THE
 SEMCO CATALOGUE).
 10-PROVIDE MORE INFORMATION FOR THE BBQ.
 IS IT MASONRY OR PRE-MANUFACTRED?
 BE SPECIFIC AND PROVIDE THE REQUIRED
 INFORMATION, SPECIFICATIONS, DETAILS.
 SECTION 104.2.1 CITY AMENDMENTS.
 11-PROVIDE PRODUCT APPROVAL FOR:
 -GARAGE DOORS (DESIGN PRESSURES OF DOOR
 SUBMITTED DOESN'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT)
 -3'-0" X 9'-0" OUTSWING ENTRY DOORS
 WITH SIDELITES ASSEMBLY.
 -4 PANELS FRENCH DOORS (OUTSWING)
 -FRENCH DOORS WITH TRANSOM ABOVE
 ASSEMBLY.
 -FRENCH DOOR WITH SIDELITE ASSEMBLY.
 12-SEE COMMENTS ON PLANS. INCLUDING
 COMMENTS BY THE OTHER TRADES.
  
  
  
  
  
  
  
  
 NOTE:
  
 -IF YOU HAVE ANY QUESTION, PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-06 Cont ID  
Sent By jgomez Date 2000-09-06 Time 14:52 Rev Time 5.00
Received By jgomez Date 2000-09-06 Time 14:52 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-LEFT HAND SIDE ELEVATION EXCEEDS THE
 PERCENTAGE OF OPENINGS ALLOWEDBY
 TABLE 600, SBC 1997.
 2-PROVIDE ATTIC ACCESS AT PORTE COCHER,
 FOYER, RIGHT WING GARAGE AREA AND ALL
 CUPOLAS. SECTION 2309.6 SBC 1997.
 -PROVIDE COMPLETE METAL FRAMING DETAILS
 AND SECTIONS AT ATTIC SPACES WITH AHU
 EQUIPMENT. INCLUDING AHU'SANCHORING
 SPECIFICATIONS AND DETAILS.
 3-ARCHITECT NEED TO DATE DRAWINGS AT
 AT THE TIME OF SEALING THEM. FLORIDA
 STATUTES, CHAPTER 481.
 4-PROVIDE A SITE PLAN WITH DIMENSIONS OR
 SURVEY WITH BUILDING LAYOUT.
 -NOTE: SURVEYOR TO PROVIDE ORIGINAL
 SIGNATURE AND DATE ON ANY DOCUMENT TO
 BE FILED FOR PUBLIC RECORDS. CHAPTER
 471 OF FLORIDA STATUTES.
 5-ARCHITECT TO REVISE/UPDATE ALL DWGS AS
 REQUIRED. USE SBC 1997 AND FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION. GET FAMILIAR WITH THIS
 CODES AND REFERENCE THE APPROPIATE
 STANDARDS AS DONE IN THESE CODES.
 -SEE PLANS FOR COMMENTS.
 6-PROVIDE COMPLETE FRAMING DETAILS AT
 ARCHED WINDOWS MULLED TOGETHER AT
 BREAKFAST AREA. SEC. 104.2.2 CITY
 AMENDMENTS.
 7-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SECTION 2405.2 SBC 1997. SEE PLANS.
 8-PROVIDE MINIMUM ONE BATHROOM WITH A
 DOOR THAT ALLOWS 29" MIN. CLEAR OPEN'G
 SECTION 11 OF FLORIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUCTION,1997 ED
 9-PROVIDE SIZE OF CEILING FANS. SEE
 TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION,1997 ED
 10-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAILS FOR CEILING CONSTRUCTION AT
 PORTE COCHER, ENTRY AND REAR PORCHES.
 INCLUDING FASTENER TYPES AND SPACING.
 SECTION 2504 SBC 1997.
 11-PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR SCREEN ENCLOSURE IN
 COVERED PATIO BY MASTER BEDROOM.
 NOTE: INCLUDE SCREENED CEILING.
 SECTION 104.2.2 CITY AMENDMENTS.
 12-PROVIDE COMPLETE SECTION/DETAIL THRU
 CHIMNEY. SPECIFY ALL CONNECTORS.
 SECTION 104.2.2 CITY AMENDMENTS.
 13-PROVIDE COMPLETE FRAMING DETAILS/
 SECTIONS AND SPECIFICATIONS FOR
 CONSTRUCTION OF KNEE WALLS AND CUPOLAS
 SECTION 104.2.2 CITY AMENDMENTS.
 14-PROVIDE COMPLETE SECTION/DETAIL FOR
 ATTACHMENT OF WINDOWS TO STEEL COLUMN
 IN MASTER BATHROOM. SECTION 104.2.2
 15-ROOF FRAMING PLAN:
 -PROVIDE ANCHOR SCHEDULE FOR WOOD TO
 WOOD CONNECTIONS.
 -SHOW CRICKET LOCATIONS AND CONSTRUCT'N
 SECTION 104.2.2 CITY AMENDMENTS.
 16-PROVIDE MORE INFORMATION FOR BBQ
 CONSTRUCTION. IS IT MASONRY OR PRE-
 MANUFACTURED. COMPLY WITH SECTION 2808
 OR 2114.4 AS REQUIRED.
 17-PROVIDE THE DESIGN PRESSURES THAT
 WERE CALCULATED FOR EXTERIOR OPENINGS
 FOR GARAGE DOORS.AND FOR THOSE OPENIGS
 NOT SHOWN ON EXTERIOR ELEVATIONS.
 NOTE: EXPLAIN WHY THE GARAGE DOOR
 DESIGN PRESSURES IN PRODUCT APPROVAL
 DRAWINGS WERE ERASED OR DELETED.
 18-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH SIDELITE ASSEMBLY, GARAGE
 DOORS, 4 PANELS FRENCH DOORS, FRENCH
 DOORS WITH TRANSOM ABOVE ASSEMBLIES,
 ROUND WINDOWS, FIXED WINDOWS LARGER
 THAN THE ONE SHOWN IN PRODUCT APPROVAL
 SUBMITTED AND LIVING ROOM LARGE WINDOW
 ASSEMBLY.
 19-SEE COMMENTS BY OTHER TRADES.
 20-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. MEAN
 ROOF HEIGHT IS +/- 33'-8".
  
  
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER ALL
 REVISIONS ARE DONE TO ORIGINAL DRAWINGS
 IN ORDER TO EXPEDITE THE REVIEW PROCESS
 -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CALL JULIO GOMEZ AT 659-8096
 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-10 Cont ID  
Sent By gjoyce Date 2000-08-10 Time 15:17 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***