Plan Review Details - Permit 00080255
Plan Review Stops For Permit 00080255
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-01-03 Cont ID  
Sent By jwitmer Date 2001-01-03 Time 14:47 Rev Time 0.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION: DELETE DENTIST CHAIRS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-09-11 Cont ID  
Sent By hpiskura Date 2000-09-11 Time 09:47 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By dpalmer Date 2000-08-24 Time 06:47 Rev Time 0.00
Received By dpalmer Date 2000-08-24 Time 06:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-10 Cont ID  
Sent By mcarsill Date 2000-08-10 Time 08:47 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) DEMOLITION OPERATIONS TO COMPLY
 WITH NFPA 241, THE STANDARD FOR
 BUILDINGS UNDER CONSTRUCTION, ALTERATION
 AND DEMOLITION OPERATIONS.
 2) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ LIFE SAFETY CODE 1985
 EDITION INSTEAD OF LIFE SAFETY CODE
 1997 EDTION.
 3) PROVIDE FIRE ALARM SYSTEM DRAWINGS
 FOR FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. A SEPARATE PLAN AND PERMIT IS
 REQUIRED.
 4) PROVIDE PLAN AND PERMIT FOR ANY FIRE
 SPRINKLER SYSTEM REMODEL DONE TO THE
 EXISTING FIRE SPRINKLER SYSTEM IN
 TENANT SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-07 Cont ID  
Sent By cthirben Date 2000-08-07 Time 11:31 Rev Time 0.00
Received By cthirben Date 2000-08-07 Time 11:32 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 *FAN SHUT-DOWN BY SMOKE DETECTOR WITH
 NOTIFICATION BY BUILDING FIRE ALARM
 SYSTEM OR RIED TO HORN AND STROBE AS PER
 NFPA 90A 4.4.4.2 OR 4.4.4.3.......
 *PROVIDE EER RATING OF AHU PER FLORIDA
 ENERGY EFFICIENCY CODE...
 *SEPERATE PERMIT REQUIRED FOR MEDICAL
 GAS, SUBMIT PLANS AT TIME OF APPLLICA-
 TION......

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-21 Cont ID  
Sent By tlarge Date 2000-09-21 Time 10:08 Rev Time 1.25
Received By tlarge Date 2000-09-21 Time 10:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-20 Cont ID  
Sent By tlarge Date 2000-08-20 Time 08:43 Rev Time 2.00
Received By tlarge Date 2000-08-20 Time 06:51 Sent To  
Notes
2001-01-08 00:00:001)THE NUMBER OF REQUIRED MINIMUM PLUMB-
 ING FIXTURES SHALL COMPLY W/SPC TABLE
 407.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.AN ADDITIONAL WATER
 CLOSET AND LAVATORY IS REQD.FOR THE
 FEMALES.
  
 2)H.C.DRINKING FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3,4.15.PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BEND-
 ING OR STOOPING.
  
 3)SUBMIT MANUF.SHEETS FOR AUTO PROCESSOR
 INFORMATION REQD.ON TYPES AND AMOUNTS OF
 CHEMICALS USED.A NEUTRALIZINGTANK MAY
 BE REQD.PER SPC SEC.801.4.
  
 4)SHT.P-2.SIZE THE COMPRESSED AIR
 DIAGRAM.INCLUDE BRANCHES TO CHAIRS.
  
 5)SHT.P-2-INDICATE SIZE OF BRANCHES TO
 CHAIRS.
  
 6)AIR COMPRESSOR INTAKE SHALL BE LOCATED
 WHERE NO CONTAMINATION FROM VACUUM
 SYSTEM DISCHARGES IS ANTICIPATED.NFPA
 99 SEC.4-5.1.1.3.
  
 7)ACCESSIBLE CLEANOUTS ARE REQD.IN THE
 VACUUM SYSTEM PER NFPA 99 SEC.4-5.2.2.1.
  
 8)SUBMIT WATER RISER DIAGRAM FOR ALL
 PLUMBING WORK BEING INSTALLED.
  
 9)SEPARATE PERMIT REQD.FOR MEDICAL GAS.
 SUBMIT PLANS,MANUF.INSTALLATION REQS.ETC
 AT TIME OF APPLICATION.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.