Plan Review Details - Permit 00080152
Plan Review Stops For Permit 00080152
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-14 Cont ID  
Sent By dpalmer Date 2000-09-14 Time 20:01 Rev Time 0.00
Received By dpalmer Date 2000-09-14 Time 20:01 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: SINCE FIRST REVIEW YOU ARE NOW
 SHOWING A COMPLETE NEW SERVICE RISER.
 PLEASE SUBMIT AIC RATINGS OF EQUIPMENT
 MAINS AND PANELS BEING INSTALLED.
 PER 110-9 AND 215-5
  
 2)NOTE: PLEASE SUBMIT COMPLETE REVISED
 PANEL SCHEDULES.215-5
  
 3)NOTE: PLEASE CLARIFY WIRE FEEDING
 125A PANEL. SHOWS 3# L.??
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE FINAL ELECTRICAL
 INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-14 Cont ID  
Sent By dpalmer Date 2000-08-14 Time 16:30 Rev Time 3.00
Received By dpalmer Date 2000-08-14 Time 16:30 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 OF EXISTING AND NEW. 220-3-C-1
  
 2)NOTE: PLEASE LIST THE BATH(S) CIRCUITS
 PER 210-11-C-3 ON PANLE SCHEDULE.
  
 3)NOTE: PLEASE MAKE NOTE AS TO ANY NEW
 BLDG. STEEL TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM 250-50
  
 4)NOTE: PANEL'A' SHOWS AS BEING 125AMP?
 RISER DIAGRAM SHOWS AS 200AMP.??
 PLEASE CORRELATE TO WHICH ONE IS CORRECT
 SHOW SIZE OF EXISTING SERVICE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESITONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-01-22 Cont ID  
Sent By jleech Date 2001-01-22 Time 07:13 Rev Time 0.25
Received By jleech Date 2001-01-22 Time 07:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-11 Cont ID  
Sent By cthirben Date 2000-08-11 Time 10:57 Rev Time 1.00
Received By cthirben Date 2000-08-11 Time 10:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 06:08 Rev Time 0.30
Received By tlarge Date 2000-08-10 Time 05:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-09-22 Cont ID  
Sent By drunnels Date 2000-09-22 Time 08:39 Rev Time 1.00
Received By sgraham Date 2000-09-22 Time 08:39 Sent To  
Notes
2001-01-08 00:00:00IMPACT FEES DUE
 RADON FEES DUE $13.28

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-09-22 Cont ID  
Sent By drunnels Date 2000-09-22 Time 08:38 Rev Time 0.00
Received By drunnels Date 1900-09-22 Time 08:33 Sent To  
Notes
2001-01-08 00:00:00REVIEWED 8/23/00 BY TM NOT ENTERED DR

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-09 Cont ID  
Sent By gjoyce Date 2000-08-09 Time 08:30 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved