Plan Review Details - Permit 00080142
| Plan Review Stops For Permit 00080142 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-12 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-12 |
Time |
19:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES REDLINED ON PLANS FOR AS-BUILTS | | | BEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-14 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-14 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ALL EQUIPMENT BEING INSTALLED. MAINS/ | | | PANELS MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT.110-9/215-5 | | | | | | 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. 210-8-A-6 | | | | | | 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS AND ON | | | EACH LEVEL OF MULTI-LEVEL RES. | | | | | | 4)NOTE: PLEASE SEE 210-52-C-3 FOR REQ`D | | | PENINSULAR RECEPT. | | | | | | 5)NOTE: PLEASE LABEL ALL GARAGE REC`S | | | AS GFI/GFI PROTECTED. 210-8 | | | | | | 6)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | SYSTEM. SEE 250-50 FOR REQ`D POINTS OF | | | GROUND.ALSO INCLUDE SIZE OF GROUNDING | | | ELECTRODE SIZE PER 250-66 | | | | | | 7)NOTE: PLEASE SHOW WIRE SIZES FOR FEED- | | | -ERS FROM METER TO MAIN PANEL. | | | | | | 8)NOTE ;PLEASE INCLUDE THE REQ`D DEDI- | | | -CATED BATH(S) CIRCUIT(S) PER 210-11-C-3 | | | ON PANEL SCHEDULE. | | | | | | 9)NOTE: PLEASE SEE LOAD CALCULATIONS FOR | | | HEAT KW., SHOWS 56% MUST BE TYPE -O | | | LOAD SHOWN IS CORRECT., | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-05-19 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2001-05-19 |
Time |
08:18 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2001-05-19 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2001-05-19 00:00:00 | RIVISON OK PLANS IN C BIN |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-11 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-11 |
Time |
10:55 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2001-05-19 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2001-05-19 00:00:00 | REVISION OK PLANS IN C BIN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-10 |
Time |
05:54 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-08-10 |
Time |
05:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2000-09-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-09-21 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK PER TONY MARCELLO 9-20-00 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-09 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-08-09 |
Time |
08:00 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|