Plan Review Details - Permit 00080142
Plan Review Stops For Permit 00080142
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 19:01 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 19:01 Sent To  
Notes
2001-01-08 00:00:00NOTES REDLINED ON PLANS FOR AS-BUILTS
 BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-14 Cont ID  
Sent By dpalmer Date 2000-08-14 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2000-08-14 Time 15:24 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL EQUIPMENT BEING INSTALLED. MAINS/
 PANELS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT.110-9/215-5
  
 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210-8-A-6
  
 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND ON
 EACH LEVEL OF MULTI-LEVEL RES.
  
 4)NOTE: PLEASE SEE 210-52-C-3 FOR REQ`D
 PENINSULAR RECEPT.
  
 5)NOTE: PLEASE LABEL ALL GARAGE REC`S
 AS GFI/GFI PROTECTED. 210-8
  
 6)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM. SEE 250-50 FOR REQ`D POINTS OF
 GROUND.ALSO INCLUDE SIZE OF GROUNDING
 ELECTRODE SIZE PER 250-66
  
 7)NOTE: PLEASE SHOW WIRE SIZES FOR FEED-
 -ERS FROM METER TO MAIN PANEL.
  
 8)NOTE ;PLEASE INCLUDE THE REQ`D DEDI-
 -CATED BATH(S) CIRCUIT(S) PER 210-11-C-3
 ON PANEL SCHEDULE.
  
 9)NOTE: PLEASE SEE LOAD CALCULATIONS FOR
 HEAT KW., SHOWS 56% MUST BE TYPE -O
 LOAD SHOWN IS CORRECT.,
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
  
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-05-19 Cont ID  
Sent By hmoser Date 2001-05-19 Time 08:18 Rev Time 0.33
Received By hmoser Date 2001-05-19 Time 08:18 Sent To  
Notes
2001-05-19 00:00:00RIVISON OK PLANS IN C BIN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-11 Cont ID  
Sent By cthirben Date 2000-08-11 Time 10:55 Rev Time 0.33
Received By hmoser Date 2001-05-19 Time 08:11 Sent To  
Notes
2001-05-19 00:00:00REVISION OK PLANS IN C BIN

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 05:54 Rev Time 0.30
Received By tlarge Date 2000-08-10 Time 05:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-09-21 Cont ID  
Sent By rmcdouga Date 2000-09-21 Time 16:09 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER TONY MARCELLO 9-20-00

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-09 Cont ID  
Sent By gjoyce Date 2000-08-09 Time 08:00 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***