Plan Review Details - Permit 00080005
Plan Review Stops For Permit 00080005
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-29 Cont ID  
Sent By drunnels Date 2000-08-29 Time 08:56 Rev Time 1.00
Received By drunnels Date 2000-08-29 Time 08:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-25 Cont ID  
Sent By drunnels Date 2000-08-25 Time 16:25 Rev Time 1.00
Received By drunnels Date 2000-08-25 Time 16:25 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION
  
 *************NOTE********************
 SIGNS TO BE UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By drunnels Date 2000-08-10 Time 12:37 Rev Time 1.00
Received By drunnels Date 2000-08-10 Time 12:36 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT FIRE SPRINKLER PLANS AND
 APPLICIATION FOR PERMIT. FIRE SPRINKLER
 PERMIT MUST BE ISSUED PRIOR TO BUILDING
 PERMIT ISSURANCE.
 2.PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR WINDOWS AND DOORS
 FOR STOREFRONT. METRO DADE COUNTY OR
 SBCCI SSTD12-96.
 3.SIGNS REQURIES SEPERATE PERMITS.
 4.NOTE: ALL WOOD BLOCKING TO BE FIRE
 RETARDANT.
 5. TITLE SHEET- PROJECT DATA-THE STORAGE
 ROOM ON THE SECOND FLOOR IS A SEPERATE
 OCCUPANCY (USE GROUP)SINCE IT IS NOT
 ATTACHED TO MAIN TENANT SPACE. THIS AREA
 REQUIRES 2 HOUR FIRE SEPERATION. PROVIDE
 UL ASSEMBLY NUMBER AND BOTH SIDES MUST
 BE FINISHED.
 6.DEMIZING WALL-GENERAL NOTE ON SHEET
 A101 READS AS IF TENANT SIDE ONLY
 COMPLETED ONLY-PARTITION DETAIL CALLS
 FOR A COMPLETED ASSEMBLY FOR 1 HOUR
 FIRE RATED CONSTRUCTION- BOTH SIDES MUST
 BE COMPLETED PRIOR TO C.O. BEING ISUED.
 7.TITLE SHEET-PROJECT DATA
 A)AMEND LSC 1991 TO 1985 NFPA 101
 B)AMEND 1994 SBC TO 1997 SBC WITH
 1999 CITY AMENDMENTS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-11-14 Cont ID  
Sent By dpalmer Date 2000-11-14 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2000-11-14 Time 17:42 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 PLEASE SEE COMMENTS FROM FIRST TWO RE-
 -VIEWS.
  
 1)NOTE: PLEASE HAVE NOTE FOR COLOR COD-
 -ING OF FEEDERS REFLECT LOCAL CODE.
 PER 215. BROWN,PURPLE,YELLOW
  
 2)NOTE: PLEASE SEE SHEET E-1. METAL
 GRATE SHOWN FOR CLOSET NEXT TO TRANS-
 -FORMER ROOM. SEE 450-21B FOR REQ`MENTS
 PLEASE MAKE CORRECTION FOR ACTUAL
 INSTALLATION ON JOBSITE.
  
 PLEASE MAKE CHANGES BEFORE C.O.
 PLEASE SUBMIT FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-28 Cont ID  
Sent By dpalmer Date 2000-08-28 Time 10:15 Rev Time 0.00
Received By dpalmer Date 2000-08-28 Time 10:04 Sent To  
Notes
2001-01-08 00:00:00************** REDLINED **************
  
 1)NOTE: COLOR CODING FOR FEEDERS IS NOT
 CORRECT. FIRST REVIEW REFERS TO LOCAL
 AMENDMENTS FOR FEEDER COLOR CODING FOR
 277/480.
  
 2)NOTE: ALSO PLEASE SEE 450-21-B FOR
 THE EXCEPTION ON TRANSFORMER INSTALLAT-
 -ION REQ`MENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By dpalmer Date 2000-08-10 Time 12:48 Rev Time 0.00
Received By dpalmer Date 2000-08-10 Time 12:48 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS
 SHOWN ON E-4. THE LOADS SHOWN FOR TRACK
 LIGHTING DOES NOT SEEM TO CORRELATE
 WITH LOADS SHOWN ON PANEL SCHEDULES OF
 LPA/LP AND NONE SHOWN ON "DP". PLEASE
 CLARIFY.
  
 2)NOTE: PLEASE SEE 450-9 AND 450-21
 OF NEC FOR REQ`MENTS FOR TRANSFORMER
 IN ELECTRICAL ROOM.
  
 3)NOTE: PLEASE SEE LOCAL CODE 210-50 FOR
 OUTLET SPACING IN STORAGE AREAS. EVERY
 20` OF UNENCUMBERED WALL SPACE.
 MALL STORAGE AREA SHOWN.
 4)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL
 EQUIPMENT/ PANELS AND DISCONNECTS.
 ALL MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT PER 110-9/ 215-5
  
 5)NOTE: PLEASE NOTE COLOR CODING FOR
 ALL FEEDERS PER LOCAL CODE 215
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW, IF THERE ARE ANY QUESTIONS
 PLEASE CALL,
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-29 Cont ID  
Sent By mcarsill Date 2000-08-29 Time 09:32 Rev Time 0.00
Received By mcarsill Date 2000-08-29 Time 09:31 Sent To  
Notes
2001-01-08 00:00:00DRAWINGS WERE RED-LINED ON AUGUST
 29, 2000, FOR FIRE SAFETY ITEMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-09 Time 16:49 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH TO BE CLASS A OR B.
 2) PROVIDE ILLUMINATED EXIT SIGNS AND
 EMERGENCY LIGHTING IN STORAGE ROOM 200.
 3) NO FIRE SPRINKLER SYSTEM DRAWINGS
 INCLUDED IN PLANS.
 4) ADDITIONAL EMERGENCY LIGHTING NEEDED
 IN FITTING ROOMS.
 5) RAMPS USED IN MEANS OF EGRESS TO
 COMPLY WITH NFPA 1985 EDITION.
 6) PLEASE INDICATE WHERE FIRE ALARM
 EQUIPMENT IS LOCATED ON THE PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2000-09-06 Cont ID  
Sent By ndenmark Date 2000-09-06 Time 10:10 Rev Time 0.50
Received By ndenmark Date 2000-09-06 Time 10:10 Sent To  
Notes
2001-01-08 00:00:00PLANS SUBMITTED/REVIEWED 9/6/00 G.C.
 CALLED TO HAVE SUBCONTRACTOR APPLY FOR
 MECH PERMIT W/ THESE PLANS. PLANS IN
 RACK WAITING

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2000-08-29 Cont ID  
Sent By drunnels Date 2000-08-29 Time 08:54 Rev Time 1.00
Received By drunnels Date 2000-08-29 Time 08:54 Sent To  
Notes
2001-01-08 00:00:00TO BE ISSUED UNDER SEPERATE PERMIT
 SEE PREVIOUS NOTES

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-08-28 Cont ID  
Sent By ndenmark Date 2000-08-28 Time 10:44 Rev Time 1.50
Received By ndenmark Date 2000-08-28 Time 10:44 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE CALCULATIONS
 SHOWING COMPLIANCE WITH 1997 SMC 501.2
 3. PROVIDE INFORMATION ON ROD SIZE FOR
 AHU MOUNTING DETAIL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-11 Cont ID  
Sent By cthirben Date 2000-08-11 Time 10:25 Rev Time 1.00
Received By cthirben Date 2000-08-11 Time 10:25 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 *PROVIDE DAMPERS LOCATION AND DETAIL AS
 PER 1997 SMC 610.1.2....
 *PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2....
 *PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89....
 *REQUIRE DUCT MATERIAL SCHDULE PER
 FLORIDE ENERGY CODE....
 *BATHROOMS VENTILATION REQUIRED AS PER
 1997 SMC 503.3.1.....
 *INDICATE SMOKE DETECTOR ON PLANS.
 NOTES:
 FAN SHUT-DOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION BY FIRE ALARM SYSTEM
 OR TIED-IN TO HORN AND STROBE AS PER
 NFPA 90A 4.4.4.2. AND 4.4.4.3.....

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-10-16 Cont ID  
Sent By tlarge Date 2000-10-16 Time 19:49 Rev Time 0.50
Received By tlarge Date 2000-10-16 Time 19:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 13:19 Rev Time 0.33
Received By tlarge Date 2000-08-29 Time 13:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 08:50 Rev Time 0.00
Received By tlarge Date 2000-08-29 Time 08:50 Sent To  
Notes
2001-01-08 00:00:00REFER TO STEP 2 FOR PLUMBING REVIEW
 STATUS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-25 Cont ID  
Sent By tlarge Date 2000-08-25 Time 12:32 Rev Time 0.75
Received By tlarge Date 2000-08-25 Time 12:06 Sent To  
Notes
2001-01-08 00:00:001)DOOR #109 CANNOT SWING INTO CLEAR
 FLOOR SPACE FOR ACCESSIBLE LAVATORY.
 FACBC SEC.4.22.2
  
 2)SIZE OF THE HANDICAP STALL SHALL
 COMPLY W/FACBC SEC.4.17.3.(MIN.83" WIDE)
  
 3)HEIGHT OF BENCH IN H.C.FITTING ROOM
 SHALL BE 17"-19" AFF,NOT 19"MIN.PER
 FACBC SEC.4.35.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-09 Cont ID  
Sent By tlarge Date 2000-08-09 Time 12:55 Rev Time 1.25
Received By tlarge Date 2000-08-09 Time 06:51 Sent To  
Notes
2001-01-08 00:00:001)DOOR #109 CANNOT SWING INTO CLEAR
 FLOOR SPACE FOR LAV.FACBC 4.22.2.
  
 2)BENCH IN HANDICAP FITTING ROOM SHALL
 COMPLY W/FACBC 4.35.4.(17-19" AFF).
  
 3)MAX.HT.TO TOP OF HANDICAP LAV.SHALL BE
 34",NOT MIN.SHT.TOO2.
  
 4)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.FOUNTAIN SHALL BE HANDICAP
 ACCESSIBLE AND COMPLY W/FACBC SEC.4.1.3
 (10)(A).PROVISIONS SHALL BE MADE FOR
 PEOPLE WHO HAVE TROUBLE BEMDING OR
 STOOPING.
  
 5)REVISE HT.OF T.P. DISPENSER.(19"TO
 CENTER,NOT 17".SHT.T002.
  
 6)MIRROR IN H.C.DRESSING ROOM SHALL
 COMPLY W/FACBC SEC.4.35.4.
  
 7) FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 8)SUBMIT UL ASSEMBLY NUMBER FOR FIRE
 SAFING DETAILS PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.4.(SHT.T005)
  
 9)FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO 4'PER SBC SEC.1204.2.
  
 10)DRY VENTS NOT PERMITTED ON SAN.SYSTEM
 PER SPC SEC.906.2.1.
  
 11)SIZE OF HANDICAP TOILET STALL SHALL
 COMPLY W/FACBC SEC.4.17.3.(MIN.83").