Plan Review Details - Permit 00071531
Plan Review Stops For Permit 00071531
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-12-22 Cont ID  
Sent By dpalmer Date 2000-12-22 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2000-12-22 Time 08:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-12-08 Cont ID  
Sent By dpalmer Date 2000-12-08 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2000-12-08 Time 14:32 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-07 Cont ID  
Sent By dpalmer Date 2000-08-07 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2000-08-07 Time 08:21 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR THE EXISTING SERVICE PER ART 220-3-C
 -1.
  
 2)NOTE: PROVIDE A REVISED PANEL SCHEDULE
 TO INCLUDE THE NEW CIRCUITS BEING ADDED
 AND THE REQ`D DEDICATED BATH CIRCUIT(S)
 PER 210-11-C-3.
  
 3)NOTE: PLEASE NOTE MISSING RECEPT.PER
 210-52
  
 4)NOTE: PLEASE NOTE THERE WILL BE A
 SMOKE DETECTOR REQ`D IN COMMON AREA OF
 ADDITION. PER NFPA-72 2-2.1.1.1
  
 5)NOTE: PLEASE SHOW THE REQ`D WP/GFI
 RECEPT. ON THE OUTSIDE OF ADDITION.
 PER 210-52E
  
 6)NOTE: PLEASE SHOW ALL NEW BLDG. STEEL
 AS BEING BONDED TO GROUNDING ELECTRODE
 SYSTEM. PER 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS.
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-12-12 Cont ID  
Sent By jleech Date 2000-12-12 Time 19:53 Rev Time 0.33
Received By jleech Date 2000-12-12 Time 19:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-08-08 Cont ID  
Sent By cthirben Date 2000-08-08 Time 09:27 Rev Time 1.00
Received By cthirben Date 2000-08-08 Time 09:25 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 NO MECHANICAL SUBMITTED FOR REVIEW ON
 PLANS....

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-12-12 Cont ID  
Sent By jleech Date 2000-12-12 Time 19:54 Rev Time 0.33
Received By jleech Date 2000-12-12 Time 19:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-09 Cont ID  
Sent By tlarge Date 2000-08-09 Time 06:20 Rev Time 0.30
Received By tlarge Date 2000-08-09 Time 06:06 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 A MIN.3"VENT THRU ROOF IS REQD.IF CONN-
 ECTING TO EXIST.BUILDING SEWER.SPC SEC.
 904.3.1.
  
 SHOWER SHALL BE A MIN.OF 30"WIDE AND
 1024 SQ.IN.FLOOR AREA.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.409.8.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-12-22 Cont ID  
Sent By rmcdouga Date 2000-12-22 Time 10:11 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-12-14 Cont ID  
Sent By rmcdouga Date 2000-12-14 Time 09:01 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)OWNER OR AGENT MUST SIGN ENERGY FORMS.
  
 2)SITE SPECIFIC PRODUCT APPROVALS FOR
 WINDOWS THAT WERE SUBMITTED MUST HAVE
 ORIGINALWET SIGNATURE, DATE AND
 IMPRESSION SEAL OF ENGINEER CERTIFYING
 THE PRODUCT CONFORMS TO 97 SBC AND THE
 SAME INFORMATION MUST BE PROVIDED BY AN
 ARCHITECT OR ENGINEER CERTIFYING THE
 PRODUCT IS SUFFICIENT FOR THE PROJECT
 SITE.
  
 3)PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE INDICATING SPECIFIC ANCHORS TO
 BE USED FOR STORM PANELS.
  
 4)PERCENTAGE OF WALL OPENINGS ALLOWED
 PER TABLE 600 OF 97 SBC ARE EXCEEDED ON
 SOUTH AND EAST ELEVATIONS. NOTE:THE
 HEIGHT OF THE WALL IS THE DISTANCE FROM
 FINISH FLOOR TO THE CEILING OF EACH
 STORY. PLEASE CORRECT.
  
 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR INSWING
 FRENCH DOORS.
  
 6)PROVIDE FASTENING DETAILS FOR ATTACH-
 ING PT WOOD BUCKS TO MASONRY AT WINDOW
 AND DOOR OPENINGS. SPECIFY THE TYPE OF
 ANCHOR AND ANCHOR SPACING.
  
 7)ONE OF THE WINDOWS SHOWN ON THE WEST
 ELEVATION IS NOT INDICATED ON THE FLOOR
 PLAN. PLEASE CLARIFY.
  
 8)DESIGN COMPLIANCE FORM MUST BE WET
 SIGNED,SEALED AND DATED BY AN ARCHITECT
 OR ENGINEER OR THE INFORMATION CAN BE
 LISTED ON THE PLANS AS NOTES. IF NOTED
 ON PLANS FORM IS NOT REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-08-15 Cont ID  
Sent By rmcdouga Date 2000-08-15 Time 12:38 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND COPY OF
 RECEIPT SUBMITTED TO CITY OF W.P.B.
 BUILDING DEPARTMENT.
  
 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR EACH
 SPECIFIC TYPE OF EXTERIOR WINDOW,DOOR,
 AND WINDOW MULLIONS TO BE USED.
  
 3)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR ROOFING
 MATERIALS OR SUBMIT WITH SEPARATE ROOF
 PERMIT APPLICATION.
  
 4)IMPACT PROTECTION IS REQUIRED ON ALL
 EXTERIOR GLAZED OPENINGS. COUNTYWIDE
 AMENDMENTS TO 97 STANDARD BUILDING CODE.
  
 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR STORM
 PANELS,KEY PLANS AND INSTALLATION
 SCHEDULE INDICATING SPECIFIC ANCHORS TO
 BE USED.
  
 6)PERCENTAGE OF ALLOWABLE WALL OPENINGS
 PER TABLE 600 IN 97 SBC ARE EXCEEDED ON
 ALL THREE ELEVATIONS.PLEASE CORRECT.
  
 7)PROVIDE 2 COMPLETED CITY OF W.P.B.
 DESIGN CERTIFICATION FORMS.
  
 8)PROVIDE STATE REQUIRED ENERGY
 CALCULATIONS INCLUDING MANUAL "J" FOR
 NEW ADDITION.
  
 9)SAFETY GLASS REQUIRED IN BATH ROOM
 WINDOW 97 SBC 2405.2
  
 10)PROVIDE CEILING HEIGHT ELEVATIONS FOR
 ADDITION AND EXISTING STRUCTURE.
  
 11)SPECIFY WIDTH OF FOOTINGS ON PLANS.
 BOTTOM OF FOOTING MUST BE A MINIMUM OF
 12" BELOW FINISH GRADE.97SBC 1804
  
 12)PROVIDE ATTIC ACCESS IF CLEAR HEIGHT
 OF ATTIC SPACE,MEASURED AT THE ROOF PEAK
 IS 24" OR MORE.
  
 13)SPECIFY SPECIFIC CONNECTORS USED TO
 ANCHOR TRUSSES TO WALLS.
  
 14)PERFORM CALCULATIONS TO DETERMINE
 WINDLOADS ON ROOF TRUSSES AND PROVIDE
 UPLIFT ON PLANS.
  
 15)PROVIDE DETAILS FOR CONNECTION OF
 ADDITION ROOF TO EXISTING ROOF.
  
 16)PROVIDE DETAILS FOR CONNECTION OF
 ADDITION FOOTINGS AND WALLS TO EXISTING
 STRUCTURE.
  
 17)PROVIDE FOUNDATION PLAN FOR ADDITION.
  
 18)PROVIDE WINDOW AND DOOR BUCK DETAILS
 FOR WIND LOAD RESISTANCE.
  
 19)PROVIDE WEST ELEVATION OF EXISTING
 STRUCTURE SHOWING ALL WINDOW AND DOOR
 OPENINGS TO VERIFY TABLE 6OO COMPLIANCE
 OR NON-COMPLIANCE OF ADDITION.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-05-16 Cont ID  
Sent By sgraham Date 2001-05-16 Time 07:34 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-03 Cont ID  
Sent By gjoyce Date 2000-08-03 Time 10:15 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***