Plan Review Details - Permit 00071380
Plan Review Stops For Permit 00071380
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-08-07 Cont ID  
Sent By bstaples Date 2000-08-07 Time 15:19 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 18:39 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE :PLEASE SEE PLANS FOR REDLINED
 MISSING OUTLETS PER 210-52
  
 PLEASE REVISE AND SUBMIT AS-BUILTS
 BEFORE FINAL. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-08 Cont ID  
Sent By mcarsill Date 2000-08-08 Time 13:31 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) APARTMENT DOORS TO BE AT LEAST 20
 MINUTE FIRE RATED EQUIPPED WITH SELF
 CLOSING DEVICES.
 2) SMOKE DETECTORS INSTALLED WITHIN THE
 APARTMENTS, WHEN ACTIVATED SHALL BE
 AUDIBLE IN THE SLEEPING ROOMS OF THAT
 UNIT. THESE DETECTORS SHALL BE INSTALLED
 A MINIMUM OF AT LEAST THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
 3) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL, MECHANICAL, STORAGE
 ROOMS, AND VERTICAL SHAFTS.
 4) SUBMIT COMPLETE FIRE ALARM SYSTEM
 DRAWINGS FOR THE BUILDING. CUT SHEETS
 AND WIRING DIAGRAM ARE TO BE SUBMITTED.
 5) ELEVATOR TO COMPLY WITH ANSI A17.1
 6) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 7) KNOX-BOX NEEDED FOR BUILDING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By ndenmark Date 2000-08-01 Time 11:22 Rev Time 1.00
Received By ndenmark Date 2000-08-01 Time 11:22 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 BATHROOMS WITH NO EXHAUST FANS TO HAVE
 WINDOWS PROVIDING IN NO CASE LESS THAN
 3 SQ FT OF OPEN SPACE

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-08 Cont ID  
Sent By tlarge Date 2000-08-08 Time 19:11 Rev Time 1.25
Received By tlarge Date 2000-08-08 Time 18:02 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 1)SHT.E-P3.01 SHOWS CD AS 1 1/4"AND SHT.
 E-P5.01 SHOWS 1".COMPLY W/SMC SEC.
 304.8.4.
  
 2)FIXTURE UNIT LOAD ON STACKS IS
 INCORRECT.COMPLY W/SPC 713.1 FOR F.U.
 LOAD VALUE.
  
 3)CLEANOUTS ARE REQD.IN WASTE AND SOIL
 STACKS.COMPLY W/SPC SEC.710.2.1.(5),
 710.2.4(1)(2).
  
 4)SHT.E-P5.01-WATER ISOMETRIC-NOTES
 "FOR CONT.SEE TYPICAL WATER ISOMETRIC
 BELOW"AND A WATER ISOMETRIC IS NOT
 SHOWN.CLARIFY.
  
 5)PROTECTION OF THE WATER DISTRIBUTION
 SYSTEM AGAINST HAZARD AND NOISE SHALL
 COMPLY W/SPC SEC.607.8.1-607.8.3.
  
 THE ABOVE INFORMATION SHALL BE PROVIDED
 PRIOR TO PLUMBING INSPECTION.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.