Plan Review Details - Permit 00071380
| Plan Review Stops For Permit 00071380 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-07 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-08-07 |
Time |
15:19 |
Rev Time |
3.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-31 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | | | | 1)NOTE :PLEASE SEE PLANS FOR REDLINED | | | MISSING OUTLETS PER 210-52 | | | | | | PLEASE REVISE AND SUBMIT AS-BUILTS | | | BEFORE FINAL. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | CITY OF WEST PALM BEACH | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-08 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) APARTMENT DOORS TO BE AT LEAST 20 | | | MINUTE FIRE RATED EQUIPPED WITH SELF | | | CLOSING DEVICES. | | | 2) SMOKE DETECTORS INSTALLED WITHIN THE | | | APARTMENTS, WHEN ACTIVATED SHALL BE | | | AUDIBLE IN THE SLEEPING ROOMS OF THAT | | | UNIT. THESE DETECTORS SHALL BE INSTALLED | | | A MINIMUM OF AT LEAST THREE FEET FROM | | | AIR CONDITIONER DIFFUSERS. | | | 3) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL ELECTRICAL, MECHANICAL, STORAGE | | | ROOMS, AND VERTICAL SHAFTS. | | | 4) SUBMIT COMPLETE FIRE ALARM SYSTEM | | | DRAWINGS FOR THE BUILDING. CUT SHEETS | | | AND WIRING DIAGRAM ARE TO BE SUBMITTED. | | | 5) ELEVATOR TO COMPLY WITH ANSI A17.1 | | | 6) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 7) KNOX-BOX NEEDED FOR BUILDING. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-01 |
Time |
11:22 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-08-01 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | BATHROOMS WITH NO EXHAUST FANS TO HAVE | | | WINDOWS PROVIDING IN NO CASE LESS THAN | | | 3 SQ FT OF OPEN SPACE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-08 |
Time |
19:11 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
2000-08-08 |
Time |
18:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | 1)SHT.E-P3.01 SHOWS CD AS 1 1/4"AND SHT. | | | E-P5.01 SHOWS 1".COMPLY W/SMC SEC. | | | 304.8.4. | | | | | | 2)FIXTURE UNIT LOAD ON STACKS IS | | | INCORRECT.COMPLY W/SPC 713.1 FOR F.U. | | | LOAD VALUE. | | | | | | 3)CLEANOUTS ARE REQD.IN WASTE AND SOIL | | | STACKS.COMPLY W/SPC SEC.710.2.1.(5), | | | 710.2.4(1)(2). | | | | | | 4)SHT.E-P5.01-WATER ISOMETRIC-NOTES | | | "FOR CONT.SEE TYPICAL WATER ISOMETRIC | | | BELOW"AND A WATER ISOMETRIC IS NOT | | | SHOWN.CLARIFY. | | | | | | 5)PROTECTION OF THE WATER DISTRIBUTION | | | SYSTEM AGAINST HAZARD AND NOISE SHALL | | | COMPLY W/SPC SEC.607.8.1-607.8.3. | | | | | | THE ABOVE INFORMATION SHALL BE PROVIDED | | | PRIOR TO PLUMBING INSPECTION. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
|