Plan Review Details - Permit 00071370
Plan Review Stops For Permit 00071370
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-11-03 Cont ID  
Sent By drunnels Date 2000-11-03 Time 10:07 Rev Time 1.00
Received By drunnels Date 2000-11-03 Time 10:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-10-19 Cont ID  
Sent By drunnels Date 2000-10-19 Time 08:23 Rev Time 1.00
Received By drunnels Date 2000-10-19 Time 08:23 Sent To  
Notes
2001-01-08 00:00:001. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANCE GLAZING FOR WINDOWS/METRO
 DADE COUNTY OR SBCCI

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-08 Cont ID  
Sent By hpiskura Date 2000-09-08 Time 09:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO NEED SHUTTERS, PROD APPROVALS
 AND WIND ZONE SKETCH

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-21 Cont ID  
Sent By hpiskura Date 2000-08-21 Time 12:45 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER W/APPLICATION

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-02-15 Cont ID  
Sent By dpalmer Date 2001-02-15 Time 06:36 Rev Time 0.00
Received By dpalmer Date 2001-02-15 Time 06:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-01-22 Cont ID  
Sent By dpalmer Date 2001-01-22 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2001-01-22 Time 18:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-28 Cont ID  
Sent By dpalmer Date 2000-09-28 Time 21:21 Rev Time 0.00
Received By dpalmer Date 2000-09-28 Time 21:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-31 Cont ID  
Sent By dpalmer Date 2000-08-31 Time 16:43 Rev Time 0.00
Received By dpalmer Date 2000-08-31 Time 16:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-11 Cont ID  
Sent By dpalmer Date 2000-08-11 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2000-08-11 Time 12:53 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%.
 LIGHTING ETC.
  
 2)NOTE: PLEASE INCLUDE BLDG STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 SEE 250-50 OF THE NEC. ALSO SIZED PER
 250-66.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-02-08 Cont ID  
Sent By dlauderm Date 2001-02-08 Time 10:17 Rev Time 1.00
Received By dlauderm Date 2001-02-08 Time 10:10 Sent To  
Notes
2001-02-08 00:00:00***NONE***
 RRVIED BY MOHAMMAD R. AMINI
 REVIEW NOTES: ***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-14 Cont ID  
Sent By dpalmer Date 2000-08-14 Time 11:05 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS
 EXTEND SIDEWALK TO PROVIDE WALK THRU
 AND HANDI CAP ACCESS FROM AUSTRALIAN AVE
 TO ACCESS DRIVEWAY.
 SEE RICHARD D. PITTMAN IF ANY QUESTIONS
 1000 45TH STREET, WPB, FL 33407
 561 659 8040
 THE UTILITIES COMMENTS HAVE BEEN GIVEN
 TO SIMMONS AND WHITE WHO IS REVISING
 PLANS AT THIS TIME.
 CONTRACTOR SHALL COORDINATE WITH
 CIVIL ENGINEERS TO WORK FROM LATEST
 SET OF PLANS.
 SHOP DRAWINGS MAY BE SUBMITTED AT THIS
 TIME FOR APPROVAL TO
 MANNY GONZALEZ AT
 PUBLIC UTILITIES ENGINEERING
 1000 45TH ST SUITE 15
 WPB FL 334O7 (561) 659 8040 EXT. 2306
 (WE WILL NEED TO KEEP TWO SETS OF
 SHOP DRAWINGS 1 FOR OUR RECORDS AND 1
 FOR OUR INSPECTOR.)
 PROVIDE PERVIOUS AND IMPERVIOUS INFO
 ON 8 1/2 X 11 SHEET PLEASE LIST
 IN SQ. FT. AND IN ACRES. ALSO PROVIDE
 PROPERTY CONTROL NUMBER AND ADDRESS IF
 KNOWN. PLEASE FAX ATTENTION MANNY GONZAL
 EZ 561 6598039. WITH THIS CALCULATIONS
 WE WILL FIGURE OUT THE STORM CHARGES
 THAT WILL APPLY TO THIS PROPERTY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-01-23 Cont ID  
Sent By mcarsill Date 2001-01-23 Time 11:23 Rev Time 0.00
Received By mcarsill Date 2001-01-23 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-29 Cont ID  
Sent By mcarsill Date 2000-08-29 Time 13:45 Rev Time 0.00
Received By mcarsill Date 2000-08-29 Time 13:45 Sent To  
Notes
2001-01-08 00:00:001) FIRE SPRINKLER PLANS INCLUDED IN
 DRAWINGS. HYDRAULIC CALCULATIONS PRESENT
 IN HEDRICK BROTHERS BOOKS ASSIGNED TO
 PROJECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-11 Cont ID  
Sent By mcarsill Date 2000-08-11 Time 09:46 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) BUILDING ADDRESS TO COMPLY WITH CITY
 CODE.
 2) NO FIRE SPRINKLER PLANS INCLUDED IN
 DRAWINGS. PLEASE PROVIDE A COMPLETE
 FIRE SPRINKLER PLAN AND HYDRAULIC
 CALCULATIONS TO THE BUILDING DEPARTMENT.
 CUT SHEETS NEEDED FOR THE TYPE FIRE
 SPRINKLER HEADS PLANNED FOR USE.
 APPLICANT HAS ADVISED THAT THE BUILDING
 WILL CONTAIN AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, SEE PAGE A2.1.
 FIRE SPRINKLER SYSTEM SUPERVISION
 IS REQUIRED BY BOTH BUILDING AND FIRE
 CODES.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2000-09-01 Cont ID  
Sent By ndenmark Date 2000-09-01 Time 14:37 Rev Time 0.25
Received By ndenmark Date 2000-09-01 Time 14:37 Sent To  
Notes
2001-01-08 00:00:00SHELL ONLY, NO MECHANICAL THIS PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-08-14 Cont ID  
Sent By cthirben Date 2000-08-14 Time 13:56 Rev Time 1.00
Received By cthirben Date 2000-08-14 Time 13:56 Sent To  
Notes
2001-01-08 00:00:00NOTES: NO MECHANICAL SUBMITTED FOR SHELL
 REVIEW AT THIS TIME. MECHANICAL PERMIT
 IS REQUIRED FOR A/C INSTALLATION.

Review Stop P PLUMBING
Rev No 7 Status P Date 2001-02-23 Cont ID  
Sent By jleech Date 2001-02-23 Time 16:35 Rev Time 1.00
Received By jleech Date 2001-02-23 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-11-14 Cont ID  
Sent By jleech Date 2000-11-14 Time 10:01 Rev Time 0.75
Received By jleech Date 2000-11-14 Time 10:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-10-16 Cont ID  
Sent By tlarge Date 2000-10-16 Time 18:37 Rev Time 0.75
Received By tlarge Date 2000-10-16 Time 18:37 Sent To  
Notes
2001-01-08 00:00:00SHT.A2.2 SHOWS 8"X6" SCUPPERS AND SHT.
 3.1 SHOWS 12"X 8"SCUPPERS.SUBMIT
 CALCULATIONS FOR OVERFLOW DRAINAGE.
 COMPLY W/SPC SEC.1109.1-1109.3.
  
 2)SHOW SQ.FT.OF ROOF AREA DRAINED BY
 EACH SCUPPER.COMPLY W/TABLE A101.2
  
  
 3)SHT.A6.1-SHOW DIMENSIONS OF SCUPPER.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-10-12 Cont ID  
Sent By tlarge Date 2000-10-12 Time 07:18 Rev Time 0.30
Received By tlarge Date 2000-10-12 Time 07:18 Sent To  
Notes
2001-01-08 00:00:00SANITARY RISER FOR U/G SANITARY.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-02 Cont ID  
Sent By tlarge Date 2000-10-02 Time 17:21 Rev Time 0.65
Received By tlarge Date 2000-10-02 Time 17:21 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT SIGNED,DATED AND SEALED
 SANITARY RISER FOR REVIEW PRIOR TO TOP
 OUT INSPECTION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-30 Cont ID  
Sent By tlarge Date 2000-08-30 Time 20:18 Rev Time 0.65
Received By tlarge Date 2000-08-30 Time 20:18 Sent To  
Notes
2001-01-08 00:00:00PERMIT IS FOR SHELL ONLY-.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 12:47 Rev Time 1.75
Received By tlarge Date 2000-08-09 Time 20:46 Sent To  
Notes
2001-01-08 00:00:001)BREAKROOM SINK SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 2)SUBMIT DIMENSIONS OF OVERFLOW SCUPPERS
 COMPLY W/SPC SEC.1109.2,1109.3,APPENDIX
 "A".
  
 3)IF THESE SPACES WILL BE SEPARATE,
 SANITARY FACILITIES SHALL BE INSTALLED
 IN EACH SPACE.MIN.NUMBER SHALL BE BASED
 ON SQUARE FEET OF HABITABLE FLOOR SPACE.
 SEE SPC SEC.407.1.3.FOR ALLOWED DEDUCT-
 IBLE AREAS.SPC TABLE 407,407.1.4.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-08 Cont ID  
Sent By gjoyce Date 2000-08-08 Time 13:07 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***