| Plan Review Stops For Permit 00071370 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-11-03 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-03 |
Time |
10:07 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-11-03 |
Time |
10:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-10-19 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-19 |
Time |
08:23 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-19 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANCE GLAZING FOR WINDOWS/METRO | | | DADE COUNTY OR SBCCI |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-09-08 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO NEED SHUTTERS, PROD APPROVALS | | | AND WIND ZONE SKETCH |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-08-21 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER W/APPLICATION |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-02-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-15 |
Time |
06:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-15 |
Time |
06:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-01-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-22 |
Time |
18:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-22 |
Time |
18:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-28 |
Time |
21:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-28 |
Time |
21:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-31 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-31 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-11 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-11 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL CONTINUOUS LOADS AT 125%. | | | LIGHTING ETC. | | | | | | 2)NOTE: PLEASE INCLUDE BLDG STEEL AS | | | PART OF THE GROUNDING ELECTRODE SYSTEM. | | | SEE 250-50 OF THE NEC. ALSO SIZED PER | | | 250-66. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-02-08 |
|
|
Cont ID |
|
| Sent By |
dlauderm |
Date |
2001-02-08 |
Time |
10:17 |
Rev Time |
1.00 |
| Received By |
dlauderm |
Date |
2001-02-08 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2001-02-08 00:00:00 | ***NONE*** | | | RRVIED BY MOHAMMAD R. AMINI | | | REVIEW NOTES: ***NONE*** |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-14 |
Time |
11:05 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED WITH PROVISOS | | | EXTEND SIDEWALK TO PROVIDE WALK THRU | | | AND HANDI CAP ACCESS FROM AUSTRALIAN AVE | | | TO ACCESS DRIVEWAY. | | | SEE RICHARD D. PITTMAN IF ANY QUESTIONS | | | 1000 45TH STREET, WPB, FL 33407 | | | 561 659 8040 | | | THE UTILITIES COMMENTS HAVE BEEN GIVEN | | | TO SIMMONS AND WHITE WHO IS REVISING | | | PLANS AT THIS TIME. | | | CONTRACTOR SHALL COORDINATE WITH | | | CIVIL ENGINEERS TO WORK FROM LATEST | | | SET OF PLANS. | | | SHOP DRAWINGS MAY BE SUBMITTED AT THIS | | | TIME FOR APPROVAL TO | | | MANNY GONZALEZ AT | | | PUBLIC UTILITIES ENGINEERING | | | 1000 45TH ST SUITE 15 | | | WPB FL 334O7 (561) 659 8040 EXT. 2306 | | | (WE WILL NEED TO KEEP TWO SETS OF | | | SHOP DRAWINGS 1 FOR OUR RECORDS AND 1 | | | FOR OUR INSPECTOR.) | | | PROVIDE PERVIOUS AND IMPERVIOUS INFO | | | ON 8 1/2 X 11 SHEET PLEASE LIST | | | IN SQ. FT. AND IN ACRES. ALSO PROVIDE | | | PROPERTY CONTROL NUMBER AND ADDRESS IF | | | KNOWN. PLEASE FAX ATTENTION MANNY GONZAL | | | EZ 561 6598039. WITH THIS CALCULATIONS | | | WE WILL FIGURE OUT THE STORM CHARGES | | | THAT WILL APPLY TO THIS PROPERTY. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-01-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-01-23 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-01-23 |
Time |
11:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-29 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-29 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) FIRE SPRINKLER PLANS INCLUDED IN | | | DRAWINGS. HYDRAULIC CALCULATIONS PRESENT | | | IN HEDRICK BROTHERS BOOKS ASSIGNED TO | | | PROJECT. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-11 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS TO COMPLY WITH CITY | | | CODE. | | | 2) NO FIRE SPRINKLER PLANS INCLUDED IN | | | DRAWINGS. PLEASE PROVIDE A COMPLETE | | | FIRE SPRINKLER PLAN AND HYDRAULIC | | | CALCULATIONS TO THE BUILDING DEPARTMENT. | | | CUT SHEETS NEEDED FOR THE TYPE FIRE | | | SPRINKLER HEADS PLANNED FOR USE. | | | APPLICANT HAS ADVISED THAT THE BUILDING | | | WILL CONTAIN AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM, SEE PAGE A2.1. | | | FIRE SPRINKLER SYSTEM SUPERVISION | | | IS REQUIRED BY BOTH BUILDING AND FIRE | | | CODES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-01 |
Time |
14:37 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-09-01 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHELL ONLY, NO MECHANICAL THIS PERMIT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-14 |
Time |
13:56 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-14 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES: NO MECHANICAL SUBMITTED FOR SHELL | | | REVIEW AT THIS TIME. MECHANICAL PERMIT | | | IS REQUIRED FOR A/C INSTALLATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2001-02-23 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-02-23 |
Time |
16:35 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-02-23 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2000-11-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-14 |
Time |
10:01 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2000-11-14 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-16 |
Time |
18:37 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-10-16 |
Time |
18:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHT.A2.2 SHOWS 8"X6" SCUPPERS AND SHT. | | | 3.1 SHOWS 12"X 8"SCUPPERS.SUBMIT | | | CALCULATIONS FOR OVERFLOW DRAINAGE. | | | COMPLY W/SPC SEC.1109.1-1109.3. | | | | | | 2)SHOW SQ.FT.OF ROOF AREA DRAINED BY | | | EACH SCUPPER.COMPLY W/TABLE A101.2 | | | | | | | | | 3)SHT.A6.1-SHOW DIMENSIONS OF SCUPPER. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-10-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-12 |
Time |
07:18 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-10-12 |
Time |
07:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SANITARY RISER FOR U/G SANITARY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-10-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-02 |
Time |
17:21 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-10-02 |
Time |
17:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT SIGNED,DATED AND SEALED | | | SANITARY RISER FOR REVIEW PRIOR TO TOP | | | OUT INSPECTION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-30 |
Time |
20:18 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-30 |
Time |
20:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PERMIT IS FOR SHELL ONLY-. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-10 |
Time |
12:47 |
Rev Time |
1.75 |
| Received By |
tlarge |
Date |
2000-08-09 |
Time |
20:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)BREAKROOM SINK SHALL COMPLY W/FACBC | | | SEC.4.24.1-4.24.7. | | | | | | 2)SUBMIT DIMENSIONS OF OVERFLOW SCUPPERS | | | COMPLY W/SPC SEC.1109.2,1109.3,APPENDIX | | | "A". | | | | | | 3)IF THESE SPACES WILL BE SEPARATE, | | | SANITARY FACILITIES SHALL BE INSTALLED | | | IN EACH SPACE.MIN.NUMBER SHALL BE BASED | | | ON SQUARE FEET OF HABITABLE FLOOR SPACE. | | | SEE SPC SEC.407.1.3.FOR ALLOWED DEDUCT- | | | IBLE AREAS.SPC TABLE 407,407.1.4. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-08-08 |
Time |
13:07 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|