Plan Review Details - Permit 00071334
Plan Review Stops For Permit 00071334
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-03-20 Cont ID  
Sent By pkrauss Date 2001-03-07 Time 13:54 Rev Time 0.35
Received By pkrauss Date 2001-03-07 Time 13:44 Sent To  
Notes
2001-03-07 00:00:00CHANGED AHU - SUPPLY AIR WENT FROM 800
 CFM TO 1200 CFM, O.A. STAYED AT 140 CFM
 AND AIR BALANCE TABLE STILL SHOWS 800
 CFMBEING SUPPLIED AND O.A. AT 140.
 SCHEDULES NEED TO CORRELATE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-05 Cont ID  
Sent By ndenmark Date 2000-09-05 Time 14:14 Rev Time 0.25
Received By ndenmark Date 2000-09-05 Time 14:14 Sent To  
Notes
2001-01-08 00:00:00SEE PROVISO UNDER 00071272