Plan Review Details - Permit 00071272
Plan Review Stops For Permit 00071272
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-30 Cont ID  
Sent By drunnels Date 2000-08-30 Time 10:29 Rev Time 1.00
Received By drunnels Date 2000-08-30 Time 10:29 Sent To  
Notes
2001-01-08 00:00:00************ PROVISO ***************
 STOREFRONT TO BE ISSUED UNDER SEPERATE
 PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By drunnels Date 2000-08-10 Time 09:56 Rev Time 1.00
Received By drunnels Date 2000-08-10 Time 09:59 Sent To  
Notes
2001-01-08 00:00:00 
  
 1. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR WINDOW & DOORS
 FOR STOREFRONT. METRO DADE COUNTY OR
 SBCCI.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-30 Cont ID  
Sent By dpalmer Date 2000-08-30 Time 16:40 Rev Time 0.00
Received By dpalmer Date 2000-08-30 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By dpalmer Date 2000-08-10 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2000-08-10 Time 11:41 Sent To  
Notes
2001-01-08 00:00:00****************UNSAT ** ***************
  
 1)NOTE:PLEASE SHOW THE REQ`D SHOW WINDOW
 RECEPTS PER 210-62. AND LOAD PER 220-3-B
 -7-B
  
 2)NOTE: PLEASE CHECK LIGHTING LOAD SHOWN
 FOR A-1. THIS DOES NOT CORRELATE WITH
 FIXTURE COUNT.
  
 3)NOTE:PLEASE NOTE THAT YOU SHOW A 60AMP
 DISCONNECT WITH 100AMP OCP FROM TENANT.?
  
 4)NOTE: PLEASE SEE ART 450-3-B FOR OCP
 CLARIFICATION.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
  
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-09 Time 16:34 Rev Time 0.00
Received By mcarsill Date 2000-08-09 Time 16:36 Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISHES TO BE CLASS A OR B.
 2) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLAN.
 3) PORTABLE FIRE EXTINGUISHER REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-30 Cont ID  
Sent By ndenmark Date 2000-08-30 Time 14:05 Rev Time 0.50
Received By ndenmark Date 2000-08-30 Time 14:05 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 THE EXCEPTION FOR NO FIRE DAMPER IF DUCT
 IS UNDER 100 SQ.IN. MUST MEET ALL FOUR
 PARTS OF THE EXCEPTION, INCLUDING
 METAL GAUGE, EXTENDING 5 FEET ON BOTH
 SIDE OF THE RATED WALL AND THE DUCT
 SHALL BE INSTALLED ABOVE A CEILING, PER
 1997 SMC 610

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By cthirben Date 2000-08-08 Time 08:14 Rev Time 1.00
Received By cthirben Date 2000-08-08 Time 08:07 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2....
 *INDICATE DAMPERS ON PLANS AT RATED WALL
 AND A DETAIL AS PER 1997 SMC 610.1.2...
 *OUTSIDE AIR SCHEDULE REQUIRED AS PER
 ASHRAE 62-89..
 *PROVIDEDETAIL OF FLEX DUCT CONNECTION

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-01 Cont ID  
Sent By tlarge Date 2000-09-01 Time 17:28 Rev Time 0.65
Received By tlarge Date 2000-09-01 Time 17:28 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
  
 1)SUBMIT A WATER RISER DIAGRAM PRIOR TO
 PLUMBING INSPECTION.COUNTYWIDE AMENDMENT
 TO SPC SEC.104.2.1.
  
 2)DOOR CANNOT SWING INTO CLEAR FLOOR
 SPACE OF DRINKING FOUNTAIN.A FRONT
 APPROACH IS REQD.FOR THE DRINKING
 FOUNTAIN.FACBC SECS.4.15.5,4.22.2
  
 3)PROVISIONS SHALL BE MADE AT THE
 FOUNTAIN FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.FACBC SEC.4.1.3.(10)
 (A).
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By tlarge Date 2000-08-08 Time 19:36 Rev Time 0.30
Received By tlarge Date 2000-08-08 Time 19:33 Sent To  
Notes
2001-01-08 00:00:00A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407 AND SHALL BE HANDICAP ACCESS-
 IBLE PER FACBC SEC.4.1.3.(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
  
 2)A FLOOR DRAIN IS REQD.IN THE TOILET
 ROOM PER SPC SEC.409.4.1.1.