| Plan Review Stops For Permit 00071272 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-30 |
Time |
10:29 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-30 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************ PROVISO *************** | | | STOREFRONT TO BE ISSUED UNDER SEPERATE | | | PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-10 |
Time |
09:56 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-10 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | 1. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT GLAZING FOR WINDOW & DOORS | | | FOR STOREFRONT. METRO DADE COUNTY OR | | | SBCCI. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-30 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-30 |
Time |
16:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-10 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-10 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************UNSAT ** *************** | | | | | | 1)NOTE:PLEASE SHOW THE REQ`D SHOW WINDOW | | | RECEPTS PER 210-62. AND LOAD PER 220-3-B | | | -7-B | | | | | | 2)NOTE: PLEASE CHECK LIGHTING LOAD SHOWN | | | FOR A-1. THIS DOES NOT CORRELATE WITH | | | FIXTURE COUNT. | | | | | | 3)NOTE:PLEASE NOTE THAT YOU SHOW A 60AMP | | | DISCONNECT WITH 100AMP OCP FROM TENANT.? | | | | | | 4)NOTE: PLEASE SEE ART 450-3-B FOR OCP | | | CLARIFICATION. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-09 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-09 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISHES TO BE CLASS A OR B. | | | 2) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON PLAN. | | | 3) PORTABLE FIRE EXTINGUISHER REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-30 |
Time |
14:05 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-08-30 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | THE EXCEPTION FOR NO FIRE DAMPER IF DUCT | | | IS UNDER 100 SQ.IN. MUST MEET ALL FOUR | | | PARTS OF THE EXCEPTION, INCLUDING | | | METAL GAUGE, EXTENDING 5 FEET ON BOTH | | | SIDE OF THE RATED WALL AND THE DUCT | | | SHALL BE INSTALLED ABOVE A CEILING, PER | | | 1997 SMC 610 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-08 |
Time |
08:14 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-08 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2.... | | | *INDICATE DAMPERS ON PLANS AT RATED WALL | | | AND A DETAIL AS PER 1997 SMC 610.1.2... | | | *OUTSIDE AIR SCHEDULE REQUIRED AS PER | | | ASHRAE 62-89.. | | | *PROVIDEDETAIL OF FLEX DUCT CONNECTION |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-01 |
Time |
17:28 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-09-01 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | | | | 1)SUBMIT A WATER RISER DIAGRAM PRIOR TO | | | PLUMBING INSPECTION.COUNTYWIDE AMENDMENT | | | TO SPC SEC.104.2.1. | | | | | | 2)DOOR CANNOT SWING INTO CLEAR FLOOR | | | SPACE OF DRINKING FOUNTAIN.A FRONT | | | APPROACH IS REQD.FOR THE DRINKING | | | FOUNTAIN.FACBC SECS.4.15.5,4.22.2 | | | | | | 3)PROVISIONS SHALL BE MADE AT THE | | | FOUNTAIN FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING.FACBC SEC.4.1.3.(10) | | | (A). | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-08 |
Time |
19:36 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-08-08 |
Time |
19:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407 AND SHALL BE HANDICAP ACCESS- | | | IBLE PER FACBC SEC.4.1.3.(10)(A). | | | PROVISIONS SHALL BE MADE FOR PEOPLE WHO | | | HAVE TROUBLE BENDING OR STOOPING. | | | | | | 2)A FLOOR DRAIN IS REQD.IN THE TOILET | | | ROOM PER SPC SEC.409.4.1.1. |
|
|