Plan Review Details - Permit 00071266
Plan Review Stops For Permit 00071266
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-09-06 Cont ID  
Sent By drunnels Date 2000-09-06 Time 08:59 Rev Time 1.00
Received By drunnels Date 2000-09-06 Time 08:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-09-05 Cont ID  
Sent By drunnels Date 2000-09-05 Time 16:13 Rev Time 1.00
Received By drunnels Date 2000-09-05 Time 16:13 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-25 Cont ID  
Sent By drunnels Date 2000-08-25 Time 12:50 Rev Time 1.00
Received By drunnels Date 2000-08-25 Time 12:50 Sent To  
Notes
2001-01-08 00:00:001.PLANS CALL FOR IMPACT RESISTANT GLASS
 STOREFRONT/REVISIONS CALL FOR HURRICANE
 SHUTTERS RESUBMIT TO CITY PLACE FOR
 APPROVAL.
 2.SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
 3.SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By drunnels Date 2000-08-10 Time 10:38 Rev Time 1.00
Received By drunnels Date 2000-08-10 Time 10:37 Sent To  
Notes
2001-01-08 00:00:00 
 1. PROVIDE PROUCT FOR IMPACT RESISTANT
 GLAZING FOR WINDOWS & DOORS FOR
 STOREFRONT/METRO DADE COUNTY OR SBCCI.
 2. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
 3. SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION.FIRE SPRINKLER PERMIT TO BE
 ISSUED PRIOR TO ISSURANCE OF BUILDING
 PERMIT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-30 Cont ID  
Sent By dpalmer Date 2000-08-30 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2000-08-30 Time 14:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-28 Cont ID  
Sent By dpalmer Date 2000-08-28 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2000-08-28 Time 11:26 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: NOTHING FROM FIRST SET OF NOTES
 ADDRESSED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CA;;.
 DEWEY PALMER
 ELETRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By dpalmer Date 2000-08-10 Time 12:13 Rev Time 0.00
Received By dpalmer Date 2000-08-10 Time 12:12 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE COMPLETE LOAD CALCULATION
 -S SHOW ALL CONTINUOUS LOADS AT 125%
 (LIGHTING ETC).PLEASE INCLUDE LOADS FOR
 SHOW WINDOW RECEPTS AND TRACK LIGHTING
 PER 220-12-A/B
  
 2)NOTE: PLEASE SEE ART 450-3-B FOR OCP
 OF TRANSFORMERS PRIM/SEC.
  
 3)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL
 EQUIPMENT/MAINS/ PANELS. MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER ART;
 110-9.
  
 4)NOTE: IS CIRCUIT #4 SHOWN AS ENTRY
 LIGHTS ON PANEL SCHEDULE CORRECT?
 PLEASE CLARIFY.
  
 5)NOTE: PLEASE SEE THAT OUTLET SPACING
 TO MEET LOCAL CODE IN STORAGE AREA.
 210-50 EVERY 20` OF WALL.
  
 6)NOTE: PLEASE SEE 210-62 FOR SHOW WIN-
 -DOW OUTLETS .
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
  
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-09-06 Cont ID  
Sent By mcarsill Date 2000-09-06 Time 08:47 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-23 Cont ID  
Sent By mcarsill Date 2000-08-23 Time 13:56 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON PLANS. A PLAN AND SEPARATE
 PERMIT IS REQUIRED.
 2) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-09 Time 17:14 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) WRONG FIRE CODE REFERENCE IN CODE
 DATA BOX. SHOULD READ NFPA 101, 1985
 INSTEAD OF NFPA 101, 1991.
 2) NO FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS.
 3) PROVIDE PLANS AND PERMIT FOR FIRE
 ALARM EQUIPMENT SHOWN ON DRAWINGS.
 4) CHEMICAL TYPE FIRE EXTINGUISHERS
 SHOWN ON FIXTURE PLAN TO BE AT LEAST
 5LBS. WITH A RATING OF AT LEAST
 2A 10BC.
 5) DEMISING RATED WALL ASSEMBLIES TO
 BE COMPLETED ON BOTH SIDES OF THE
 WALL PRIOR TO OCCUPANCY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-24 Cont ID  
Sent By ndenmark Date 2000-08-24 Time 14:37 Rev Time 0.33
Received By ndenmark Date 2000-08-24 Time 14:37 Sent To  
Notes
2001-01-08 00:00:00REVISIONS ADDRESS PRIOR MECH REVIEW
 COMMENTS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By cthirben Date 2000-08-10 Time 07:30 Rev Time 1.00
Received By cthirben Date 2000-08-10 Time 07:20 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.REQUIRES ENERGY CALCULATIONS PER
 FLORIDA ENERGY CODE...
 2.PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2......
 3.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 4.SHOW AND PROVIDE DAMPERS ON PLANS AS R
 REQUIRED PER 610.1.2....
 5.REQUIRED DUCT MOUNTING DETAIL.
 6.PROVIDE MOUNTING DETAIL OF THE AHU
 SYSTEM ON PLANS...

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-11-02 Cont ID  
Sent By tlarge Date 2000-11-02 Time 09:33 Rev Time 0.30
Received By tlarge Date 2000-11-02 Time 09:33 Sent To  
Notes
2001-01-08 00:00:00AS BUILT WATER RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-08 Cont ID  
Sent By tlarge Date 2000-08-08 Time 17:34 Rev Time 0.00
Received By tlarge Date 2000-08-08 Time 17:34 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 1)HANDICAP ACCESSIBLE TOILET ROOMS SHALL
 BE INDELIBLY POSTED FOR THE INTENDED
 USE,BE ON AN ACCESSIBLE ROUTE AND BE
 AVAILABLE TO THE PUBLIC WITHOUT
 RESTRICTION DURING NORMAL OPERATING
 HOURS.FACBC SECS.4.1,4.2,4.3 AND SPC
 SEC.4.7.2.2.
  
 2)TITLE SHEET SHALL READ SPC 1994 ED.
 SPC 101.1,& FLA.STATUTE.
  
 3)DRINKING FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3.(10)(A).PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.E.W.C. SHALL
 BE MOUNTED PER FACBC 4.15.
  
 4)COND.DRAIN SHALL NOT DISCHARGE TO
 SANITARY.CONNECT TO EXISTING COND.SYSTEM
 SMC 304.8.3.
  
 5)FLOORS AND WALLS IN TOILET SHALL BE
 NONABSORBENT TO A HEIGHT OF 4 FEET PER
 SBC 1204.2.