| Plan Review Stops For Permit 00071266 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-06 |
Time |
08:59 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-06 |
Time |
08:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-05 |
Time |
16:13 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-05 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. SUBMIT FIRE SPRINKLER PLANS AND | | | PERMIT APPLICATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-25 |
Time |
12:50 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-25 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.PLANS CALL FOR IMPACT RESISTANT GLASS | | | STOREFRONT/REVISIONS CALL FOR HURRICANE | | | SHUTTERS RESUBMIT TO CITY PLACE FOR | | | APPROVAL. | | | 2.SUBMIT LETTER FROM SPECIAL INSPECTOR | | | RELEASING SPACE. | | | 3.SUBMIT FIRE SPRINKLER PLANS AND PERMIT | | | APPLICATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-10 |
Time |
10:38 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-10 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | 1. PROVIDE PROUCT FOR IMPACT RESISTANT | | | GLAZING FOR WINDOWS & DOORS FOR | | | STOREFRONT/METRO DADE COUNTY OR SBCCI. | | | 2. SUBMIT LETTER FROM SPECIAL INSPECTOR | | | RELEASING SPACE. | | | 3. SUBMIT FIRE SPRINKLER PLANS AND | | | APPLICATION.FIRE SPRINKLER PERMIT TO BE | | | ISSUED PRIOR TO ISSURANCE OF BUILDING | | | PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-30 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-30 |
Time |
14:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-28 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-28 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: NOTHING FROM FIRST SET OF NOTES | | | ADDRESSED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CA;;. | | | DEWEY PALMER | | | ELETRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-10 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-10 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE COMPLETE LOAD CALCULATION | | | -S SHOW ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING ETC).PLEASE INCLUDE LOADS FOR | | | SHOW WINDOW RECEPTS AND TRACK LIGHTING | | | PER 220-12-A/B | | | | | | 2)NOTE: PLEASE SEE ART 450-3-B FOR OCP | | | OF TRANSFORMERS PRIM/SEC. | | | | | | 3)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL | | | EQUIPMENT/MAINS/ PANELS. MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER ART; | | | 110-9. | | | | | | 4)NOTE: IS CIRCUIT #4 SHOWN AS ENTRY | | | LIGHTS ON PANEL SCHEDULE CORRECT? | | | PLEASE CLARIFY. | | | | | | 5)NOTE: PLEASE SEE THAT OUTLET SPACING | | | TO MEET LOCAL CODE IN STORAGE AREA. | | | 210-50 EVERY 20` OF WALL. | | | | | | 6)NOTE: PLEASE SEE 210-62 FOR SHOW WIN- | | | -DOW OUTLETS . | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-06 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-23 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON PLANS. A PLAN AND SEPARATE | | | PERMIT IS REQUIRED. | | | 2) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-09 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG FIRE CODE REFERENCE IN CODE | | | DATA BOX. SHOULD READ NFPA 101, 1985 | | | INSTEAD OF NFPA 101, 1991. | | | 2) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. | | | 3) PROVIDE PLANS AND PERMIT FOR FIRE | | | ALARM EQUIPMENT SHOWN ON DRAWINGS. | | | 4) CHEMICAL TYPE FIRE EXTINGUISHERS | | | SHOWN ON FIXTURE PLAN TO BE AT LEAST | | | 5LBS. WITH A RATING OF AT LEAST | | | 2A 10BC. | | | 5) DEMISING RATED WALL ASSEMBLIES TO | | | BE COMPLETED ON BOTH SIDES OF THE | | | WALL PRIOR TO OCCUPANCY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-24 |
Time |
14:37 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-24 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISIONS ADDRESS PRIOR MECH REVIEW | | | COMMENTS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-10 |
Time |
07:30 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-10 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | 1.REQUIRES ENERGY CALCULATIONS PER | | | FLORIDA ENERGY CODE... | | | 2.PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2...... | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 4.SHOW AND PROVIDE DAMPERS ON PLANS AS R | | | REQUIRED PER 610.1.2.... | | | 5.REQUIRED DUCT MOUNTING DETAIL. | | | 6.PROVIDE MOUNTING DETAIL OF THE AHU | | | SYSTEM ON PLANS... |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-11-02 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-11-02 |
Time |
09:33 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-11-02 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | AS BUILT WATER RISER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-08 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-08-08 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | 1)HANDICAP ACCESSIBLE TOILET ROOMS SHALL | | | BE INDELIBLY POSTED FOR THE INTENDED | | | USE,BE ON AN ACCESSIBLE ROUTE AND BE | | | AVAILABLE TO THE PUBLIC WITHOUT | | | RESTRICTION DURING NORMAL OPERATING | | | HOURS.FACBC SECS.4.1,4.2,4.3 AND SPC | | | SEC.4.7.2.2. | | | | | | 2)TITLE SHEET SHALL READ SPC 1994 ED. | | | SPC 101.1,& FLA.STATUTE. | | | | | | 3)DRINKING FOUNTAIN SHALL COMPLY W/ | | | FACBC SEC.4.1.3.(10)(A).PROVISIONS | | | SHALL BE MADE FOR PEOPLE WHO HAVE | | | TROUBLE BENDING OR STOOPING.E.W.C. SHALL | | | BE MOUNTED PER FACBC 4.15. | | | | | | 4)COND.DRAIN SHALL NOT DISCHARGE TO | | | SANITARY.CONNECT TO EXISTING COND.SYSTEM | | | SMC 304.8.3. | | | | | | 5)FLOORS AND WALLS IN TOILET SHALL BE | | | NONABSORBENT TO A HEIGHT OF 4 FEET PER | | | SBC 1204.2. |
|
|