Plan Review Details - Permit 00071225
Plan Review Stops For Permit 00071225
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-28 Cont ID  
Sent By cthirben Date 2000-08-01 Time 11:42 Rev Time 1.00
Received By ndenmark Date 2000-08-01 Time 11:36 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 FAN SHUTDOWN REQUIRED FOR AHU PER NFPA
 90A 4.4.4.2 AND 4.4.4.3...
  
 PROVIDE OUTSIDE AIR AS PER ASHRAE 62-89.
 CONTRACTOR INDICATES OVERHEAD DOORS OPEN
 WHEN OCCUPIED
 CONDENSATE TO BE PER 1997 SMC TO PERMI-
 ABLE LOCATION AND OVERFLOW PROTECTION
 REQUIRED