| 2001-01-08 00:00:00 | DENIED |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY, PLANS STAMPED BY THEM AND COPY |
| | OF RECIEPT SUBMITTED TO CITY OF WPB |
| | BUILDING DEPT. BEFORE A PERMIT CAN BE |
| | ISSUED. |
| | |
| | 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR EXTERIOR |
| | WINDOW SHOWN ON PLANS. |
| | |
| | 3)MISSLE IMPACT PROTECTION IS REQUIRED |
| | FOR ALL EXTERIOR GLAZING. CITY AMENDMENT |
| | TO 97 SBC 1606.4. |
| | |
| | 4)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS INDICATING |
| | SPECIFIC ANCHORS TO BE USED FOR STORM |
| | PANELS. |
| | |
| | 5)SAFETY GLASS IS REQUIRED IN BATHROOM |
| | WINDOW WHERE BOTTOM EDGE OF GLAZING IS |
| | LESS THAN 60" ABOVE DRAIN INLET. 97 SBC |
| | 2405.2 |
| | |
| | 6)PROVIDE R-11 INSULATION IN FLOOR PER |
| | 1997 FLORIDA ENERGY CODE. |
| | |
| | 7)R-19 BAT INSULATION WILL NOT FIT IN A |
| | 2X4 WALL AS INDICATED ON PLANS.CLARIFY. |
| | |
| | 8)PLANS INDICATE U-BLOCK ON TOP OF STEM |
| | WALL. INDICATE TYPE OF STEEL REINFORCE- |
| | MENT TO BE USED. |
| | |
| | 9)PROVIDE FIRE STOPS AT CEILING IN |
| | BALLOON FRAMED EXTERIOR WALL.97 SBC 2305 |
| | |
| | 10)PROVIDE ACCESS TO ATTIC.97 SBC 2309.6 |
| | |
| | 11)PROVIDE CRAWL SPACE VENTILATION PER |
| | 97 SBC 1804.6.2.1 |
| | |
| | 12)SPECIFY CRAWL SPACE ACCESS OPENING |
| | SIZE PER 97 SBC 1804.6.2.2 |
| | |
| | 13)CLARIFY CONNECTION OF FLOOR JOISTS TO |
| | P.T. SILL PLATE. |
| | |
| | 14)SPECIFY TYPE OF CONNECTORS USED TO |
| | ANCHOR NEW RAFTERS TO LEDGER ON EXISTING |
| | ROOF AND RAFTER TO RIDGE CONNECTIONS. |
| | |
| | 15)CLARIFY ATTACHMENT OF GABLE WALL TO |
| | ROOF CONNECTIONS. |
| | |
| | 16)CLARIFY 12" MAXIMUM SPACING OF NAILS |
| | AT 2X6 LEDGER ON EXISTING ROOF. SHOULD |
| | IT BE NAILED AT EVERY RAFTER OR TRUSS. |