Plan Review Details - Permit 00071201
Plan Review Stops For Permit 00071201
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-14 Cont ID  
Sent By drunnels Date 2000-09-14 Time 15:07 Rev Time 0.50
Received By drunnels Date 2000-09-14 Time 15:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-12 Cont ID  
Sent By drunnels Date 2000-09-12 Time 14:17 Rev Time 1.00
Received By drunnels Date 2000-09-12 Time 14:17 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT PRODUCT APPROVAL FOR WINDOW
 GLAZING FOR STROEFRONT. METRO DADE
 COUNTY OR SBCCI SSTD 12-97

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By drunnels Date 2000-08-08 Time 15:41 Rev Time 1.00
Received By drunnels Date 2000-08-08 Time 15:40 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
 1. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
 2. SUBMIT FLORIDA ENERGY SHEETS SEALED
 AND SIGNED BY OWNER/AGENT.
 3. PROVIDE PRODUCT APPROVAL FOR
 STOREFRONT SYSTEM. METRO DADE COUNTY OR
 SBCCI.
 4. SUBMIT FIRE SPRINKLER APPLICATION
 AND PLANS. FIRE SPRINKLER PERMIT MUST BE
 ISSUED PRIOR TO ISSURANCE OF BUILDING
 PERMIT.
 5. SHEET AI.O WALL DETAIL AND SHEET A1.1
 DETAIL B TYPICAL HANGER REFERS TO ICBO
 NUMBERS, WHAT IS THIS.
 6. SHEET A1-O AND A2.1 REFERS TO ADAAG
 SHOULD BE 1997 FACBC.
 7. ALL WOOD BLOCKING SHALL BE FIRE
 RETADANT.
 8. SHEET AI.0 NOTE ON CORRIDOR WALL
 REFRENCES (UBC 1005.7) CHANGE TO SBC.
 9. SHEET C1.0 TENANT CODE SUMMARY
 CORRECT CODES.
 10. SHEET A3.1 SECTION 1&3 SUPPLY
 STRUSTURAL INFORMATION FOR CONCRETE
 BLOCKING BY TENANT G.C. FOR WIND LOADS
 AND LOADS IMPOSED BY GLAZING SYSTEM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 10:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By dpalmer Date 2000-08-04 Time 13:33 Rev Time 0.00
Received By dpalmer Date 2000-08-04 Time 13:33 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE GIVE CLARIFICATION ON
 PANEL"H" 125A MLO IS BEING SHOWN? NEEDS
 TO HAVE MAIN AND RISER SHOWS IT AS 80A
 MCB? PLEASE ADJUST.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By mcarsill Date 2000-09-12 Time 12:45 Rev Time 0.00
Received By mcarsill Date 2000-09-12 Time 12:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-08 Time 16:26 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ THE 1985 EDITION OF THE
 LIFE SAFETY CODE INSTEAD OF 1997
 EDITION.
 2) WRONG INTERIOR FINISHES. INTERIOR
 FINISHES NOT PERMITTED TO BE CLASS C,
 ONLY A OR B ALLOWED.
 3) NO FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS.
 4) PROVIDE MORE INFORMATION ON FIRE
 ALARM DEVICES. THE PLANS INDICATE A
 PANEL AND ONE SMOKE DETECTOR BUT
 WRITER COULD NOT LOCATE ANY AV DEVICES.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-07 Cont ID  
Sent By ndenmark Date 2000-09-07 Time 15:25 Rev Time 0.33
Received By ndenmark Date 2000-09-07 Time 15:25 Sent To  
Notes
2001-01-08 00:00:00PRIOR COMMENTS ADDRESSED BY REVISION
 DATED 8/18/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By ndenmark Date 2000-08-04 Time 10:57 Rev Time 0.33
Received By ndenmark Date 2000-08-04 Time 10:57 Sent To  
Notes
2001-01-08 00:00:00****************DENIED*****************
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 08:38 Rev Time 0.25
Received By tlarge Date 2000-10-29 Time 08:38 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-09 Cont ID  
Sent By tlarge Date 2000-09-09 Time 05:34 Rev Time 0.65
Received By tlarge Date 2000-09-09 Time 05:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By tlarge Date 2000-08-03 Time 20:05 Rev Time 0.50
Received By tlarge Date 2000-08-03 Time 20:05 Sent To  
Notes
2001-01-08 00:00:001)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER TABLE 407 OF SPC
 BASED ON THE SQUARE FEET OF HABITABLE
 FLOOR SPACE PER SPC SEC.407.1.3.
  
 2)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 3)SSF IN TOILET ROOM SHALL COMPLY W/
 FACBC SEC.4.4.1.(PROTRUDING OBJECTS
 SHALL NOT REDUCE THE CLEAR WIDTH OF A
 MANEUVERING SPACE.
  
 4)HANDICAP TOILET ROOMS AND DRINKING
 FOUNTAIN SHALL BE LOCATED ON AN ACCESS-
 IBLE ROUTE AND AVAILABLE TO THE PATRONS
 WITHOUT RESTRICTION DURING NORMAL
 OPERATING HOURS.ACCESSIBLE ROUTE SHALL
 BE CLEARLY DEFINED ON THE PLANS.FACBC
 SECS.4.1.3(11),4.2.1,4.3.1,4.3.2,(3),
 4.3.3.
  
 IF YOU HAVE ANY QUESTIONS CALL
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved