Plan Review Details - Permit 00071200
Plan Review Stops For Permit 00071200
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-01-03 Cont ID  
Sent By jwitmer Date 2001-01-03 Time 15:19 Rev Time 5.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: LARGE MISSLE IMPACT TO BE UNDER
 SEPERATE PERMIT, ARMOR SCREEN SERIES
 2000 WILL REQUIRE TECHNICAL DRAWINGS FOR
 COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-10-30 Cont ID  
Sent By drunnels Date 2000-10-30 Time 15:36 Rev Time 1.00
Received By jwitmer Date 2000-10-30 Time 15:36 Sent To  
Notes
2001-01-08 00:00:001. PLEASE SUBMIT PRODUCT APPROVAL FOR
 DOORS AND ROOF COVER /METRO DADE COUNTY
 OR SBCCI
 2. PROVIDE ENERGY EFFICIENCY CALCULATION
 3. ALL SHEETS SHALL BE SIGNED AND SEALED
 4. SUBMIT SIGNED AND SEALED SURVEY
 5. SHEET S1, DTAILS WT-4 AND TT-5
 SHALL FOLLOW TO ASCE 7-95

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-29 Cont ID  
Sent By lmartine Date 2000-08-29 Time 10:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1] PLEASE SUBMIT TEST REPORTS FOR ROOF
 COVER AND EXTERIOR WINDOWS AND DOORS.
 2] PROVIDE ENERGY EFFICIENCY CALCULATION
 3] ALL PAGES SHALL BE SIGNED AND SEALED.
 4] PROVIDE SOIL INVESTIGATION REPORT,
 SEE 1805 SBC.
 5] SUBMIT SIGNED AND SEALED SURVEYS.
 6] SEE PAGE SL1,CALLS FOR DETAILS 4,5,
 AND 8 OF SD3.2,[SHEET MISSING].
 7] SEE PAGE S1,DETAILS WT-4 AND TT-5
 SHALL FOLLOW ASCE 7-95.
 8] VERIFY ALL WOOD CONSTRUCTION COMPLYS
 WITH 2304.2 SBC.
 9] EXPLAIN CONSTRUCTION TYPE,WHY TYPE V,
 PROTECTED.
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 659-8096 #8456

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-01-03 Cont ID  
Sent By dpalmer Date 2001-01-03 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2001-01-03 Time 14:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-10-25 Cont ID  
Sent By dpalmer Date 2000-10-25 Time 01:10 Rev Time 0.00
Received By dpalmer Date 2000-10-25 Time 01:10 Sent To  
Notes
2001-01-08 00:00:00******************** UNSAT *************
  
 1)NOTE: ONLY ONE SET OF PLANS WERE SUB-
 -MITTED FOR REVIEW. PLEASE SUBMIT TWO
 COMPLETE SETS.
  
 2)NOTE: PLEASE SEE NOTES FROM FISRT
 REVIEW.
 CONTINUOUS LOADS AT 125%
 GROUND FOR TRANSFORMER TO BE MORE SPECI-
 -FIC. PER250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 20:41 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 20:41 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 **** PLANS NEED TO BE SIGNED AND SEALED*
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%
 FOR LIGHTING ETC.
  
 2)NOTE: PLEASE SEE 220-12-B FOR LOAD
 CALCS ON TRACK LIGHTING.
  
 3)NOTE: YOU SHOW GROUND FROM TRANSFORMER
 GOING TO BLDG STEEL OR COLD WATER.
 PLEASE SEE 250-50
  
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-14 Cont ID  
Sent By mgonzale Date 2000-08-14 Time 09:33 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-11-21 Cont ID  
Sent By mcarsill Date 2000-11-21 Time 10:16 Rev Time 0.00
Received By mcarsill Date 2000-11-21 Time 10:16 Sent To  
Notes
2001-01-08 00:00:001) ELECTRICAL AND MECHANICAL ROOMS TO
 BE AT LEAST ONE HOUR SEPARATED SINCE
 NO FIRE SPRINKLER SYSTEM IS PRESENT.
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-10-30 Cont ID  
Sent By mcarsill Date 2000-10-30 Time 12:17 Rev Time 0.00
Received By mcarsill Date 2000-10-30 Time 12:17 Sent To  
Notes
2001-01-08 00:00:001) PREVIOUS PLAN REVIEW COMMENTS NOT
 PROPERLY ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By mcarsill Date 2000-08-10 Time 10:52 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO BUILDING ADDRESS NOTED ON
 ELEVATION DRAWINGS.
 2) INTERIOR FINISHES IN EXITS SHALL BE
 CLASS A OR B. INTERIOR FINISHES IN
 OFFICES SHALL BE CLASS A,B OR C.
 3) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, 1985 EDITION.
 4) PROVIDE COMPLETE FIRE ALARM SYSTEM
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS. A SEPARATE PLAN AND PERMIT
 REQUIRED PRIOR TO INSTALLATION.
 5) PROVIDE MORE DETAILS ON THE FIRE
 DEPARTMENT CONNECTION AND HOSE VALVE
 CABINET SHOWN ON PAGE PL1.
 6) WHERE ARE THE FIRE HYDRANTS NEAR
 THE PROPERTY LOCATED.
 7) HAZARDOUS AREAS OR ROOMS TO BE
 PROTECTED BY AT LEAST ONE HOUR FIRE
 RATED CONSTRUCTION WITH RATED FIRE
 DOORS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-01-02 Cont ID  
Sent By ndenmark Date 2001-01-02 Time 14:00 Rev Time 0.50
Received By ndenmark Date 2001-01-02 Time 14:00 Sent To  
Notes
2001-01-08 00:00:00OVERFLOW PROTECTION REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-10-28 Cont ID  
Sent By ndenmark Date 2000-10-28 Time 13:54 Rev Time 0.50
Received By ndenmark Date 2000-10-28 Time 13:54 Sent To  
Notes
2001-01-08 00:00:00REQUIRE MINIMUM 2 COMPLETE SETS OF
 SIGNED SEALED PLANS FOR STAMPS AND
 COMMENTS FROM THIS OFFICE
 PLAN ACL2 SHOWS AIR BALANCE AS REQUESTED
 ON PRIOR REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By cthirben Date 2000-08-04 Time 07:36 Rev Time 0.00
Received By cthirben Date 2000-08-04 Time 07:36 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2. BEFORE A
 ANY COMMENCEMENT OF WORK.
 ENGINEEROR ARCHITECT RAISED AND SIGNED
 SEAL REQUIRED..

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-06-12 Cont ID  
Sent By kstevens Date 2001-06-12 Time 08:59 Rev Time 0.50
Received By kstevens Date 2001-06-12 Time 08:59 Sent To  
Notes
2001-06-12 00:00:00REVIEW NOTES PASSED
  
 PER CONVERSATION WITH MICHAEL MCTEAGUE
 THERE WILL BE A SINGLE EWC CENTERED ON
 WALL WITH DRINKING CUP DISPENSOR FOR
 PEOPLE WHO HAVE TROUBLE BENDING. THIS
 WILL GIVE PROPER CLEAR FLOOR SPACE.
  
 KSTEVENS

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-05-09 Cont ID  
Sent By kstevens Date 2001-05-09 Time 19:20 Rev Time 1.50
Received By kstevens Date 2001-05-09 Time 19:20 Sent To  
Notes
2001-05-09 00:00:00REVIEW NOTES:FAILED
  
 PLUMBING PLAN REVIEW RESUBMIT UNSAT.
 1) BREAK ROOM SINK STILL NOT ADDRESSED
 FROM PREVIOUS REVIEWS. SHOW ELEVATION
 DETAILS.
  
 2) SHT PL-1 D/F COMPLY WITH FACBC SECT.
 4.1.3 (10) (A), CLEAR FLOOR SPACE, ELEV.
 DETAIL (PLMB FIXTURE DETAIL SHOWS 34"
 TO SPOUT, SHOULD BE 36"), PROVISIONS FOR
 PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING.
  
 3) PLUMBING FIXTURE SCHEDULE SHOWS SK-1
 SINK WITH 3-1/4" DRAIN, SHOULD READ
 1-1/2".
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-19 Cont ID  
Sent By pschmitz Date 2000-10-14 Time 09:42 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW RESUBMIT UNSAT
 (1) BREAK RM SINK NOT ADDRSSED FROM
 PREVIOUS COMMENTS, SHOW ELV DETAIL.
 (2)SHT PL-1 D/F COMPLY W/FACBC SEC 4.1.3
 (10)(A), CLEAR FLR SPACE,ELV DETAIL,
 PROVISIONS FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
 (3) SHT PL-1 W/C ON 2" WASTE LINE,
 VENT SHOWN ON W/C STUB,
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-10-19 Cont ID  
Sent By tlarge Date 2000-08-09 Time 20:08 Rev Time 0.75
Received By pschmitz Date 2000-08-09 Time 19:30 Sent To  
Notes
2001-01-08 00:00:001)BREAK ROOM SINK SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3.(10)(A).PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
  
 3)SHT.AL4-WAINSCOTING SHALL COMPLY W/SBC
 SEC.1204.2.(MIN.48"IN HEIGHT.)
  
 4)SHT.PL1-WATER CLOSETS NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.
  
 5)CHECK DRAIN SIZE IN MEN'S TOILET ROOM.
 (SIZE CHANGES FROM 4" TO 3" TO 4".
 SPC 307.5.