| Notes |
| 2001-01-08 00:00:00 | PROVISO: LARGE MISSLE IMPACT TO BE UNDER | | | SEPERATE PERMIT, ARMOR SCREEN SERIES | | | 2000 WILL REQUIRE TECHNICAL DRAWINGS FOR | | | COMPLIANCE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-10-30 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-30 |
Time |
15:36 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2000-10-30 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. PLEASE SUBMIT PRODUCT APPROVAL FOR | | | DOORS AND ROOF COVER /METRO DADE COUNTY | | | OR SBCCI | | | 2. PROVIDE ENERGY EFFICIENCY CALCULATION | | | 3. ALL SHEETS SHALL BE SIGNED AND SEALED | | | 4. SUBMIT SIGNED AND SEALED SURVEY | | | 5. SHEET S1, DTAILS WT-4 AND TT-5 | | | SHALL FOLLOW TO ASCE 7-95 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-08-29 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | 1] PLEASE SUBMIT TEST REPORTS FOR ROOF | | | COVER AND EXTERIOR WINDOWS AND DOORS. | | | 2] PROVIDE ENERGY EFFICIENCY CALCULATION | | | 3] ALL PAGES SHALL BE SIGNED AND SEALED. | | | 4] PROVIDE SOIL INVESTIGATION REPORT, | | | SEE 1805 SBC. | | | 5] SUBMIT SIGNED AND SEALED SURVEYS. | | | 6] SEE PAGE SL1,CALLS FOR DETAILS 4,5, | | | AND 8 OF SD3.2,[SHEET MISSING]. | | | 7] SEE PAGE S1,DETAILS WT-4 AND TT-5 | | | SHALL FOLLOW ASCE 7-95. | | | 8] VERIFY ALL WOOD CONSTRUCTION COMPLYS | | | WITH 2304.2 SBC. | | | 9] EXPLAIN CONSTRUCTION TYPE,WHY TYPE V, | | | PROTECTED. | | | | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 659-8096 #8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-01-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-03 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-03 |
Time |
14:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-10-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-25 |
Time |
01:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-25 |
Time |
01:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************** UNSAT ************* | | | | | | 1)NOTE: ONLY ONE SET OF PLANS WERE SUB- | | | -MITTED FOR REVIEW. PLEASE SUBMIT TWO | | | COMPLETE SETS. | | | | | | 2)NOTE: PLEASE SEE NOTES FROM FISRT | | | REVIEW. | | | CONTINUOUS LOADS AT 125% | | | GROUND FOR TRANSFORMER TO BE MORE SPECI- | | | -FIC. PER250-50 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRCIAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-15 |
Time |
20:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-15 |
Time |
20:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | **** PLANS NEED TO BE SIGNED AND SEALED* | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | FOR LIGHTING ETC. | | | | | | 2)NOTE: PLEASE SEE 220-12-B FOR LOAD | | | CALCS ON TRACK LIGHTING. | | | | | | 3)NOTE: YOU SHOW GROUND FROM TRANSFORMER | | | GOING TO BLDG STEEL OR COLD WATER. | | | PLEASE SEE 250-50 | | | | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-08-14 |
Time |
09:33 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-21 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-21 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) ELECTRICAL AND MECHANICAL ROOMS TO | | | BE AT LEAST ONE HOUR SEPARATED SINCE | | | NO FIRE SPRINKLER SYSTEM IS PRESENT. | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-10-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-30 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-30 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PREVIOUS PLAN REVIEW COMMENTS NOT | | | PROPERLY ADDRESSED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-10 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO BUILDING ADDRESS NOTED ON | | | ELEVATION DRAWINGS. | | | 2) INTERIOR FINISHES IN EXITS SHALL BE | | | CLASS A OR B. INTERIOR FINISHES IN | | | OFFICES SHALL BE CLASS A,B OR C. | | | 3) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101, 1985 EDITION. | | | 4) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON PLANS. A SEPARATE PLAN AND PERMIT | | | REQUIRED PRIOR TO INSTALLATION. | | | 5) PROVIDE MORE DETAILS ON THE FIRE | | | DEPARTMENT CONNECTION AND HOSE VALVE | | | CABINET SHOWN ON PAGE PL1. | | | 6) WHERE ARE THE FIRE HYDRANTS NEAR | | | THE PROPERTY LOCATED. | | | 7) HAZARDOUS AREAS OR ROOMS TO BE | | | PROTECTED BY AT LEAST ONE HOUR FIRE | | | RATED CONSTRUCTION WITH RATED FIRE | | | DOORS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-01-02 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-01-02 |
Time |
14:00 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-01-02 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OVERFLOW PROTECTION REQUIRED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-10-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-28 |
Time |
13:54 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-10-28 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REQUIRE MINIMUM 2 COMPLETE SETS OF | | | SIGNED SEALED PLANS FOR STAMPS AND | | | COMMENTS FROM THIS OFFICE | | | PLAN ACL2 SHOWS AIR BALANCE AS REQUESTED | | | ON PRIOR REVIEW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-04 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-04 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-08-04 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. BEFORE A | | | ANY COMMENCEMENT OF WORK. | | | ENGINEEROR ARCHITECT RAISED AND SIGNED | | | SEAL REQUIRED.. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-06-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-12 |
Time |
08:59 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-06-12 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2001-06-12 00:00:00 | REVIEW NOTES PASSED | | | | | | PER CONVERSATION WITH MICHAEL MCTEAGUE | | | THERE WILL BE A SINGLE EWC CENTERED ON | | | WALL WITH DRINKING CUP DISPENSOR FOR | | | PEOPLE WHO HAVE TROUBLE BENDING. THIS | | | WILL GIVE PROPER CLEAR FLOOR SPACE. | | | | | | KSTEVENS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-05-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-05-09 |
Time |
19:20 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2001-05-09 |
Time |
19:20 |
Sent To |
|
|
| Notes |
| 2001-05-09 00:00:00 | REVIEW NOTES:FAILED | | | | | | PLUMBING PLAN REVIEW RESUBMIT UNSAT. | | | 1) BREAK ROOM SINK STILL NOT ADDRESSED | | | FROM PREVIOUS REVIEWS. SHOW ELEVATION | | | DETAILS. | | | | | | 2) SHT PL-1 D/F COMPLY WITH FACBC SECT. | | | 4.1.3 (10) (A), CLEAR FLOOR SPACE, ELEV. | | | DETAIL (PLMB FIXTURE DETAIL SHOWS 34" | | | TO SPOUT, SHOULD BE 36"), PROVISIONS FOR | | | PEOPLE WHO HAVE TROUBLE BENDING OR | | | STOOPING. | | | | | | 3) PLUMBING FIXTURE SCHEDULE SHOWS SK-1 | | | SINK WITH 3-1/4" DRAIN, SHOULD READ | | | 1-1/2". | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-10-19 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-10-14 |
Time |
09:42 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW RESUBMIT UNSAT | | | (1) BREAK RM SINK NOT ADDRSSED FROM | | | PREVIOUS COMMENTS, SHOW ELV DETAIL. | | | (2)SHT PL-1 D/F COMPLY W/FACBC SEC 4.1.3 | | | (10)(A), CLEAR FLR SPACE,ELV DETAIL, | | | PROVISIONS FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | (3) SHT PL-1 W/C ON 2" WASTE LINE, | | | VENT SHOWN ON W/C STUB, | | | END OF COMMENTS PAUL SCHMITZ | | | 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-10-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-09 |
Time |
20:08 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
2000-08-09 |
Time |
19:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)BREAK ROOM SINK SHALL COMPLY W/FACBC | | | SEC.4.24.1-4.24.7. | | | | | | 2)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.DRINKING FOUNTAIN SHALL COMPLY | | | W/FACBC SEC.4.1.3.(10)(A).PROVISIONS | | | SHALL BE MADE FOR PEOPLE WHO HAVE | | | TROUBLE BENDING OR STOOPING. | | | | | | 3)SHT.AL4-WAINSCOTING SHALL COMPLY W/SBC | | | SEC.1204.2.(MIN.48"IN HEIGHT.) | | | | | | 4)SHT.PL1-WATER CLOSETS NOT PERMITTED ON | | | WET VENTS PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.911.1.1. | | | | | | 5)CHECK DRAIN SIZE IN MEN'S TOILET ROOM. | | | (SIZE CHANGES FROM 4" TO 3" TO 4". | | | SPC 307.5. |
|
|