Plan Review Details - Permit 00071152
Plan Review Stops For Permit 00071152
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-12-14 Cont ID  
Sent By lmartine Date 2000-12-14 Time 16:29 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-10-23 Cont ID  
Sent By lmartine Date 2000-10-23 Time 15:35 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-07 Cont ID  
Sent By lmartine Date 2000-09-07 Time 17:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1]PROVIDE 18" CLEAR AT PULL SIDE OF DOOR
 #251,AND 12" CLEAR AT PUSH SIDE OF
 DOORS #203A,#203B, SEE FAC 4.13.6
 2]CORRIDOR #252,REMOVE SMALL SECTION OF
 WALL OBSTRUCTING EXIT ACCESS,SBC1012.5
 SEE HIGHLIGHTED AREA.
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 659 8096 8456

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-02-15 Cont ID  
Sent By dpalmer Date 2001-02-15 Time 17:51 Rev Time 0.00
Received By dpalmer Date 2001-02-15 Time 17:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 22:04 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 21:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By dpalmer Date 2000-08-24 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2000-08-24 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-12-14 Cont ID  
Sent By mcarsill Date 2000-12-14 Time 08:34 Rev Time 0.00
Received By mcarsill Date 2000-12-14 Time 08:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-10-27 Cont ID  
Sent By mcarsill Date 2000-10-24 Time 12:14 Rev Time 0.00
Received By mcarsill Date 2000-10-24 Time 12:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-10 Cont ID  
Sent By mcarsill Date 2000-08-10 Time 12:24 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) DOOR TO TOILET (260) INTERFERES WITH
 EXIT ACCESS CORRIDOR TO SOUTH
 STAIRTOWER.
 2) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B. INTERIOR FINISHES IN
 OFFICES CAN BE CLASS A,B, OR C.
 3) FIRE ALARM SYSTEM TO BE ADDRESSABLE
 OR CLASS A. LOCKS ON EGRESS DOORS TIED
 INTO FIRE ALARM SYSTEM TO COMPLY WITH
 SPECIAL LOCKING ARRANGEMENTS, NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION.
 4) WHEN ACTIVATED, THE FIRE ALARM SYSTEM
 ON THE SECOND FLOOR IS TO BE AUDIBLE
 THROUGHOUT SPACE.
 5) NO SMOKE DETECTOR (S) SHOWN IN
 ELEVATOR LOBBY.
 6) CORRIDORS USED FOR EXITING MUST BE
 AT LEAST ONE HOUR FIRE RATED, WHEN
 OCCUPANCIES OF 30 OR MORE PERSONS ARE
 PRESENT.
 7) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS. A SEPARATE PERMIT IS REQUIRED.
 8) PROVIDE FIRE SPRINKLER SYSTEM SHOP
 DRAWINGS. A SEPARATE PERMIT IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-02-27 Cont ID  
Sent By pkrauss Date 2001-02-27 Time 11:45 Rev Time 0.35
Received By pkrauss Date 2001-02-27 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2000-12-14 Cont ID  
Sent By ndenmark Date 2000-12-14 Time 10:10 Rev Time 0.33
Received By ndenmark Date 2000-12-14 Time 10:10 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1. 1997 SMC 610.6 REQUIRES LOCATION AND
 INSTALLATION DETAILS OF FIRE DAMPERS
 REQUIRED BY 610.1.2 TO BE SHOWN AND
 PROPERLY INDICATED ON PLANS BY THE
 DESIGNER. DUCTS PENETRATING ELEVATOR
 LOBBY WALLS REQUIRE PROTECTION TO
 MAINTAIN RATING OF WALLS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-11 Cont ID  
Sent By cthirben Date 2000-08-11 Time 14:09 Rev Time 1.00
Received By cthirben Date 2000-08-11 Time 14:06 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 APRROVED WITH REFERENCE PER PERMIT
 NO: 00020273.OUTSIDE/AIR CALCULATION
 ATTACHED TO THE AVOVE MENTIONED PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-01 Cont ID  
Sent By cthirben Date 2000-08-01 Time 13:42 Rev Time 2.00
Received By cthirben Date 2000-08-01 Time 13:41 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2...

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-12-13 Cont ID  
Sent By jleech Date 2000-12-13 Time 15:16 Rev Time 1.00
Received By jleech Date 2000-12-13 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-01 Cont ID  
Sent By tlarge Date 2000-10-01 Time 06:36 Rev Time 1.50
Received By tlarge Date 2000-10-01 Time 05:34 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 THE CORE RESTROOMS ARE NON-COMPLIANT PER
 SPC TABLE 407.CERTIFICATE OF OCCUPANCY
 SHALL NOT BE ISSUED UNTIL THIS MATTER IS
 RESOLVED.SEE PERMIT #99101414.
  
 2)THE HANDICAP ACCESSIBLE STALLS DO NOT
 COMPLY W/FACBC SEC.4.17.3.THIS LAYOUT
 HAS BEEN REVISED BY THE ARCHITECT AND
 REVIEWED BY THIS DEPARTMENT FOR
 COMPLIANCE.SUBMIT CURRENT LAYOUT FOR THE
 ACCESSIBLE STALLS.SEE PERMIT #99101414.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-06 Cont ID  
Sent By pschmitz Date 2000-08-06 Time 09:51 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW UNSAT REF SPC 94
 (1A) SHT A-1 IS NOT THE MOST CURRENT
 COPY OF THE PUBLIC REST RM'S AS BUILT.
 (1B) PRIVATE REST RM'S #214A,208A TO
 COMPLY W/FACBC 4.1.3(11) SHALL BE H/C
 ADAPTABLE TO BE SHOWN ON ELEVATION SHTS.
 (1C) SHT A-1 MIN FACILITIES SEC 407.1.3
 SHOW SQUARE FOOTAGE FOR NUMBER OF
 OCCUPANTS.
 (2) SHT A3-1 INTERIOR ELEVATIONS, COMPLY
 W/FACBC 4.24 BREAK RM SINKS, CLEAR FLOOR
 SPACE, KNEE CLEARANCE.
 (3) SHTP3.1 OWNER HAS PROVIDED A WATER
 CONNECTION OUT SIDE THE PUBLIC REST RM'S
 (4) SHT P2-1 BREAK RM # 290 SHOW DRAIN,
 WASTE & VEVT CONNECTION TO EX.
 END OF COMMENTSPES