| Plan Review Stops For Permit 00071152 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-12-14 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-10-23 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-10-23 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-07 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-07 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | 1]PROVIDE 18" CLEAR AT PULL SIDE OF DOOR | | | #251,AND 12" CLEAR AT PUSH SIDE OF | | | DOORS #203A,#203B, SEE FAC 4.13.6 | | | 2]CORRIDOR #252,REMOVE SMALL SECTION OF | | | WALL OBSTRUCTING EXIT ACCESS,SBC1012.5 | | | SEE HIGHLIGHTED AREA. | | | | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 659 8096 8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-02-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-15 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-15 |
Time |
17:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-12-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-13 |
Time |
22:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-13 |
Time |
21:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-24 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-24 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-14 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-14 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-10-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-10-24 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-10-24 |
Time |
12:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-10 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) DOOR TO TOILET (260) INTERFERES WITH | | | EXIT ACCESS CORRIDOR TO SOUTH | | | STAIRTOWER. | | | 2) INTERIOR FINISH IN EXITS SHALL BE | | | CLASS A OR B. INTERIOR FINISHES IN | | | OFFICES CAN BE CLASS A,B, OR C. | | | 3) FIRE ALARM SYSTEM TO BE ADDRESSABLE | | | OR CLASS A. LOCKS ON EGRESS DOORS TIED | | | INTO FIRE ALARM SYSTEM TO COMPLY WITH | | | SPECIAL LOCKING ARRANGEMENTS, NFPA 101, | | | THE LIFE SAFETY CODE, 1985 EDITION. | | | 4) WHEN ACTIVATED, THE FIRE ALARM SYSTEM | | | ON THE SECOND FLOOR IS TO BE AUDIBLE | | | THROUGHOUT SPACE. | | | 5) NO SMOKE DETECTOR (S) SHOWN IN | | | ELEVATOR LOBBY. | | | 6) CORRIDORS USED FOR EXITING MUST BE | | | AT LEAST ONE HOUR FIRE RATED, WHEN | | | OCCUPANCIES OF 30 OR MORE PERSONS ARE | | | PRESENT. | | | 7) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS. A SEPARATE PERMIT IS REQUIRED. | | | 8) PROVIDE FIRE SPRINKLER SYSTEM SHOP | | | DRAWINGS. A SEPARATE PERMIT IS REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-02-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-02-27 |
Time |
11:45 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-02-27 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-14 |
Time |
10:10 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-12-14 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. 1997 SMC 610.6 REQUIRES LOCATION AND | | | INSTALLATION DETAILS OF FIRE DAMPERS | | | REQUIRED BY 610.1.2 TO BE SHOWN AND | | | PROPERLY INDICATED ON PLANS BY THE | | | DESIGNER. DUCTS PENETRATING ELEVATOR | | | LOBBY WALLS REQUIRE PROTECTION TO | | | MAINTAIN RATING OF WALLS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-11 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-11 |
Time |
14:09 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-11 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES: | | | APRROVED WITH REFERENCE PER PERMIT | | | NO: 00020273.OUTSIDE/AIR CALCULATION | | | ATTACHED TO THE AVOVE MENTIONED PERMIT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-01 |
Time |
13:42 |
Rev Time |
2.00 |
| Received By |
cthirben |
Date |
2000-08-01 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2... |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-12-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-13 |
Time |
15:16 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2000-12-13 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-10-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-01 |
Time |
06:36 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-10-01 |
Time |
05:34 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | | | | THE CORE RESTROOMS ARE NON-COMPLIANT PER | | | SPC TABLE 407.CERTIFICATE OF OCCUPANCY | | | SHALL NOT BE ISSUED UNTIL THIS MATTER IS | | | RESOLVED.SEE PERMIT #99101414. | | | | | | 2)THE HANDICAP ACCESSIBLE STALLS DO NOT | | | COMPLY W/FACBC SEC.4.17.3.THIS LAYOUT | | | HAS BEEN REVISED BY THE ARCHITECT AND | | | REVIEWED BY THIS DEPARTMENT FOR | | | COMPLIANCE.SUBMIT CURRENT LAYOUT FOR THE | | | ACCESSIBLE STALLS.SEE PERMIT #99101414. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-06 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-08-06 |
Time |
09:51 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW UNSAT REF SPC 94 | | | (1A) SHT A-1 IS NOT THE MOST CURRENT | | | COPY OF THE PUBLIC REST RM'S AS BUILT. | | | (1B) PRIVATE REST RM'S #214A,208A TO | | | COMPLY W/FACBC 4.1.3(11) SHALL BE H/C | | | ADAPTABLE TO BE SHOWN ON ELEVATION SHTS. | | | (1C) SHT A-1 MIN FACILITIES SEC 407.1.3 | | | SHOW SQUARE FOOTAGE FOR NUMBER OF | | | OCCUPANTS. | | | (2) SHT A3-1 INTERIOR ELEVATIONS, COMPLY | | | W/FACBC 4.24 BREAK RM SINKS, CLEAR FLOOR | | | SPACE, KNEE CLEARANCE. | | | (3) SHTP3.1 OWNER HAS PROVIDED A WATER | | | CONNECTION OUT SIDE THE PUBLIC REST RM'S | | | (4) SHT P2-1 BREAK RM # 290 SHOW DRAIN, | | | WASTE & VEVT CONNECTION TO EX. | | | END OF COMMENTSPES |
|
|