Plan Review Details - Permit 00071134
Plan Review Stops For Permit 00071134
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-09-06 Cont ID  
Sent By lmartine Date 2000-09-06 Time 11:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-21 Cont ID  
Sent By dpalmer Date 2000-12-21 Time 13:22 Rev Time 0.00
Received By dpalmer Date 2000-12-21 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-08-23 Cont ID  
Sent By dpalmer Date 2000-08-23 Time 06:51 Rev Time 0.00
Received By dpalmer Date 2000-08-23 Time 06:51 Sent To  
Notes
2001-01-08 00:00:00************* PROVISO ******************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.
  
 2)NOTE: PLEASE SUBMIT ALL AIC RATINGS
 FOR ALL EQUIPMENT. THIS IS TO BE SUBMIT-
 -TED ON E-SHEET AND BY ENGINEER OF RE-
 -CORD.THIS IS TO BE SHOWN ON PLANS.
 A MIN.RATING IS REQ`D. IF A HIGHER AIC
 RATING IS INSTALLED THEN THAT WILL BE
 ACCEPTED. PER 110-9/215-5 OF NEC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-29 Cont ID  
Sent By mgonzale Date 2000-08-29 Time 15:40 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISO
 CONTRACTOR MUST USE THE SILT SCREEN
 FENCE ALONG THE PERIMETER OF SITE TO
 CONTAIN ALL CONSTRUCTION DEBRIS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-18 Cont ID  
Sent By mcarsill Date 2000-08-18 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2000-08-18 Time 12:21 Sent To  
Notes
2001-01-08 00:00:001) NO BUILDING ADDRESS SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 IS TO COMPLY WITH CITY CODE REQUIREMENTS
 2) HOW DOES FIRE RESCUE ENTER SITE
 THROUGH PROPOSED DOUBLE SWING GATE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By ndenmark Date 2000-08-24 Time 15:29 Rev Time 0.33
Received By ndenmark Date 2000-08-24 Time 15:29 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1997 SMC -406

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-20 Cont ID  
Sent By tlarge Date 2000-08-20 Time 06:22 Rev Time 0.33
Received By tlarge Date 2000-08-20 Time 06:11 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 SCUPPERS SHALL BE SIZED PER SPC 1109.3,
 FIGURE 1109.3.INCLUDE 1/2 AREA OF ANY
 VERTICAL WALLS PER SPC SEC.1108.3.
 SEE SPC APPENDIX"A",TABLE A101.2.
 SUBMIT DIMENSIONS OF SCUPPERS.DETAILS
 SHALL BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL.
  
 2)SCUPPERS SHALL COMPLY W/SBC SEC.
 1517.6.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-17 Cont ID  
Sent By gjoyce Date 2000-08-10 Time 08:27 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***