Plan Review Details - Permit 00071117
| Plan Review Stops For Permit 00071117 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-10-12 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-10-10 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1] DOOR SPECS SUBMITTED ARE NOT LEGABLE. | | | 2] DRAWINGS INDICATE FRENCH DOORS,"NANA" | | | #R2+1,REPORT SUBMITTED IS FOR STORE- | | | FRONT SYSTEM? | | | 3] PROVIDE TESTING FOR 48" DOORS | | | | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 659-8096 | | | EXT. 8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-10-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-10-04 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | SUBMIT PRODUCT TEST REPORTS FOR NEW | | | EXTERIOR WINDOWS AND DOORS. IMPACT | | | PROTECTION REQUIRED FOR EXTERIOR | | | GLAZING. | | | | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 659-8096 | | | EXTEN. 8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-15 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | INTERIOR WORK ONLY!!!!!! |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-08-19 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | 1]REVIEWED INTERIOR WORK ONLY,HISTORICAL | | | PLANNER DENIED ALL EXTERIOR WORK. | | | 2]VERIFY ACCESSIBILE ROUTE WILL BE | | | AVAILABLE AFTER FLOOR IS RAISED. | | | 3]SUBMIT DETAIL FOR INTERIOR WOOD COLUMN | | | 4]CLERIFY IF INTERIOR WALL DETAILED WILL | | | SERVE AS TENANT SEPERATION. | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 659-8096-#8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-10-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-04 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-04 |
Time |
13:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-09-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-13 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-13 |
Time |
18:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR MAIN PANEL.PLEASE SHOW ALL LOADS | | | THAT ARE CONTINUOUS LOADS AT 125%. | | | | | | | | | 2)NOTE:PLEASE SEE 220-12-B FOR TRACK | | | LIGHTING CALCS. | | | | | | 3)NOTE: PANEL SCHEDULE SUBMITTED NEEDS | | | TO BE MORE DETAILED ON CORRELATING | | | BRANCH CIRCUIT #`S. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-26 |
Time |
21:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-26 |
Time |
21:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT PANEL SCHEDULES TO | | | CORRELATE WITH BRANCH CIRCUIT #`S. | | | SHOW SIZE OF PANELS AND SUBMIT LOAD | | | CALCULATIONS FOR ADDITIONAL LOADS BEING | | | ADDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659=8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-08-03 |
Time |
11:03 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|