Plan Review Details - Permit 00071117
Plan Review Stops For Permit 00071117
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-10-12 Cont ID  
Sent By lmartine Date 2000-10-10 Time 08:30 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:001] DOOR SPECS SUBMITTED ARE NOT LEGABLE.
 2] DRAWINGS INDICATE FRENCH DOORS,"NANA"
 #R2+1,REPORT SUBMITTED IS FOR STORE-
 FRONT SYSTEM?
 3] PROVIDE TESTING FOR 48" DOORS
  
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096
 EXT. 8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-10-04 Cont ID  
Sent By lmartine Date 2000-10-04 Time 14:08 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 SUBMIT PRODUCT TEST REPORTS FOR NEW
 EXTERIOR WINDOWS AND DOORS. IMPACT
 PROTECTION REQUIRED FOR EXTERIOR
 GLAZING.
  
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096
 EXTEN. 8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-15 Cont ID  
Sent By lmartine Date 2000-09-15 Time 09:30 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00INTERIOR WORK ONLY!!!!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-19 Cont ID  
Sent By lmartine Date 2000-08-19 Time 10:40 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1]REVIEWED INTERIOR WORK ONLY,HISTORICAL
 PLANNER DENIED ALL EXTERIOR WORK.
 2]VERIFY ACCESSIBILE ROUTE WILL BE
 AVAILABLE AFTER FLOOR IS RAISED.
 3]SUBMIT DETAIL FOR INTERIOR WOOD COLUMN
 4]CLERIFY IF INTERIOR WALL DETAILED WILL
 SERVE AS TENANT SEPERATION.
  
 REVIEWED BY;
 LUIS MARTINEZ
 659-8096-#8456

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-04 Cont ID  
Sent By dpalmer Date 2000-10-04 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2000-10-04 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 18:46 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 18:46 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR MAIN PANEL.PLEASE SHOW ALL LOADS
 THAT ARE CONTINUOUS LOADS AT 125%.
  
  
 2)NOTE:PLEASE SEE 220-12-B FOR TRACK
 LIGHTING CALCS.
  
 3)NOTE: PANEL SCHEDULE SUBMITTED NEEDS
 TO BE MORE DETAILED ON CORRELATING
 BRANCH CIRCUIT #`S.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By dpalmer Date 2000-07-26 Time 21:12 Rev Time 0.00
Received By dpalmer Date 2000-07-26 Time 21:12 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT PANEL SCHEDULES TO
 CORRELATE WITH BRANCH CIRCUIT #`S.
 SHOW SIZE OF PANELS AND SUBMIT LOAD
 CALCULATIONS FOR ADDITIONAL LOADS BEING
 ADDED.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659=8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-03 Cont ID  
Sent By rturnque Date 2000-08-03 Time 11:03 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***