Plan Review Details - Permit 00071114
Plan Review Stops For Permit 00071114
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-15 Cont ID  
Sent By rmcdouga Date 2000-09-15 Time 09:48 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By rmcdouga Date 2000-08-04 Time 15:10 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)SPECIFY SPECIFIC TYPE OF HURRICANE
 ANCHOR THAT WILL BE USED TO PROVIDE
 CONTINOUS CONNECTION FROM FOUNDATION TO
 ROOF, AT EACH STUD AND RAFTER.
  
 2)SPECIFY TYPE OF EXTERIOR WALL COVERING
 THAT WILL BE USED.
  
 3)MINIMUM 1/2" O.D. FENDER WASHERS WILL
 BE REQUIRED ON TAPCONS ANCHORING PLATE
 TO SLAB.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 19:03 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE NOTE,,UNDER ART;110-26 OF
 THE NEC. THE WORK SHOWN ON DRAWINGS
 WILL NOT BE ALLOWED BY NEC.
 ALSO PLEASE SEE ART: 215-5 OF THE NEC.
  
 PLEASE SUBMIT ALL THE INFORMATION ON
 PLANS/DRAWINGS AS PREVIOUSLY ASKED FOR
 UNDER 215-5.
 PLEASE SEE FIRST SET OF NOTES. IF THERE
 ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-01 Cont ID  
Sent By dpalmer Date 2000-08-01 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2000-08-01 Time 19:03 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE GIVE CLARIFICATION ON
 THE SERVICE SHOWN. IS THIS IN ADDITION
 TO EXISTING SERVICE? OR NEW? PLEASE
 SUBMIT MORE DETAILS ON WIRE SIZES,
 CONDUIT SIZES, MAIN DISC SIZE ETC ETC.
  
 2)NOTE: PLEASE SUBMIT DETAIL ON OTHER
 ELECTRICAL WORKTO BE DONE FOR WASHER/
 DRYER? REPLACING EXISTING? IN ADDITION
 TO?
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM
 659-8096 EXT 8372

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-13 Cont ID  
Sent By tlarge Date 2000-09-13 Time 18:41 Rev Time 0.50
Received By tlarge Date 2000-09-13 Time 18:41 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT A SANITARY AND WATER ISOMETRIC
 FOR REVIEW THAT CLEARLY SHOWS THE
 ENTIRE SCOPE OF PLUMBING WORK BEING DONE
  
 2)THESE PLANS WILL NOT BE APPROVED
 UNLESS THE GAS DRAWINGS ARE REMOVED.THE
 GAS CONTRACTOR SHALL SUBMIT PROFESSIONAL
 QUALITY PLANS FOR THE GAS INSTALLATION.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-02 Cont ID  
Sent By tlarge Date 2000-08-02 Time 07:28 Rev Time 0.00
Received By tlarge Date 2000-08-02 Time 07:28 Sent To  
Notes
2001-01-08 00:00:00SUBMIT FLOOR PLAN SHOWING LOCATION OF
 ALL PLUMBING FIXTURES.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 2)SUBMIT ISOMETRIC DRAWING SHOWING ALL
 NEW PLUMBING AND CONNECTION TO EXISTING.
  
 3)INSTALLATION OF GAS SYSTEM SHALL BE
 DONE BY QUALIFIED PERSONNEL.(LICENSED
 CONTRACTOR).SUBMIT COMPLETE GAS
 DRAWING FOR REVIEW. SEE ATTACHED REQS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By gjoyce Date 2000-08-01 Time 12:49 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***