Plan Review Details - Permit 00071095
Plan Review Stops For Permit 00071095
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-27 Cont ID  
Sent By lmartine Date 2000-09-27 Time 06:54 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-28 Cont ID  
Sent By lmartine Date 2000-07-28 Time 17:22 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE COMMENTS ON BACK OF APPLICATION,LM

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-14 Cont ID  
Sent By dpalmer Date 2000-08-14 Time 09:57 Rev Time 0.00
Received By dpalmer Date 2000-08-14 Time 09:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-01 Cont ID  
Sent By dpalmer Date 2000-08-01 Time 10:55 Rev Time 0.00
Received By dpalmer Date 2000-08-01 Time 10:55 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE PROVIDE CLASS LOCATIONS
 FOR SURROUNDING AREAS OF PAINT BOOTH.
 PLEASE SHOW LIGHTING INTERIOR OR EXTERI-
 -OR FOR BOOTH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-09-21 Cont ID  
Sent By mcarsill Date 2000-09-21 Time 14:25 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-09-05 Cont ID  
Sent By mcarsill Date 2000-09-05 Time 12:27 Rev Time 0.00
Received By mcarsill Date 2000-09-05 Time 12:27 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE INFORMATION ON THE
 FLOORING TYPE MATERIAL LOCATED WITHIN
 SPRAY BOOTH.
 2) PLEASE INDICATE IF ANY VISION PANELS
 ARE PRESENT AND WHAT TYPE THEY ARE.
 3) HOW IS GROUNDING AND BONDING OF THE
 SPRAY BOOTH BEING ACCOMPLISHED.
 4) PLEASE INDICATE HOW MAKE-UP AIR IS
 BEING PROVIDED.
 5) EXHAUST DUCT TO BE A MINIMUM OF SIX
 FEET FROM ANY WALL OR ROOF.
 6) WHEN THE FIRE SPRINKLER SYSTEM
 ACTIVATES FOR THE BOOTH, AN AUDIBLE
 ALARM IS TO BE PROVIDED IF A BUILDING
 FIRE ALARM SYSTEM IS NOT PRESENT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-16 Cont ID  
Sent By mcarsill Date 2000-08-16 Time 11:20 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NOT ENOUGH INFORMATION TO REVIEW
 SPRAY BOOTH TO DETERMINE IF SPRAY BOOTH
 MEETS THE MINIMUM REQUIREMENTS OF NFPA
 33.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By mcarsill Date 2000-07-25 Time 14:37 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INFORMATION NOT DETAILED ENOUGH TO
 PERFORM PLAN REVIEW.
 2) NO FIRE PROTECTION SHOWN ON DRAWINGS.
 3) SPRAY BOOTH REQUIRED TO MEET MINIMUM
 CODE REQUIREMENT OF NFPA 33.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-09-26 Cont ID  
Sent By lsmith Date 2000-09-26 Time 12:05 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER ND9/26/00

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2000-09-14 Cont ID  
Sent By ndenmark Date 2000-09-14 Time 11:28 Rev Time 0.33
Received By ndenmark Date 2000-09-14 Time 11:28 Sent To  
Notes
2001-01-08 00:00:00DENIED
 SEE FIRE DEPT COMMENTS ON DUCT TERMINA-
 TION HEIGHT ABOVE ROOF
 PROVIDE INFORMATION ON MATERIAL TO BE
 USED IN BOOTH AND CUT OFF OF PRODUCT IN
 CASE OF FIRE TO SHOW COMPLIANCE W/
 NFPA 33

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-08-14 Cont ID  
Sent By ndenmark Date 2000-08-14 Time 11:11 Rev Time 0.50
Received By ndenmark Date 2000-08-14 Time 11:10 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.NOT ENOUGH INFORMATION PROVIDED TO
 REVIEW FOR COMPLIANCE WITH 1996 NFPA 33
 (REQUESTED LAST REVIEW ALSO)
 2. PROVIDE INFORMATION ON VENT DUCT
 (MATERIAL, SUPPORT, AND ROOF TERMINATION
 3. PROVIDE INFORMATION ON MATERIAL TO
 BE SUPPLIED TO BOOTH AND CUT OFF PER
 NFPA 33

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By ndenmark Date 2000-07-25 Time 14:17 Rev Time 0.33
Received By ndenmark Date 2000-07-25 Time 14:17 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
 1. PAINT SPRAY BOOTH TO COMPLY WITH 1996
 NFPA 33 PROVIDE PLANS AND SPECIFICATIONS
 SHOWING COMPLIANCE WITH STANDARD
 2. PAINT SPRAY BOOTH REQUIRES MECHANICAL
 PERMIT BY LICENSED MECHANICAL CONTRACTOR
 G.C. SHALL NOT INSTALL MECHANICAL PARTS
 OF BOOTH.
 3. FIRE PROTECTION PER NFPA 33,CH 7 REQD
 SUBMIT INFORMATION AT TIME OF PERMIT APP
 LICATION.


Account Summary | Usage Policy | Privacy Policy