Plan Review Details - Permit 00071087
Plan Review Stops For Permit 00071087
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-18 Cont ID  
Sent By mgonzale Date 2000-08-18 Time 15:04 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS
 SHEET C-2 REQUIRES HANDI CAP ACCESSABILI
 TY OFF EXECUTIVE CENTER DRIVE
 SEE MARKED PLAN WHERE HC RAMPS ARE
 REQUIRED.
 SHEET C-2 REFLECT DUMPSTER HAVING 12'-0"
 OPENING.IT IS REQUIRED THAT THE OPENIN
 G BE 12'-6" MINIMUM.
 SHEET C-4
 CLEAN-OUT REQUIRED ON SANITARY LATERAL
 SEE PLAN
 SHEET C-4
 DOUBLE DETECTOR CHECK VALVE MUST BE MOVE
 D CLOSER TO PROPERTY LINE.
 LIFT STATION INFORMATION MUST BE
 SUBMITTED TO PUBLIC UTILITIES SO THAT
 THE LIFT STATION DEPARTMENT REVIEWS IT.
 ALONG WITH THE SPECIFICATIONS OF ALL
 EQUIPMENT TO BE INSTALLED.
 1000 45TH STREET,
 WEST PALM BEACH, FL 33407
 (561) 659-8040 EXT. 2306
 ATTNETION MANNY GONZALEZ

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-06 Cont ID  
Sent By tlarge Date 2000-08-06 Time 10:50 Rev Time 1.50
Received By tlarge Date 2000-08-06 Time 09:30 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 1)A WELL DRILLING PERMIT IS REQD.FROM
 SO.FLA.WATER MANAGEMENT DISTRICT FOR THE
 IRRIGATION WELL PER FLA.STATUTE 373.342.
  
 2)A WATER USE PERMIT WILL BE REQD.FROM
 SO.FLA.WATER MANAGEMENT DISTRICT FOR THE
 IRRIGATION SYSTEM.A COPY OF THE WATER
 USE PERMIT SHALL BE SUBMITTED PRIOR TO
 ISSUANCE OF THE IRRIGATION PERMIT.FLA.
 STATUTE SEC.373.219.
  
 3) A PERMIT FROM DEP SHALL BE REQD.FOR
 THE WATER AND SEWER SYSTEM INSTALLATION.
  
 4)A PERMIT MAY BE REQD.FROM THE HEALTH
 DEPT.FOR THE WATER SYSTEM AND THE
 IRRIGATION WELL.COUNTYWIDE AMENDMENTS TO
 SPC SEC.101.4.7.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.