| Plan Review Stops For Permit 00071044 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-14 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-14 |
Time |
14:11 |
Rev Time |
0.50 |
| Received By |
drunnels |
Date |
2000-09-14 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO | | | STOREFRONT TO BE UNDER SEPERATE PERMIT | | | PER. BCBG (NATHALIE RYAN) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-12 |
Time |
12:27 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-12 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.PROVIDE PRODUCT APPROVAL FOR WINDOW | | | AND DOOR GLAZING FOR STORE FRONT/ METRO | | | DADE COUNTY OR SBCCI SSTD 12-97 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-03 |
Time |
09:01 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | 1. FLORIDA ENERGY CALULATIONS MUST BE | | | SIGNED BY THE OWNER/ AGENT | | | 2. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT WINDOW GLAZING FOR STOREFRONT/ | | | METRO DADE COUNTY OR SBCCI SSTD12-97 | | | 3. SUBMIT FIRE SPRINKLER APPLICATION AND | | | PLANS, FIRE SPRINKLER PERMIT MUST BE | | | ISSUED PRIOR TO BUILDING PERMIT BEING | | | ISSUED. | | | 4. SHEET A-5 COVE DETAIL INDICATES WOOD | | | CEILING JOIST,NOT PERMITED (BUILDING IS | | | TYPE 2 CONSTRUCTION) | | | ALL WOOD FRAMING TO BE FIRE RETARTANT | | | TREATED. 1997 SBC CHAPTERS 6 & 7 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-03 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-03 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-12 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-12 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) SUBMIT FLAME SPREAD CERTIFICATE FOR | | | AWNING. | | | 2) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON PLANS. PULL STATIONS ARE NOT | | | REQUIRED IN TENANT SPACE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-07-25 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | | FOR FIRE SPRINKLER SYSTEM DRAWINGS. | | | 2) EXITING THROUGH STOCKROOM PERMITTED | | | ONLY IF: NOT MORE THAN 50 PERCENT OF | | | EXIT ACCESS IS PROVIDED THROUGH | | | STOCKROOM, STOCKROOM NOT SUBJECT TO | | | LOCKING, MAIN AISLE THROUGH STOCKROOM | | | SHALL BE AT LEAST 44 INCHES AND BE | | | MAINTAINED AT THAT WIDTH. | | | 3) RED AWNING IS TO BE FIRE RETARDANT | | | SHOWN ON SHEET A-6. | | | 4) INTERIOR FINISH TO BE CLASS A OR B. | | | 5) PORTABLE FIRE EXTINGUISHERS REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-11 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-11 |
Time |
16:42 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-09-11 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | RETURN AIR PLENUM (MECH ROOM) SHALL BE | | | ENTIRELY OF NON COMBUSTIBLE MATERIALS | | | PER 1997 SMC 609.1.1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-25 |
Time |
09:04 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-25 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | 1.FIRE DAMPERS REQUIRED AT RATED WALLS | | | AS PER 1997 SMC 610.1.2.. | | | 2.PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2.. | | | 3.REQUIRES FLEX DUCT CONNECTION DETAIL. | | | 4.AHU MOUNTING DETAIL TO BE PROVIDED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-28 |
Time |
09:38 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-09-28 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-27 |
Time |
18:51 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-09-27 |
Time |
18:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2000-09-15 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-15 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
2000-09-15 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PERMIT AND PLANS TO BE | | | SUBMITTED SEPARATELY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-12 |
Time |
11:07 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-09-12 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)CLEARLY SHOW WIDTH OF TOILET ROOMS ON | | | THE PLAN.THE DIMENSIONS ON SHT.A-10 ARE | | | ILLEGIBLE.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | 2)SHT.A-3-DOOR CANNOT SWING INTO CLEAR | | | FLOOR SPACE FOR DRINKING FOUNTAIN.FACBC | | | SEC.4.22.2. | | | | | | 3)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | 4)SUBMIT OCCUPANT LOAD PER SPC TABLE 407 | | | SEE SPC SEC.407.1.3.FOR ALLOWED DEDUCT- | | | IBLE AREAS.(STOCKROOM CANNOT BE DELETED) | | | | | | 5)AN ADDITIONAL LAVATORY IS REQD.IN THE | | | WOMEN'S TOILET ROOM PER SPC TABLE 407. | | | | | | 6)SHOW DIMENSIONS/MOUNTING HEIGHTS OF | | | ALLHANDICAP FIXTURES AND APPURTENANCES | | | THE DIMENSIONS ON SHT.A-10 ARE ILLEGIBLE | | | | | | 7)WALLS AND FLOORS IN TOILET ROOMS SHALL | | | BE NONABSORBENT TO 4' PER SBC SEC.1204.2 | | | | | | 8)SEE ATTACHED REQS.FOR TOILET ROOMS | | | LOCATED IN STORAGE ROOMS | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-08-02 |
Time |
10:48 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW REF SPC 94 | | | (1A) SHT A-3,1 DRINKING FOUNTAIN | | | REQUIRED TAB 407, TO COMPLY W/FACBC | | | SEC 4.1.3 (10) (A) PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | (B)ACCESS TO PUBLIC REST ROOMS THRU A | | | STORAGE AREA,TO COMPLY W/ FACBC 4.1.2(7) | | | 4.1.3(16) SINAGE, REST RM'S TO BE | | | LOCATED ON AN ACCESSIBLE ROUTE FACBC | | | SEC4.1.3.(11),4.2.1,4.3.1,4.3.2(3), | | | 4.3.3 ACCESSIBLE ROUTE SHALL BE CLEARLY | | | DEFINEED ON PLANS. | | | SPC SEC 407.2.2 TOILET FACILITIES SHALL | | | BE AVILABLE TO PATRONS WITHOUT | | | RESTRICITION DURING NORMAL OPERATING | | | HOURS. | | | (B) 1 DRINKING FOUNTAIN REQUIRED TAB 407 | | | TO COMPLY W/FACBC 4.1.3(10)(A), | | | PROVISIONS SHALL BE MADE FOR PEOPLE WHO | | | HAVE TROUBLE BENDING OR STOOPING. | | | (C) H/C FITTING ROOM TO COMPLY W/FACBC | | | 4.35.4 FIXED BENCH ALONG THE LONGER | | | DIMENSION, THE BENCH SHALL BE 24"X48"X | | | 17" TO 19" AFF. | | | (D)CASH WRAP COUNTRER,TO COMPLY W/FACBC | | | 7.2(2)(I) A PORTION OF THEN COUNTER TO | | | BE 36"IN LGTH, WITH A MAX HGTH OF 36"AFF | | | END OF COMMENTS |
|
|