Plan Review Details - Permit 00071044
Plan Review Stops For Permit 00071044
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-14 Cont ID  
Sent By drunnels Date 2000-09-14 Time 14:11 Rev Time 0.50
Received By drunnels Date 2000-09-14 Time 14:11 Sent To  
Notes
2001-01-08 00:00:00PROVISO
 STOREFRONT TO BE UNDER SEPERATE PERMIT
 PER. BCBG (NATHALIE RYAN)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-12 Cont ID  
Sent By drunnels Date 2000-09-12 Time 12:27 Rev Time 1.00
Received By drunnels Date 2000-09-12 Time 12:27 Sent To  
Notes
2001-01-08 00:00:001.PROVIDE PRODUCT APPROVAL FOR WINDOW
 AND DOOR GLAZING FOR STORE FRONT/ METRO
 DADE COUNTY OR SBCCI SSTD 12-97

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By drunnels Date 2000-08-03 Time 09:01 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
 1. FLORIDA ENERGY CALULATIONS MUST BE
 SIGNED BY THE OWNER/ AGENT
 2. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT WINDOW GLAZING FOR STOREFRONT/
 METRO DADE COUNTY OR SBCCI SSTD12-97
 3. SUBMIT FIRE SPRINKLER APPLICATION AND
 PLANS, FIRE SPRINKLER PERMIT MUST BE
 ISSUED PRIOR TO BUILDING PERMIT BEING
 ISSUED.
 4. SHEET A-5 COVE DETAIL INDICATES WOOD
 CEILING JOIST,NOT PERMITED (BUILDING IS
 TYPE 2 CONSTRUCTION)
 ALL WOOD FRAMING TO BE FIRE RETARTANT
 TREATED. 1997 SBC CHAPTERS 6 & 7

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-08-03 Cont ID  
Sent By dpalmer Date 2000-08-03 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2000-08-03 Time 08:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By mcarsill Date 2000-09-12 Time 16:59 Rev Time 0.00
Received By mcarsill Date 2000-09-12 Time 16:59 Sent To  
Notes
2001-01-08 00:00:001) SUBMIT FLAME SPREAD CERTIFICATE FOR
 AWNING.
 2) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS. PULL STATIONS ARE NOT
 REQUIRED IN TENANT SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-25 Cont ID  
Sent By mcarsill Date 2000-07-25 Time 14:46 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 FOR FIRE SPRINKLER SYSTEM DRAWINGS.
 2) EXITING THROUGH STOCKROOM PERMITTED
 ONLY IF: NOT MORE THAN 50 PERCENT OF
 EXIT ACCESS IS PROVIDED THROUGH
 STOCKROOM, STOCKROOM NOT SUBJECT TO
 LOCKING, MAIN AISLE THROUGH STOCKROOM
 SHALL BE AT LEAST 44 INCHES AND BE
 MAINTAINED AT THAT WIDTH.
 3) RED AWNING IS TO BE FIRE RETARDANT
 SHOWN ON SHEET A-6.
 4) INTERIOR FINISH TO BE CLASS A OR B.
 5) PORTABLE FIRE EXTINGUISHERS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-11 Cont ID  
Sent By ndenmark Date 2000-09-11 Time 16:42 Rev Time 0.25
Received By ndenmark Date 2000-09-11 Time 16:42 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 RETURN AIR PLENUM (MECH ROOM) SHALL BE
 ENTIRELY OF NON COMBUSTIBLE MATERIALS
 PER 1997 SMC 609.1.1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By cthirben Date 2000-07-25 Time 09:04 Rev Time 1.00
Received By cthirben Date 2000-07-25 Time 09:04 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.FIRE DAMPERS REQUIRED AT RATED WALLS
 AS PER 1997 SMC 610.1.2..
 2.PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2..
 3.REQUIRES FLEX DUCT CONNECTION DETAIL.
 4.AHU MOUNTING DETAIL TO BE PROVIDED.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-09-28 Cont ID  
Sent By tlarge Date 2000-09-28 Time 09:38 Rev Time 0.50
Received By tlarge Date 2000-09-28 Time 09:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-27 Cont ID  
Sent By tlarge Date 2000-09-27 Time 18:51 Rev Time 0.75
Received By tlarge Date 2000-09-27 Time 18:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2000-09-15 Cont ID  
Sent By tlarge Date 2000-09-15 Time 09:28 Rev Time 0.00
Received By tlarge Date 2000-09-15 Time 09:28 Sent To  
Notes
2001-01-08 00:00:00PLUMBING PERMIT AND PLANS TO BE
 SUBMITTED SEPARATELY.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-12 Cont ID  
Sent By tlarge Date 2000-09-12 Time 11:07 Rev Time 2.00
Received By tlarge Date 2000-09-12 Time 08:20 Sent To  
Notes
2001-01-08 00:00:001)CLEARLY SHOW WIDTH OF TOILET ROOMS ON
 THE PLAN.THE DIMENSIONS ON SHT.A-10 ARE
 ILLEGIBLE.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 2)SHT.A-3-DOOR CANNOT SWING INTO CLEAR
 FLOOR SPACE FOR DRINKING FOUNTAIN.FACBC
 SEC.4.22.2.
  
 3)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 4)SUBMIT OCCUPANT LOAD PER SPC TABLE 407
 SEE SPC SEC.407.1.3.FOR ALLOWED DEDUCT-
 IBLE AREAS.(STOCKROOM CANNOT BE DELETED)
  
 5)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
  
 6)SHOW DIMENSIONS/MOUNTING HEIGHTS OF
 ALLHANDICAP FIXTURES AND APPURTENANCES
 THE DIMENSIONS ON SHT.A-10 ARE ILLEGIBLE
  
 7)WALLS AND FLOORS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO 4' PER SBC SEC.1204.2
  
 8)SEE ATTACHED REQS.FOR TOILET ROOMS
 LOCATED IN STORAGE ROOMS
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-02 Cont ID  
Sent By pschmitz Date 2000-08-02 Time 10:48 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW REF SPC 94
 (1A) SHT A-3,1 DRINKING FOUNTAIN
 REQUIRED TAB 407, TO COMPLY W/FACBC
 SEC 4.1.3 (10) (A) PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
 (B)ACCESS TO PUBLIC REST ROOMS THRU A
 STORAGE AREA,TO COMPLY W/ FACBC 4.1.2(7)
 4.1.3(16) SINAGE, REST RM'S TO BE
 LOCATED ON AN ACCESSIBLE ROUTE FACBC
 SEC4.1.3.(11),4.2.1,4.3.1,4.3.2(3),
 4.3.3 ACCESSIBLE ROUTE SHALL BE CLEARLY
 DEFINEED ON PLANS.
 SPC SEC 407.2.2 TOILET FACILITIES SHALL
 BE AVILABLE TO PATRONS WITHOUT
 RESTRICITION DURING NORMAL OPERATING
 HOURS.
 (B) 1 DRINKING FOUNTAIN REQUIRED TAB 407
 TO COMPLY W/FACBC 4.1.3(10)(A),
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
 (C) H/C FITTING ROOM TO COMPLY W/FACBC
 4.35.4 FIXED BENCH ALONG THE LONGER
 DIMENSION, THE BENCH SHALL BE 24"X48"X
 17" TO 19" AFF.
 (D)CASH WRAP COUNTRER,TO COMPLY W/FACBC
 7.2(2)(I) A PORTION OF THEN COUNTER TO
 BE 36"IN LGTH, WITH A MAX HGTH OF 36"AFF
 END OF COMMENTS