Plan Review Details - Permit 00071003
Plan Review Stops For Permit 00071003
Review Stop    
Rev No 1 Status P Date 2000-08-23 Cont ID  
Sent By drunnels Date 2000-08-23 Time 15:30 Rev Time 1.00
Received By drunnels Date 2000-08-23 Time 15:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-16 Cont ID  
Sent By drunnels Date 2000-08-16 Time 09:38 Rev Time 1.00
Received By drunnels Date 2000-08-16 Time 09:38 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION. FIRE SPRINKLER PERMIT TO BE
 ISSUED PRIOR TO BUILDING PERMIT BEING
 ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-07 Cont ID  
Sent By drunnels Date 2000-08-07 Time 07:54 Rev Time 1.00
Received By drunnels Date 2000-08-07 Time 07:53 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 1. FLORIDA ENERGY CALUCLATION SHEETS
 MUST BE SIGNED BY OWNER/AGENTT
 2.
 PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR WINDOWS & DOORS
 FOR STORE FRONT/METRO DADE COUNTY OR
 SBCCI SSTD12-97
 3.SHEET 0.02 BUILDING DATA CHANGE 1999
 SBC TO 1997 SBC
 4. SUBMIT FIRE SPRINKLER APPLICATION AND
 PLANS. FIRE SPRINKLER PERMIT MUST BE
 ISSUED PRIOR TO BUILDING PERMIT BEING
 ISSUED.
 5. SIGNS TO BE UNDER SEPERATE PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-25 Cont ID  
Sent By dpalmer Date 2000-07-25 Time 06:42 Rev Time 0.00
Received By dpalmer Date 2000-07-25 Time 06:42 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO *****************
  
 1)NOTE: PLEASE SUBMIT AND SHOW LOAD
 CALCULATIONS. SHOW ALL CONTINUOUS LOADS
 AT 125% (LIGHTING).
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL INSPECT-
 -IONIS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-25 Cont ID  
Sent By mcarsill Date 2000-07-25 Time 16:43 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE ALARM DEVICES SHOWN.
 2) ADD ILLUMINATED EXIT SIGN ABOVE
 DOOR LEADING FROM SALES AREA.
 3) DOOR FROM BATHROOM CANNOT INTERFERE
 WITH EXITING FROM SALES AREA.
 4) SOFFITS SHALL NOT INTERFERE WITH
 FIRE SPRINKLER HEAD DISCHARGE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-15 Cont ID  
Sent By cthirben Date 2000-08-15 Time 13:08 Rev Time 1.00
Received By cthirben Date 2000-08-15 Time 13:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By ndenmark Date 2000-08-04 Time 10:42 Rev Time 0.33
Received By ndenmark Date 2000-08-04 Time 10:42 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE W/ 1997 SMC 501.2

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-15 Cont ID  
Sent By tlarge Date 2000-08-15 Time 18:44 Rev Time 0.65
Received By tlarge Date 2000-08-15 Time 18:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-22 Cont ID  
Sent By pschmitz Date 2000-07-22 Time 10:35 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1A) SHT A-1 ACCESS TO H/C REST ROOMS
 THRU A STORAGE ROOM,IS NOT ACCESSIBLE
 TO THE PUBLIC AS REQUIRED, COMPLY
 WITH FCBC 4.1.3 (11).
 (B) 1 D/F REQ SPC 94 TAB 407 TO COMPLY
 W/FACBC 4.1.3 (10) (A) PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
 (C) PROVIDE ELEVATIONS OF H/C REST RM'S
 TOILET FIXTURES / ACCESSORY LEGEND
 SHOWING MOUNTING HIGHTS COMPLING
 W/FACBVC 4.1
 (D) SALES AND SERVICE COUNTER #101
 COMPLY W/FACBC 7.2(1),LGTH 36"X AFF 36".
 END OF COMMENTS