Plan Review Details - Permit 00070985
Plan Review Stops For Permit 00070985
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-10-20 Cont ID  
Sent By drunnels Date 2000-10-20 Time 07:58 Rev Time 1.00
Received By drunnels Date 2000-10-20 Time 07:58 Sent To  
Notes
2001-01-08 00:00:00REVISIONS 10/19/00

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-10-11 Cont ID  
Sent By drunnels Date 2000-10-11 Time 13:41 Rev Time 1.00
Received By drunnels Date 2000-10-11 Time 13:40 Sent To  
Notes
2001-01-08 00:00:001. PLANS MUST BE SEALED BY THE ARCH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-14 Cont ID  
Sent By bstaples Date 2000-08-14 Time 15:35 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. PRODUCT APPROVAL INFORMATION FOR
 WINDOW AND DOOR SYSTEM NOT SUBMITTED
 CONTRACTOR TO APPLY FOR PAY FEES AND
 SECURE A SEPERATE PERMIT PRIOR TO
 INSTALLING SYSTEM. SEE PRIOR NOTE #2
 2. SIGNS REQUIRE SEPERATE PERMITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By drunnels Date 2000-08-08 Time 14:48 Rev Time 1.00
Received By drunnels Date 2000-08-08 Time 14:48 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
 1. FLORIDA ENERGY SHEETS MUST BE SIGNED
 BY OWNER/AGENT.
 2. SUBMIT PRODUCT APPROVAL FOR WINDOWS
 AND DOORS FOR IMPACT RESSTANT GLAZING
 FOR STOREFRONT. METRO DADE COUNTY OR
 SBCCI.
 3. SHEET A2 SCHEDULE #5 PROVIDE UL#,
 BOTH SIDES OF WALL MUST BE COMPLETED
 PRIOR TO C.O. BEING ISSUED.
 4. SIGNS TO BE UNDER SEPERATE PERMIT.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2000-10-19 Cont ID  
Sent By dpalmer Date 2000-10-19 Time 20:46 Rev Time 0.00
Received By dpalmer Date 2000-10-19 Time 20:46 Sent To  
Notes
2001-01-08 00:00:00NO ELECTRICAL SHEETS ONLY BUILDING.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-10-11 Cont ID  
Sent By dpalmer Date 2000-10-11 Time 13:21 Rev Time 0.00
Received By dpalmer Date 2000-10-11 Time 13:21 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE ADDRESS ORIG PROVISO FROM
 FIRST REVIEW. THE AIC RATING FOR ALL
 EQUIPMENT BEING INSTALLED IS REQ`D BY
 110-9 AND 215-5 OF NEC.
  
  
 I PASSED THE ORIG. PLANS WITH A PROVISO
 THAT ASKED FOR THE ABOVE INFORMATION
 BEFORE ROUGH ELECTRICAL. PLEASE SUBMIT
 THE INFORMAITON FOR REVIEW WITH NEW REV-
 -ISIONS. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 15:01 Sent To  
Notes
2001-01-08 00:00:00NO E-SHEETS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-26 Cont ID  
Sent By dpalmer Date 2000-07-26 Time 12:21 Rev Time 0.00
Received By dpalmer Date 2000-07-26 Time 12:21 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO****************
  
 1)NOTE: PLEASE NOTE THAT ALL AIC RATINGS
 ARE TO BE SUMITTED FOR ALL EQUIPMENT.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRCIAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
  
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-08-29 Cont ID  
Sent By mcarsill Date 2000-08-29 Time 11:18 Rev Time 0.00
Received By mcarsill Date 2000-08-29 Time 11:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-08-21 Cont ID  
Sent By mcarsill Date 2000-08-21 Time 09:39 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) COMPLETE FIRE SPRINKLER DRAWINGS NOT
 INCLUDED WITH PLANS. THIS ITEM WAS
 PREVIOUSLY ADDRESSED.
 2) NO CLARIFICATION ON FLAME SPREAD
 DATA. ITEM PREVIOUSLY ADDRESSED.
 3) NO FIRE ALARM DEVICES SHOWN. ITEM
 PREVIOUSLY ADDRESSED.
 4) EXITING THROUGH STOCKROOM TO MEET
 CODE REQUIREMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-15 Cont ID  
Sent By mcarsill Date 2000-08-15 Time 08:43 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) DEFINE EXITING WITHIN SPACE.
 3) NO ILLUMINATED EXIT SIGNS OR
 EMERGENCY LIGHTING SHOWN.
 4) DEFINE TERRACE AREA AND HOW DOES IT
 EFFECT EXITING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By mcarsill Date 2000-07-26 Time 13:00 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INCOMPLETE FIRE SPRINKLER DRAWINGS
 ON PAGE M-2.M-2 PAGE REVEALS ONLY FOUR
 FIRE SPRINKLER HEADS AND SOME NOTES.
 2) FOUNTAIN LOCATED IN FRONT OF EXIT
 ACCESS TO MAIN EXIT DOORS. WHY IS THIS
 CONDITION SHOWN ON THE DRAWINGS.
 3) SOFFITS ARE NOT TO INTERFERE WITH
 FIRE SPRINKLER DISCHARGE PATTERNS.
 4) INTERIOR FINISH SHALL BE CLASS A OR
 B. CHECK FLAME SPREAD DATA ON PLANS.
 5) WHEN THE BUILDINGS FIRE ALARM SYSTEM
 IS ACTIVATED HOW IS IT HEARD IN CUTTER
 AND BUCK.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2000-10-06 Cont ID  
Sent By ndenmark Date 2000-10-06 Time 11:30 Rev Time 0.33
Received By ndenmark Date 2000-10-06 Time 11:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-09-05 Cont ID  
Sent By ndenmark Date 2000-09-05 Time 08:43 Rev Time 0.50
Received By ndenmark Date 2000-09-05 Time 08:43 Sent To  
Notes
2001-01-08 00:00:00REVISION DATED 9/1/2000 OK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2000-08-30 Cont ID  
Sent By ndenmark Date 2000-08-30 Time 08:22 Rev Time 0.25
Received By ndenmark Date 2000-08-30 Time 08:22 Sent To  
Notes
2001-01-08 00:00:00PERMIT TO BE ISSUED WITHOUT MECH,
 ENGINEER TO SUBMIT ADDITIONAL INFORMATIO
 AS REQUIRED FOR REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2000-08-21 Cont ID  
Sent By ndenmark Date 2000-08-21 Time 13:57 Rev Time 0.33
Received By ndenmark Date 2000-08-21 Time 13:57 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
  
 1. AIR BALANCE SCHEDULE SHOWING COMPLI-
 ANCE WITH 1997 SMC 501.2 HAS NOT BEEN
 PROVIDED AS REQUESTED ONE PRIOR REVIEWS
 PROVIDE SCHEDULE TO COMPLETE PLANS FOR
 REVIEW
 QUESTIONS? CALL NANCY DENMARK (561) 659-
 8096 EXT 8221

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-08-15 Cont ID  
Sent By cthirben Date 2000-08-15 Time 09:20 Rev Time 1.00
Received By cthirben Date 2000-08-15 Time 09:15 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 AS REQUESTED ON REVIEW DATED07.25.00
 1.PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2...
 2.PROVIDE OUTSIDE AIR SCHEDULE/CALCULA-
 TIONS AS PER ASHRAE 62-89...

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By cthirben Date 2000-07-25 Time 07:19 Rev Time 1.00
Received By cthirben Date 2000-07-25 Time 07:19 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.PROVIDE REQUIRES FIRE DAMPERS AT RATED
 WALLS WHERE APPLICABLE.
 2.PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2..
 3.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89.
 4DUCT MATERIAL SCHEDULE IS REQUIRED
 5.EXHAUST FANS DETAIL AND SCHEDULE
 REQUIRED.
 6. AHU MOUNTING DETAIL TO BE PROVIDED.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 12:17 Rev Time 0.30
Received By tlarge Date 2000-08-29 Time 12:13 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 POINT OF USE WATER HEATER SHALL NOT
 PROTRUDE INTO THE CLEAR AREAS SHOWN IN
 FIG.32 OF THE FACBC.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-21 Cont ID  
Sent By tlarge Date 2000-08-21 Time 18:22 Rev Time 0.30
Received By tlarge Date 2000-08-21 Time 18:22 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
 POINT OF USE WATER HEATER SHALL NOT
 PROTRUDE INTO THE CLEAR AREAS SHOWN IN
 FIG.32 OF THE FACBC.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-15 Cont ID  
Sent By tlarge Date 2000-08-15 Time 06:53 Rev Time 0.50
Received By tlarge Date 2000-08-15 Time 06:53 Sent To  
Notes
2001-01-08 00:00:001)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
 (ACCORDING TO SQ.FT.OF SPACE & OCCUPANT
 LOAD.)SEE SPC SEC.407.1.3 FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 2)H.C FITTING ROOM SHALL BE EQUIPPED W/
 BENCH FIXED ALONG WALL W/THE LONGER
 DIMENSION PER FACBC SEC.4.35.4.
  
 3)SHOW CLEAR INSIDE DIMENSIONS OF TOILET
 ROOMS.(LXW)COMPLY W/FACBC SEC.4.16.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-02 Cont ID  
Sent By pschmitz Date 2000-08-02 Time 09:37 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW REF SPC 94
 (1A) SHT A-2 CLEAR FLOOR SPACE H/C
 REST RM, COMPLY W/ FACBC 4.16.2 FIG 28
 MIN 66" FROM BACK WALL TO DOOR SWING.
 (B) FITTING RM, COMPLY W/FACBC 4.35.4
 FIXED BENCH 24"X 48"X 17" TO 19" AFF,
 ALONG THE LONGER DEMINISON OF THE WALL.
 (2) SHT M-2 DWV RISER DIAGRAM,
 MIN SIZEDRAIN PIPE UNDER SLAB 2",
 SEC.714.4
 END OF COMMENTS