| Plan Review Stops For Permit 00070985 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-10-20 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-20 |
Time |
07:58 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-20 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISIONS 10/19/00 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-10-11 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-11 |
Time |
13:41 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-11 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. PLANS MUST BE SEALED BY THE ARCH. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-08-14 |
Time |
15:35 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. PRODUCT APPROVAL INFORMATION FOR | | | WINDOW AND DOOR SYSTEM NOT SUBMITTED | | | CONTRACTOR TO APPLY FOR PAY FEES AND | | | SECURE A SEPERATE PERMIT PRIOR TO | | | INSTALLING SYSTEM. SEE PRIOR NOTE #2 | | | 2. SIGNS REQUIRE SEPERATE PERMITS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-08 |
Time |
14:48 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-08 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | | | | 1. FLORIDA ENERGY SHEETS MUST BE SIGNED | | | BY OWNER/AGENT. | | | 2. SUBMIT PRODUCT APPROVAL FOR WINDOWS | | | AND DOORS FOR IMPACT RESSTANT GLAZING | | | FOR STOREFRONT. METRO DADE COUNTY OR | | | SBCCI. | | | 3. SHEET A2 SCHEDULE #5 PROVIDE UL#, | | | BOTH SIDES OF WALL MUST BE COMPLETED | | | PRIOR TO C.O. BEING ISSUED. | | | 4. SIGNS TO BE UNDER SEPERATE PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
N |
Date |
2000-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-19 |
Time |
20:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-19 |
Time |
20:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO ELECTRICAL SHEETS ONLY BUILDING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2000-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-11 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-11 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE ADDRESS ORIG PROVISO FROM | | | FIRST REVIEW. THE AIC RATING FOR ALL | | | EQUIPMENT BEING INSTALLED IS REQ`D BY | | | 110-9 AND 215-5 OF NEC. | | | | | | | | | I PASSED THE ORIG. PLANS WITH A PROVISO | | | THAT ASKED FOR THE ABOVE INFORMATION | | | BEFORE ROUGH ELECTRICAL. PLEASE SUBMIT | | | THE INFORMAITON FOR REVIEW WITH NEW REV- | | | -ISIONS. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-15 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-15 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO E-SHEETS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-26 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-26 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO**************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL AIC RATINGS | | | ARE TO BE SUMITTED FOR ALL EQUIPMENT. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRCIAL INSPECT- | | | -ION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-29 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-29 |
Time |
11:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-21 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) COMPLETE FIRE SPRINKLER DRAWINGS NOT | | | INCLUDED WITH PLANS. THIS ITEM WAS | | | PREVIOUSLY ADDRESSED. | | | 2) NO CLARIFICATION ON FLAME SPREAD | | | DATA. ITEM PREVIOUSLY ADDRESSED. | | | 3) NO FIRE ALARM DEVICES SHOWN. ITEM | | | PREVIOUSLY ADDRESSED. | | | 4) EXITING THROUGH STOCKROOM TO MEET | | | CODE REQUIREMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-15 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) DEFINE EXITING WITHIN SPACE. | | | 3) NO ILLUMINATED EXIT SIGNS OR | | | EMERGENCY LIGHTING SHOWN. | | | 4) DEFINE TERRACE AREA AND HOW DOES IT | | | EFFECT EXITING. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-07-26 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INCOMPLETE FIRE SPRINKLER DRAWINGS | | | ON PAGE M-2.M-2 PAGE REVEALS ONLY FOUR | | | FIRE SPRINKLER HEADS AND SOME NOTES. | | | 2) FOUNTAIN LOCATED IN FRONT OF EXIT | | | ACCESS TO MAIN EXIT DOORS. WHY IS THIS | | | CONDITION SHOWN ON THE DRAWINGS. | | | 3) SOFFITS ARE NOT TO INTERFERE WITH | | | FIRE SPRINKLER DISCHARGE PATTERNS. | | | 4) INTERIOR FINISH SHALL BE CLASS A OR | | | B. CHECK FLAME SPREAD DATA ON PLANS. | | | 5) WHEN THE BUILDINGS FIRE ALARM SYSTEM | | | IS ACTIVATED HOW IS IT HEARD IN CUTTER | | | AND BUCK. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-06 |
Time |
11:30 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-10-06 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-05 |
Time |
08:43 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-09-05 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION DATED 9/1/2000 OK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-30 |
Time |
08:22 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-08-30 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PERMIT TO BE ISSUED WITHOUT MECH, | | | ENGINEER TO SUBMIT ADDITIONAL INFORMATIO | | | AS REQUIRED FOR REVIEW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-21 |
Time |
13:57 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-21 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | | | | 1. AIR BALANCE SCHEDULE SHOWING COMPLI- | | | ANCE WITH 1997 SMC 501.2 HAS NOT BEEN | | | PROVIDED AS REQUESTED ONE PRIOR REVIEWS | | | PROVIDE SCHEDULE TO COMPLETE PLANS FOR | | | REVIEW | | | QUESTIONS? CALL NANCY DENMARK (561) 659- | | | 8096 EXT 8221 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-15 |
Time |
09:20 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-15 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | AS REQUESTED ON REVIEW DATED07.25.00 | | | 1.PROVIDE AIR BALANCE SCHEDULE PER 1997 | | | SMC 501.2... | | | 2.PROVIDE OUTSIDE AIR SCHEDULE/CALCULA- | | | TIONS AS PER ASHRAE 62-89... |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-25 |
Time |
07:19 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-25 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | 1.PROVIDE REQUIRES FIRE DAMPERS AT RATED | | | WALLS WHERE APPLICABLE. | | | 2.PROVIDE AIR BALANCE SCHEDULE PER 1997 | | | SMC 501.2.. | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89. | | | 4DUCT MATERIAL SCHEDULE IS REQUIRED | | | 5.EXHAUST FANS DETAIL AND SCHEDULE | | | REQUIRED. | | | 6. AHU MOUNTING DETAIL TO BE PROVIDED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-29 |
Time |
12:17 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-08-29 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | POINT OF USE WATER HEATER SHALL NOT | | | PROTRUDE INTO THE CLEAR AREAS SHOWN IN | | | FIG.32 OF THE FACBC. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-21 |
Time |
18:22 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-08-21 |
Time |
18:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | POINT OF USE WATER HEATER SHALL NOT | | | PROTRUDE INTO THE CLEAR AREAS SHOWN IN | | | FIG.32 OF THE FACBC. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-15 |
Time |
06:53 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-15 |
Time |
06:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)AN ADDITIONAL LAVATORY IS REQD.IN THE | | | WOMEN'S TOILET ROOM PER SPC TABLE 407. | | | (ACCORDING TO SQ.FT.OF SPACE & OCCUPANT | | | LOAD.)SEE SPC SEC.407.1.3 FOR ALLOWED | | | DEDUCTIBLE AREAS. | | | | | | 2)H.C FITTING ROOM SHALL BE EQUIPPED W/ | | | BENCH FIXED ALONG WALL W/THE LONGER | | | DIMENSION PER FACBC SEC.4.35.4. | | | | | | 3)SHOW CLEAR INSIDE DIMENSIONS OF TOILET | | | ROOMS.(LXW)COMPLY W/FACBC SEC.4.16. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-08-02 |
Time |
09:37 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW REF SPC 94 | | | (1A) SHT A-2 CLEAR FLOOR SPACE H/C | | | REST RM, COMPLY W/ FACBC 4.16.2 FIG 28 | | | MIN 66" FROM BACK WALL TO DOOR SWING. | | | (B) FITTING RM, COMPLY W/FACBC 4.35.4 | | | FIXED BENCH 24"X 48"X 17" TO 19" AFF, | | | ALONG THE LONGER DEMINISON OF THE WALL. | | | (2) SHT M-2 DWV RISER DIAGRAM, | | | MIN SIZEDRAIN PIPE UNDER SLAB 2", | | | SEC.714.4 | | | END OF COMMENTS |
|
|