Plan Review Details - Permit 00070819
Plan Review Stops For Permit 00070819
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-11 Cont ID  
Sent By drunnels Date 2000-08-11 Time 12:34 Rev Time 1.00
Received By drunnels Date 2000-08-11 Time 12:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By drunnels Date 2000-08-04 Time 09:05 Rev Time 1.00
Received By drunnels Date 2000-08-04 Time 09:04 Sent To  
Notes
2001-01-08 00:00:00 
 1. SIGN TO BE PERMITED SEPERATLY
 2. FIRE SPRINKLER PERMIT TO BE ISSUED
 PRIOR TO BUILDING PERMIT BEING ISSUED.
 3. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASEING SUITE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By dpalmer Date 2000-08-10 Time 11:58 Rev Time 0.00
Received By dpalmer Date 2000-08-10 Time 11:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 18:11 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 18:11 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT*******************
  
 1)NOTE:PLEASE SUBMIT PANEL "D" WITH
 COMPLETE INFORMATION ON PANEL LIKE PANEL
 'A'.
  
 2)NOTE: PLEASE COMPLETE LOAD CALCULATION
 -S SHOWING ALL CONTINUOUS LOADS AT 125%
 (LIGHTING, SHOW WINDOW REC AND ALL LOADS
 FOR TRACK LIGHTING PER 210-62 AND 220-12
 -B. PLEASE ADJUST.
  
 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL EQUIPMENT MAINS AND PANELS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
  
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-09 Time 12:47 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 ON PLANS. SHOULD READ THE 1985 LIFE
 SAFETY CODE INSTEAD OF 1997 LIFE SAFETY
 CODE.
 2) FIRE SPRINKLER PLAN ALREADY SUBMITTED
 AND REVIEWED BY FIRE RESCUE, SEE PERMIT
 70570.
 3) SUBMIT COMPLETE FIRE ALARM SYSTEM
 PLANS AND PERMIT TO BUILDING DEPARTMENT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-11 Cont ID  
Sent By cthirben Date 2000-08-11 Time 11:22 Rev Time 1.00
Received By cthirben Date 2000-08-11 Time 11:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-21 Cont ID  
Sent By cthirben Date 2000-07-21 Time 11:50 Rev Time 0.00
Received By cthirben Date 2000-07-21 Time 12:00 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 FIRE/SMOKE DAMPER DETAIL AND LOCATION IS
 REQUIRES AT RATED WALLS.
 DUCT MATERIAL SCHEDULE REQUIRED.
 PROVIDE EXHAUST FANS DETAIL.
 ENERGY EFFICIENCY RATING REQUIRED PER
 FLORIDA ENERGY EFFICIENCY CODE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-09 Cont ID  
Sent By tlarge Date 2000-08-09 Time 18:08 Rev Time 0.50
Received By tlarge Date 2000-08-09 Time 18:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-22 Cont ID  
Sent By pschmitz Date 2000-07-22 Time 10:11 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1A) SHT A-1,H/C REST RM #2 DOOR SWING,
 IN TURNING RADIUS OF WHEEL CHAIR,
 COMPLY FACBC 4.15.5,CLEAR FLR SPACE.
 (B) DRINKING FOUNTAIN, CLEAR FLR SPACE,
 COMPLY W/FACBC 4.15.5
 (2) SHT P-1 WATER ISOMETRIC,SPC 94 CNTY
 WIDE AMD. SEC 607.7 NO MORE THAN 2
 FIXTURES SHALL BE SUPPLIED WITH 1/2"
 COLD WATER SUPPLY.
 END OF COMMENTS