Plan Review Details - Permit 00070801
Plan Review Stops For Permit 00070801
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-10-18 Cont ID  
Sent By drunnels Date 2000-10-18 Time 12:56 Rev Time 1.00
Received By drunnels Date 2000-10-18 Time 12:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-10-05 Cont ID  
Sent By drunnels Date 2000-10-05 Time 12:09 Rev Time 2.00
Received By drunnels Date 2000-10-05 Time 12:09 Sent To  
Notes
2001-01-08 00:00:001. COVER SHEET: PROJECT DATA SHOWS PLANS
 DESIGNED UNDER 1999 ERITION OF THE
 STANDARD BUILDING,PLUMBING, MECHANICAL,
 FIRE PREVENTION,AND NFPA LIFE SAFETY
 CODES- THE CITY OF WEST PALM BEACH IS
 UNDER THE 1997 SBC,1997 SMC,1994 SPC,
 AND THE 1985 NFPA LIFE SAFETY CODES WITH
 LOCAL AMENDMENTS/ WE DO NOT USE THE
 STANDARD FIRE PREVENTION CODE. PLEASE
 CHANGE PROJECT DATA INFORMATION TO
 REFLECT CORRECT CODES.
 2. SHEET A-6 DETAIL Q SHOWS "ACRYLIC
 BLOCK WINDOWS" IF THESE ARE TO BE USED
 PLEASE SUBMIT INFORMATION AS TO THE FIRE
 RESISTANCE RATING AND WIND LOAD CAPACITY
 SEE SBC 104.2
 3. SUBMIT SPECIFIC DETAILS FOR THE
 EXTERIOR METAL STUD SYSTEM AND DESIGN TO
 BE ANTICIPATED IN SBC 1606.1.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-16 Cont ID  
Sent By hpiskura Date 2000-08-16 Time 07:26 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER W/APP

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-16 Cont ID  
Sent By dpalmer Date 2000-10-16 Time 20:21 Rev Time 0.00
Received By dpalmer Date 2000-10-16 Time 20:20 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
  
 1)NOTE: UPON FURTHER REVIEW,,,,I HAVE
 READ YOUR RESPONSE TO AIC RATINGS ON
 SHEET E-4. PLEASE SEE E-4,,,AIC RATINGS
 ARE GIVEN FOR BRANCH BREAKERS, NOT PANEL
 -S OR MAIN? LIKE ORIGINALLY NOTED.
 PLEASE SEE 110-9/110-10/215-5
 MAINS/PANELS ALSO MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. BRANCH BREAKERS
 ONLY HAVE TO MEET THE SERIES RATINGS(
 DOWNSTREAM RATINGS)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELETCRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-27 Cont ID  
Sent By dpalmer Date 2000-09-27 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2000-09-27 Time 16:01 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE ALL ORIGINAL NOTES...
 NOT ALL NOTES WERE ADDRESSED.
  
 2)NOTE: THE 8 1/2X 11 IS NOT COMPLETE
 FOR THE LOAD CALCULATIONS REQUESTED.
 215-5
 ALL THE LOAD CALCS MUST BE ON PLANS FOR
 JOB.E SHEETS 1-4 FOR EACH PANEL AND
 MDP
 3)NOTE:PANEL SCHEDULES WERE NOT SUBMITT-
 -ED FOR ALL PANELS AS ASKED FOR ON THE
 FIRST REVIEW.MUST CORRELATE WITH FLOOR
 PLANS/LIGHTING LAYOUTS.
 4)NOTE: AIC RATINGS FOR ALL EQUIPMENT
 MAINS/PANELS/BREAKERS. ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER 110-
 -9 AND 215-5.
 5)NOTE:GROUNDING ELECTRODE SYSTEM SHOWN
 BUT NEEDS TO BE SHOWN TO COLD WATER
 ALSO/COLD WATER BOND.250-50
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATON
 FOR REVIEW.
 PLEASE SUBMIT AFTER ALL REVIEWS HAVE
 BEEN COMPLETED. NEED TO MAKE TWO COMPL-
 -ETE SETS FOR REVIEW AND PLEASE KEEP
 ANY OLD SHEETS THAT MAY HAVE ALREADY
 BEEN STAMPED AND /OR PASSED BY OTHER
 TRADES.
  
 ONCE AGAIN IF THERE ARE ANY QUESTIONS ON
 ANY OF THE ELECTRICAL NOTES PLEASE CALL!
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By dpalmer Date 2000-08-03 Time 11:00 Rev Time 0.00
Received By dpalmer Date 2000-08-03 Time 11:00 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE; PLEASE SUBMIT PANEL SCHEDULE FOR
 ALL PANELS.
  
 2)NOTE: PLEASE SUBMIT PLANS SHOWING WITH
 ALL THE REQ`MENTS FOR ARTS:517-50-C-1/
 517-30 -35 SEE FIG.517-30A
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL EQUIPMENT BEING INSTALLED. MAINS AND
 PANELS. 110-9 215-5
  
 4)NOTE: PLEASE SUBMIT GROUNDING ELECTRO-
 -DE SYSTEM.
  
 5)NOTE: PLEASE SUBMIT PLANS WITH EQUIP-
 -MENT LISTINGS.
  
 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR EACH PANEL AND FOR MDP. SHOW ALL
 CONTINUOUS LOADS AT 125%.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372
 JAKE LEAHY
 CHIEF ELECTRICAL INSPECTOR
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-02 Cont ID  
Sent By rturnque Date 2000-08-02 Time 14:54 Rev Time 0.55
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-21 Cont ID  
Sent By ndenmark Date 2000-09-21 Time 15:07 Rev Time 0.50
Received By ndenmark Date 2000-09-21 Time 15:07 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
  
  
 1. GFCI OUTLET REQUIRED ON ROOF FOR
 SERVICE OF MECHANICAL EQUIPMENT
 2.CONDENSATE TO TERMINATE OFF ROOF IN A
 PERVIOUS LOCATION. NOT ON ASPHALT OR
 CONRETE.
 3.MEDICAL GAS REQUIRES SEPARATE MECHAN-
 ICAL PERMIT. SUBMIT PLANS FOR REVIEW AT
 TIME OF PERMIT APPLICATION FOR THAT WORK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By ndenmark Date 2000-07-27 Time 13:36 Rev Time 0.50
Received By ndenmark Date 2000-07-27 Time 13:36 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1. PROVIDE OUSTIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE W/ 1997 SMC 501.2
 3 NO DETAIL FOR EQUIPMENT CURBS ON ROOF
 4. FAN SHUT DOWN REQUIRED BY DUCT SMOKE
 DETECTOR PER 1997 SMC 406 WITH NOTIFICAT
 ION PER NFPA 90A 4-4.4.2 OR 4-4.4.3
 5. MEDICAL GAS REQUIRES MECH PERMIT,
 SUBMIT PLANS AT TIME OF PERMIT APPLICATI
 ON FOR THIS WORK

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-09-30 Cont ID  
Sent By tlarge Date 2000-09-30 Time 09:24 Rev Time 1.50
Received By tlarge Date 2000-09-30 Time 08:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-16 Cont ID  
Sent By tlarge Date 2000-09-16 Time 09:53 Rev Time 1.25
Received By tlarge Date 2000-09-16 Time 09:10 Sent To  
Notes
2001-01-08 00:00:00 
 TITLE SHEET-THE PLUMBING CODE IN EFFECT
 IS THE 1994 STANDARD PLUMBING CODE,NOT
 1999.
  
 2)SHT.P-4 SHOWS 2"SANITARY LINE ON SITE
 PLAN DETAIL AND RISER DIAGRAM SHOWS 4".
 CLARIFY.
  
 3)SUBMIT ROOF PLAN SHOWING DISCHARGE OF
 CONDENSATE DRAINS.SHT.P-1 STILL SHOWS
 WASTE STACK UP TO RTU.DELETE STACK AND
 PIPING FROM PLANS IF NOT APPLICABLE.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 4)SHT.P-6-"WATER PIPING "SPECS.-IF
 CALCULATED AIR CHAMBERS ARE TO BE USED
 THEY SHALL COMPLY W/SPC SEC.607.8.3,
 607.8.4.
  
 5)SHT.P-3-CLARIFY LEGEND FOR PIPE
 SYSTEMS.BOTH ARE LABELED AS "1"IN THE
 LEGEND.CORRECTLY IDENTIFY EACH SYSTEM ON
 THE PLAN.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 6)SHT.P-6-MOUNTING HEIGHTS FOR DRINKING
 FOUNTAIN SHALL COMPLY W/FACBC SEC.4.15.
  
 7)CLEARLY SHOW TOILET ROOM DIMENSIONS
 (LXW)ON THE PLANS.THE DIMENSIONS ARE NOT
 SHOWN ON THE TITLE SHEET PER YOUR
 RESPONSE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-05 Cont ID  
Sent By tlarge Date 2000-08-05 Time 06:29 Rev Time 2.00
Received By tlarge Date 2000-08-04 Time 19:44 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT MANUF.DATA SHEETS ON WATER
 TREATMENT SYSTEM.WATER SUPPLY SYSTEM
 SHALL BE PROTECTED AGAINST CONTAMINATION
 PER SPC SEC.609.1.
  
 2)SUBMIT OCCUPANT LOAD OF SPACE BASED ON
 SPC TABLE 407.SEE SEC.407.1.3.FOR
 ALLOWED DEDUCTIBLE AREAS.
  
 3)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3.(10)(A).PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
  
 4)FLOOR DRAINS IN TOILET ROOMS SHALL BE
 EQUIPPED W/TRAP PRIMERS PER SPC SEC.
 409.4.1.1.
  
 5)CLEARLY SHOW DIMENSIONS OF ALL TOILET
 ROOMS.(LXW)COMPLY W/FACBC SEC.4.16.2.
  
 6)SINK AND CABINET IN LOUNGE SHALL BE
 HANDICAP ACCESSIBLE AND COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 7)THE MINIMUM NUMBER OF EACH TYPE OF
 PLUMBING FIXTURE SHALL COMPLY W/SPC SEC.
 407.
  
 8)WALLS IN TOILET ROOMS SHALL BE NON-
 ABSORBENT TO A HEIGHT OF 4'PER SBC SEC.
 1204.2.
  
 9)SUBMIT COMPLETE GAS RISER DIAGRAM FOR
 REVIEW AND MANUF.SHEETS FOR GAS EQUIP.
 SEE ATTACHED LIST OF REQS.
  
 10)PLANS REFER TO SITE PLAN FOR CONTIN-
 UATION OF PLUMBING LINES.SITE PLAN IS
 NOT INCLUDED IN SET.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 11)MAXIMUM LENGTH OF INDIRECT WASTE
 LINES SHALL COMPLY W/SPC 805.1.1,805.1.2
 WASTE LINES SHALL BE TRAPPED.
  
 12)CONDENSATE DRAINS FORM RTU'S CANNOT
 DISCHARGE INTO THE SANITARY SYSTEM.
 CONNECTION TO STORM SHALL BE INDIRECT
 AND OUTSIDE OF BUILDING WALLS.SPC 807.2,
 SMC SEC.304.8.3.
  
 13)SUBMIT SIGNED,DATED AND SEALED WATER
 RISER DIAGRAM FOR ALL WORK.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 14)SUBMIT DETAILS ON VENTING OF GAS
 WATER HEATER.SHOW SIZE OF VENT,DISTANCE
 TO TERMINATION PT.,COMPLY W/SGC CHAPT 6.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved