| Plan Review Stops For Permit 00070801 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-10-18 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-18 |
Time |
12:56 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-18 |
Time |
12:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-10-05 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-05 |
Time |
12:09 |
Rev Time |
2.00 |
| Received By |
drunnels |
Date |
2000-10-05 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. COVER SHEET: PROJECT DATA SHOWS PLANS | | | DESIGNED UNDER 1999 ERITION OF THE | | | STANDARD BUILDING,PLUMBING, MECHANICAL, | | | FIRE PREVENTION,AND NFPA LIFE SAFETY | | | CODES- THE CITY OF WEST PALM BEACH IS | | | UNDER THE 1997 SBC,1997 SMC,1994 SPC, | | | AND THE 1985 NFPA LIFE SAFETY CODES WITH | | | LOCAL AMENDMENTS/ WE DO NOT USE THE | | | STANDARD FIRE PREVENTION CODE. PLEASE | | | CHANGE PROJECT DATA INFORMATION TO | | | REFLECT CORRECT CODES. | | | 2. SHEET A-6 DETAIL Q SHOWS "ACRYLIC | | | BLOCK WINDOWS" IF THESE ARE TO BE USED | | | PLEASE SUBMIT INFORMATION AS TO THE FIRE | | | RESISTANCE RATING AND WIND LOAD CAPACITY | | | SEE SBC 104.2 | | | 3. SUBMIT SPECIFIC DETAILS FOR THE | | | EXTERIOR METAL STUD SYSTEM AND DESIGN TO | | | BE ANTICIPATED IN SBC 1606.1.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-08-16 |
Time |
07:26 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER W/APP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-16 |
Time |
20:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-16 |
Time |
20:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | | | | 1)NOTE: UPON FURTHER REVIEW,,,,I HAVE | | | READ YOUR RESPONSE TO AIC RATINGS ON | | | SHEET E-4. PLEASE SEE E-4,,,AIC RATINGS | | | ARE GIVEN FOR BRANCH BREAKERS, NOT PANEL | | | -S OR MAIN? LIKE ORIGINALLY NOTED. | | | PLEASE SEE 110-9/110-10/215-5 | | | MAINS/PANELS ALSO MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. BRANCH BREAKERS | | | ONLY HAVE TO MEET THE SERIES RATINGS( | | | DOWNSTREAM RATINGS) | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELETCRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-09-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-27 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-27 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE ALL ORIGINAL NOTES... | | | NOT ALL NOTES WERE ADDRESSED. | | | | | | 2)NOTE: THE 8 1/2X 11 IS NOT COMPLETE | | | FOR THE LOAD CALCULATIONS REQUESTED. | | | 215-5 | | | ALL THE LOAD CALCS MUST BE ON PLANS FOR | | | JOB.E SHEETS 1-4 FOR EACH PANEL AND | | | MDP | | | 3)NOTE:PANEL SCHEDULES WERE NOT SUBMITT- | | | -ED FOR ALL PANELS AS ASKED FOR ON THE | | | FIRST REVIEW.MUST CORRELATE WITH FLOOR | | | PLANS/LIGHTING LAYOUTS. | | | 4)NOTE: AIC RATINGS FOR ALL EQUIPMENT | | | MAINS/PANELS/BREAKERS. ALL MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER 110- | | | -9 AND 215-5. | | | 5)NOTE:GROUNDING ELECTRODE SYSTEM SHOWN | | | BUT NEEDS TO BE SHOWN TO COLD WATER | | | ALSO/COLD WATER BOND.250-50 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATON | | | FOR REVIEW. | | | PLEASE SUBMIT AFTER ALL REVIEWS HAVE | | | BEEN COMPLETED. NEED TO MAKE TWO COMPL- | | | -ETE SETS FOR REVIEW AND PLEASE KEEP | | | ANY OLD SHEETS THAT MAY HAVE ALREADY | | | BEEN STAMPED AND /OR PASSED BY OTHER | | | TRADES. | | | | | | ONCE AGAIN IF THERE ARE ANY QUESTIONS ON | | | ANY OF THE ELECTRICAL NOTES PLEASE CALL! | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-03 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-03 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE; PLEASE SUBMIT PANEL SCHEDULE FOR | | | ALL PANELS. | | | | | | 2)NOTE: PLEASE SUBMIT PLANS SHOWING WITH | | | ALL THE REQ`MENTS FOR ARTS:517-50-C-1/ | | | 517-30 -35 SEE FIG.517-30A | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ALL EQUIPMENT BEING INSTALLED. MAINS AND | | | PANELS. 110-9 215-5 | | | | | | 4)NOTE: PLEASE SUBMIT GROUNDING ELECTRO- | | | -DE SYSTEM. | | | | | | 5)NOTE: PLEASE SUBMIT PLANS WITH EQUIP- | | | -MENT LISTINGS. | | | | | | 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR EACH PANEL AND FOR MDP. SHOW ALL | | | CONTINUOUS LOADS AT 125%. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 | | | JAKE LEAHY | | | CHIEF ELECTRICAL INSPECTOR | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-08-02 |
Time |
14:54 |
Rev Time |
0.55 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-21 |
Time |
15:07 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-09-21 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | | | | | | | 1. GFCI OUTLET REQUIRED ON ROOF FOR | | | SERVICE OF MECHANICAL EQUIPMENT | | | 2.CONDENSATE TO TERMINATE OFF ROOF IN A | | | PERVIOUS LOCATION. NOT ON ASPHALT OR | | | CONRETE. | | | 3.MEDICAL GAS REQUIRES SEPARATE MECHAN- | | | ICAL PERMIT. SUBMIT PLANS FOR REVIEW AT | | | TIME OF PERMIT APPLICATION FOR THAT WORK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-07-27 |
Time |
13:36 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-07-27 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. PROVIDE OUSTIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE W/ 1997 SMC 501.2 | | | 3 NO DETAIL FOR EQUIPMENT CURBS ON ROOF | | | 4. FAN SHUT DOWN REQUIRED BY DUCT SMOKE | | | DETECTOR PER 1997 SMC 406 WITH NOTIFICAT | | | ION PER NFPA 90A 4-4.4.2 OR 4-4.4.3 | | | 5. MEDICAL GAS REQUIRES MECH PERMIT, | | | SUBMIT PLANS AT TIME OF PERMIT APPLICATI | | | ON FOR THIS WORK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-09-30 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-30 |
Time |
09:24 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-09-30 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-09-16 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-16 |
Time |
09:53 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
2000-09-16 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | TITLE SHEET-THE PLUMBING CODE IN EFFECT | | | IS THE 1994 STANDARD PLUMBING CODE,NOT | | | 1999. | | | | | | 2)SHT.P-4 SHOWS 2"SANITARY LINE ON SITE | | | PLAN DETAIL AND RISER DIAGRAM SHOWS 4". | | | CLARIFY. | | | | | | 3)SUBMIT ROOF PLAN SHOWING DISCHARGE OF | | | CONDENSATE DRAINS.SHT.P-1 STILL SHOWS | | | WASTE STACK UP TO RTU.DELETE STACK AND | | | PIPING FROM PLANS IF NOT APPLICABLE. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 4)SHT.P-6-"WATER PIPING "SPECS.-IF | | | CALCULATED AIR CHAMBERS ARE TO BE USED | | | THEY SHALL COMPLY W/SPC SEC.607.8.3, | | | 607.8.4. | | | | | | 5)SHT.P-3-CLARIFY LEGEND FOR PIPE | | | SYSTEMS.BOTH ARE LABELED AS "1"IN THE | | | LEGEND.CORRECTLY IDENTIFY EACH SYSTEM ON | | | THE PLAN.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | 6)SHT.P-6-MOUNTING HEIGHTS FOR DRINKING | | | FOUNTAIN SHALL COMPLY W/FACBC SEC.4.15. | | | | | | 7)CLEARLY SHOW TOILET ROOM DIMENSIONS | | | (LXW)ON THE PLANS.THE DIMENSIONS ARE NOT | | | SHOWN ON THE TITLE SHEET PER YOUR | | | RESPONSE. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-05 |
Time |
06:29 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-08-04 |
Time |
19:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT MANUF.DATA SHEETS ON WATER | | | TREATMENT SYSTEM.WATER SUPPLY SYSTEM | | | SHALL BE PROTECTED AGAINST CONTAMINATION | | | PER SPC SEC.609.1. | | | | | | 2)SUBMIT OCCUPANT LOAD OF SPACE BASED ON | | | SPC TABLE 407.SEE SEC.407.1.3.FOR | | | ALLOWED DEDUCTIBLE AREAS. | | | | | | 3)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.DRINKING FOUNTAIN SHALL COMPLY | | | W/FACBC SEC.4.1.3.(10)(A).PROVISIONS | | | SHALL BE MADE FOR PEOPLE WHO HAVE | | | TROUBLE BENDING OR STOOPING. | | | | | | 4)FLOOR DRAINS IN TOILET ROOMS SHALL BE | | | EQUIPPED W/TRAP PRIMERS PER SPC SEC. | | | 409.4.1.1. | | | | | | 5)CLEARLY SHOW DIMENSIONS OF ALL TOILET | | | ROOMS.(LXW)COMPLY W/FACBC SEC.4.16.2. | | | | | | 6)SINK AND CABINET IN LOUNGE SHALL BE | | | HANDICAP ACCESSIBLE AND COMPLY W/FACBC | | | SEC.4.24.1-4.24.7. | | | | | | 7)THE MINIMUM NUMBER OF EACH TYPE OF | | | PLUMBING FIXTURE SHALL COMPLY W/SPC SEC. | | | 407. | | | | | | 8)WALLS IN TOILET ROOMS SHALL BE NON- | | | ABSORBENT TO A HEIGHT OF 4'PER SBC SEC. | | | 1204.2. | | | | | | 9)SUBMIT COMPLETE GAS RISER DIAGRAM FOR | | | REVIEW AND MANUF.SHEETS FOR GAS EQUIP. | | | SEE ATTACHED LIST OF REQS. | | | | | | 10)PLANS REFER TO SITE PLAN FOR CONTIN- | | | UATION OF PLUMBING LINES.SITE PLAN IS | | | NOT INCLUDED IN SET.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | 11)MAXIMUM LENGTH OF INDIRECT WASTE | | | LINES SHALL COMPLY W/SPC 805.1.1,805.1.2 | | | WASTE LINES SHALL BE TRAPPED. | | | | | | 12)CONDENSATE DRAINS FORM RTU'S CANNOT | | | DISCHARGE INTO THE SANITARY SYSTEM. | | | CONNECTION TO STORM SHALL BE INDIRECT | | | AND OUTSIDE OF BUILDING WALLS.SPC 807.2, | | | SMC SEC.304.8.3. | | | | | | 13)SUBMIT SIGNED,DATED AND SEALED WATER | | | RISER DIAGRAM FOR ALL WORK.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 14)SUBMIT DETAILS ON VENTING OF GAS | | | WATER HEATER.SHOW SIZE OF VENT,DISTANCE | | | TO TERMINATION PT.,COMPLY W/SGC CHAPT 6. |
|
|