Plan Review Details - Permit 00070765
Plan Review Stops For Permit 00070765
Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-04-04 Cont ID  
Sent By dpalmer Date 2001-04-04 Time 19:06 Rev Time 0.00
Received By dpalmer Date 2001-04-04 Time 19:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-04-03 Cont ID  
Sent By dpalmer Date 2001-04-03 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2001-04-03 Time 18:33 Sent To  
Notes
2001-04-03 00:00:00**************UNSAT ***************
  
 NOTE: PLEASE NOTE THAT SINCE DEC,13,2000
 NO ONE HAS COME IN FOR AN ELECTRICAL
 PERMIT.
 PLEASE CALL THIS OFFICE TO CLEAR THIS MA
 TTER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 19:24 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 19:24 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLANS ARE STILL NOT CORRECT??
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOM PER NFPA-72
 2-2.1.1.1 NONE SHOWN ON PLANS ????
 ALSO ON EACH LEVEL.
 2)NOTE: PLEASE SEE E-1 SHOWS ELEVATOR
 AND NOTES TO RISER? THE RISER SHOWS
 EL 2P. IS THIS THE SAME THING? ALSO THE
 PANEL SCHEDULE THAT FEEDS EL-2P DOESNOT
 SHOW ELEVATOR? PLEASE CLARIFY.
  
 3)NOTE: PLEASE NOTE THAT ON 9/20/00 IT
 WAS REQ`STED BY THE CONTRACTOR TO THE
 BLDG PLAN REVIEWER AND MYSELF THAT THE
 PERMIT BE ISSUED WITHOUT THE ELECTRICAL
 BEING APPROVED. SEPARATE APPLICATION
 AND PLANS WERE REQ`D FOR ELEC.
 ON 11/21/00 A MISC ELEC DEMO PERMIT WAS
 ISSUED TO ELEC CONTRACTOR BECAUSE HE DID
 NOT HAVE PLANS. ONLY MISC ELEC DEMO!!!
 PLEASEHAVE ELECTRICAL CONTRACTOR
 SUBMIT CORRECTED PLAN WITH HIS PERMIT
 APPLICATION.
  
 4)NOTE: PLEASE SEE PLANS E-2 SERVICE
 CALCS SHOW LOAD AT 236AMPS. A NEW GUTTER
 IS SHOWN BUT NO NEW SERVICE CONDUCTORS??
 OR METERCAN AND SIZE.
  
 5)NOTE: PLANS ARE NOW SHOWING THE NEW
 EQUIPMENT AND NO AIC RATINGS??PER 110-9
 AND 215-5
  
  
 6)NOTE: PLEASE NOTE THAT COMPLETE AS-
 -BUILTS AND PANEL SCHEDULES ARE REQ`D
 BEFORE FINAL ELECTRICAL INSPECTION.
  
 7)NOTE: PLEASE SEE NOTES FORM OTHER
 REVIEWS. PANEL "B" SHOWN IN CLOSET.
 THE PANEL WILL HAVE TO BE MOVED OR THIS
 ROOM WOULD HAVE TO BE DEDICATED FOR
 ELECTRICAL/ EQUIPMENT. SEE 384-7
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2000-09-20 Cont ID  
Sent By jgomez Date 2000-09-20 Time 14:08 Rev Time 0.15
Received By dpalmer Date 2000-09-20 Time 14:08 Sent To  
Notes
2001-01-08 00:00:00CONTRACTOR TO APPLY FOR A SEPARATE
 PERMIT. 9-20-00.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-19 Cont ID  
Sent By dpalmer Date 2000-09-19 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2000-09-19 Time 12:49 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
  
 1)NOTE: AS PER CONVERSATION WITH THE
 ENGINEER MR. CHANE. THE ITEMS WE WENT
 OVER WERE NOT ADDRESSED AND CHANGES WERE
 NOT MADE ON THE PLANS.
  
 2)NOTE: PLEASE SEE 384-7 FOR PANEL "B"
 SHOWN ON E-3
  
 3)NOTE: UPON REVIEW OF PLANS THE SECOND
 TIME. MORE THAN 50% OF THE WIRING SHOWN
 NEW ON PLANS. PLEASE NOTE OUTLET SPACING
 TO BE BROUGHT UP TO CODE. 210-52
  
 PLEASE HAVE ENGINEER CALL TO SET UP A
 MEETING WITH PLAN REVIEWERS TO CLEAR UP
 ALL COMMENTS IN PERSON.
 PLEASE CALL
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-01 Cont ID  
Sent By dpalmer Date 2000-08-01 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2000-08-01 Time 16:59 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 PLEASE NOTE THAT MORE THAN 50% OF THE
 ELECTRICAL WORK IS BEING DONE. PLEASE
 NOTE :ALL ELECTRICAL WILL HAVE TO BE
 BROUGHT UP TO CODE.
  
 1)NOTE: PLEASE SHOW ALL EXISTING AND
 NEW MEAMS OF EGRESS LIGHTING PER 210-70
  
 2)NOTE: SMOKE DETECTORS WILL BE REQ`D
 PER NFPA-72 2-2.1.1.1 INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS. AND EACH LEVEL OF
 MULTI-LEVEL DWELLING.
  
 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210-8-A-6
  
 4)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 PLEASE SHOW PANEL "D" MCB . YOU SAY IT
 IS BEING FED BY 100 MCB ?? WHERE IS THIS
 E-3 SHOWS PANEL B?? WHERE IS THIS ON
 RISER DIADGRAM.
  
 5)NOTE: PLEASE SHOW LOCATION OF ALL
 EQUIPMENT/PANELS/MAINS ETC.
 MAINS MUST BE GROUPED PER 230-72
 PLEASE GIVE CLARIFICATION ON SERVICE
 ENTRANCE CONDUCTORS. COPPER/ALUM?
 YOU SHOW LOAD AT 222 AMPS AND NO ROOM
 FOR SPARE LOAD.PLEASE SHOW LOADS ON EACH
 PANEL.
  
 6)NOTE: PLEASE SHOW EXISTING ELECTRICAL
 OUTLETS ETC.SPACING SHALL BE BROUGHT UP
 TO CODE. PER 210-52
 7)NOTE: PLEASE SHOW EXISTING GROUNDING
 ELECTRODE SYSTEM.215-5
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
  
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-03-28 Cont ID  
Sent By pkrauss Date 2001-03-28 Time 08:44 Rev Time 0.30
Received By pkrauss Date 2001-03-28 Time 08:44 Sent To  
Notes
2001-03-28 00:00:00NO REVISIONS TO MECHANICAL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-08 Cont ID  
Sent By jleech Date 2000-12-08 Time 14:51 Rev Time 0.33
Received By jleech Date 2000-12-08 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2000-09-20 Cont ID  
Sent By jgomez Date 2000-09-20 Time 14:06 Rev Time 0.15
Received By jgomez Date 2000-09-20 Time 14:06 Sent To  
Notes
2001-01-08 00:00:00CONTRACTOR WILL APPLY FOR A SEPARATE
 PERMIT. 9-20-00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-28 Cont ID  
Sent By cthirben Date 2000-07-28 Time 15:33 Rev Time 1.00
Received By cthirben Date 2000-07-28 Time 15:32 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 CFM VALUE OF EACH SUPPLY DROP TO BE SUB-
 MITTED BEFORE INSPECTION.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-04-02 Cont ID  
Sent By jleech Date 2001-04-02 Time 13:54 Rev Time 0.50
Received By jleech Date 2001-04-02 Time 13:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-12-08 Cont ID  
Sent By jleech Date 2000-12-08 Time 14:52 Rev Time 0.33
Received By jleech Date 2000-12-08 Time 14:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-09-20 Cont ID  
Sent By jgomez Date 2000-09-20 Time 14:21 Rev Time 0.15
Received By jgomez Date 2000-09-20 Time 14:10 Sent To  
Notes
2001-01-08 00:00:00CONTRACTOR TO APPLY FOR SEPARATE PERMIT
 9-20-00.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-01 Cont ID  
Sent By tlarge Date 2000-08-01 Time 09:48 Rev Time 0.65
Received By tlarge Date 2000-08-01 Time 09:48 Sent To  
Notes
2001-01-08 00:00:001)SHT.M-2-PLANS SHOW GAS WATER HEATER IN
 CLOSET.GAS WATER HEATER CANNOT BE LOCAT-
 ED IN CLOSET PER SGC SEC.504.1.SEE
 "EXCEPTION" FOR INSTALLATION REQS.AND
 SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 COMPLY W/SGC SEC.402.4.`

Review Stop R ROOF PLAN REVIEW
Rev No 7 Status P Date 2001-05-22 Cont ID  
Sent By jgomez Date 2001-05-21 Time 18:50 Rev Time 2.00
Received By jgomez Date 2001-05-21 Time 18:49 Sent To  
Notes
2001-05-21 00:00:00APPROVED WITH PROVISO:
  
 1-MINIMUM HEADROOM AT STAIRS TO BE
 6'-8". SECTION 1007.7 SBC 1997.
 VERIFY IN FIELD THE HEADROOM BY
 EXISTING BEAM.
  
 2-PROVIDE COMPLETE SHOP DRAWINGS FOR
 RAILINGS.
 -PROFESSIONAL OF RECORD TO REVIEW ALL
 SHOP DRAWINGS PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 3-NEED TO PROVIDE SMOKE DETECTORS AT
 EACH STORY AS REQUIRED BY SECTION
 905.2.2 SBC 1997.
  
 4-PROVIDE COMPLETE STRUCTURAL BUCK
 DETAIL TO RESIST THE LOADS IMPOSSED
 BY THE GARAGE DOOR. SECTION 104.2.2
 CITY AMENDMENTS TO SBC 1997.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status F Date 2001-04-12 Cont ID  
Sent By jgomez Date 2001-04-12 Time 11:06 Rev Time 3.00
Received By jgomez Date 2001-04-11 Time 19:21 Sent To  
Notes
2001-04-12 00:00:00SECOND CHECKLIST TO REVISIONS:
 1-PROVIDE REVISED ENERGY CALCULATIONS
 TO REFLECT REVISIONS (NO DONE FROM
 CHECKLIST DATED 12-18-00).
 2-CEILING FANS:
 -ENGINEER TO REVIEW TABLE 6-6 FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION AND THEN
 CLEARLY INDICATE NUMBER, SIZE AND
 LOCATION OF CEILING FANS (NOT DONE
 FROM PREVIOUS CHECKLIST).
 3-SECTION THRU NEW STAIRS:
 -IT IS NOT CLEAR IF STAIRS PROVIDE THE
 6'-8" HEADROOM CLEARANCE BY EXISTING
 BEAM AREA. IF DRAWINGS ARE DONE TO
 SCALE HOW COME HEADROOM MEASURES 6'-4"
 BUT THE DIMENSION CALLED IS 6'-11".
 VERIFY IN FIELD ACTUAL HEIGHT OF BOTT.
 OF BEAM TO VERIFY HEADROOM.
 -PROVIDE COMPLETE INFORMATION REGARDING
 RAILINGS AND GUARDRAILS AS REQUIRED ON
 SECTION 1007 SBC 1997 (THIS INFO. WAS
 REQUESTED ON PROVISO DATED 9-20-00 BUT
 WAS NEVER PROVIDED)
 4-PROVIDE LANDING AS REQUIRED AT STEPS
 AT REAR SIDE OF THE HOUSE AS
 REQUIRED BY SECTION 1012.1.6 SBC 1997.
 5-SPECIFY SMOKE DETECTORS AT EACH STORY
 AS REQUIRED BY SEC. 905.2.2 SBC 1997.
 6-PROVIDE PRODUCT APPROVAL FOR GARAGE
 DOOR. (GARAGE DOOR WAS NOT PART OF THE
 SCOPE OF WORK ON ORIGINAL APPLICATION)
 7-CONTRACTOR NEEDS TO UPDATE INSURANCE.
 IT EXPIRED ON 2-20-01.
 8-PAY $7.50 ADDITIONAL RADON FEE FOR
 REVISED ADDITIONAL AREA. SEE RECEIPT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2000-12-19 Cont ID  
Sent By jgomez Date 2000-12-19 Time 08:57 Rev Time 2.50
Received By jgomez Date 2000-12-18 Time 17:17 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
  
 1-ARCHITECT DIDN'T SIGN, SEAL AND DATED
 THE DRAWINGS. CHAPTER 481 FL. STATUTES
  
 2-PROVIDE REVISED ENERGY CALCULATIONS.
  
 3-NEW ELEVATOR:
 -PROVIDE COMPLETE SECTION DETAIL THRU
 ELEVATOR SHAFT. SECTION 104.2.2 OF
 CITY AMENDMENTS TO SBC 1997.
 -PROVIDE COMPLETE SPECIFICATIONS FOR
 ELEVATOR CONFORMING TO ANSI/ASME A17.1
  
 4-SPECIFY NUMBER OF CEILING FANS AS
 REQUIRED BY TABLE 6-6 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING CONST.,
 1997 EDITION. SEE COMMENTS ON PLANS.
  
 5-CORRECT AREA TABULATIONS AS REQUIRED
 WITH NEW ENCLOSED AREA. SEE SHEET R1.
  
 6-SECOND FLOOR WINDOWS AT MASTER BEDRM
 DON'T COMPLY WITH EGRESS REQUIREMENTS
 SECTION 1005.4.4 SBC 1997. REVISE
 WINDOW SCHEDULE AS REQUIRED.
  
 7-SEE COMMENTS ON PLANS. INCLUDING
 COMMENTS BY THE OTHER TRADES.
  
 8-SECTION THRU NEW STAIRS SHOW HEADROOM
 CLEARANCE OF 6'-3" +/-.IT IS NOT
 ALLOWED. MIN. HEADROOM CLEARANCE IS
 6'-8" AS PER SECTION 1007.7 SBC 1997.
 REVISE STAIRS AS REQUIRED.
  
 9-NEED TO OBTAIN A PERMIT FOR MECHANICAL
 WORK. THERE IS NONE APPLIED FOR.
  
 10-ADDITIONAL FEES OF $101.00 ARE DUE
 FOR REVISION UPGRADES. ADDITIONAL
 CONSTRUCTION.
  
  
 NOTES:
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
 -PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 IN ORDER TO EXPEDITE THE REVIEW.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2000-09-20 Cont ID  
Sent By jgomez Date 2000-09-20 Time 12:09 Rev Time 1.00
Received By jgomez Date 2000-09-20 Time 12:09 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-STAIRWAY CONSTRUCTION:
 -REVISE STRUCTURAL DRAWINGS TO MATCH
 ARCHITECT'S NEW LAYOUT.
 -PROVIDE COMPLETE INFORMATION REGARDING
 CONSTRUCTION OF RAILINGS & GUARDRAILS.
 2-REVISE ALL ORIGINAL DRAWINGS AS REQ'D.
 SEE COMMENTS ON PLANS. INCLUDING THOSE
 BY THE OTHER TRADES.
 3-EGRESS WINDOWS AT MASTER BEDROOM NEED
 TO BE REVISED. (2)17X47 CASEMENT
 WINDOWS DON'T PROVIDE THE MINIMUM
 WIDTH REQUIRED. SEC. 1005.4.4 SBC 1997
 (THERE'S A MULLION IN BETWEEN).
 4-ROOFING, MECHANICAL, ELECTRICAL AND
 PLUMBING CONTRACTORS NEED TO APPLY FOR
 THEIR OWN PERMIT. REFERENCE THIS
 PERMIT APPLICATION NUMBER.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2000-09-19 Cont ID  
Sent By jgomez Date 2000-09-19 Time 17:20 Rev Time 0.50
Received By jgomez Date 2000-09-19 Time 17:20 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST
 1-STAIRWAY CONSTRUCTION:
 -REVISE STRUCTURAL DRAWINGS TO MATCH
 ARCHITECT'S NEW LAYOUT, WHICH COMPLIES
 WITH SECTION 1007 SBC 1997.
 -PROVIDE COMPLETE INFORMATION REGARDING
 RAILINGS AND GUARDRAILS CONSTRUCTION
 AND DESIGN.
 2-REVISE ALL ORIGINAL DRAWINGS AS REQ'D
 SEE COMMENTS ON PLANS. INCLUDING THOSE
 BY THE OTHER TRADES.
 3-EGRESS WINDOWS AT MASTER BEDROOM NEED
 TO BE REVISED. (2)17X47 CASEMENT
 WINDOWS DON'T PROVIDE THE MINIMUM
 WITH REQUIRED. SEC. 1005.4.4 SBC 1997.
 (THERE IS A MULLION IN BETWEEN WIND'S)
  
  
  
 NOTES:
 -CONTRACTOR NEEDS TO UPDATE LICENSE.
 -ELECTRICAL, MECHANICAL, PLUMBING AND
 ROOFING CONTRACTORS DIDN'T SIGN THE
 PERMIT APPLICATION. THEREFORE, THEY
 NEED TO APPLY FOR THEIR OWN PERMIT.
 -BUILDING REVIEW WAS APPROVED WITH A
 PROVISO. BUT, SINCE NOT REVISIONS WERE
 DONE TO THE ELECTRICAL AND PLUMBING
 PLANS, THEN, THEY WERE DENIED AGAIN.
 SO, IN ORDER TO EXPEDITE AND FACILITATE
 THE REVIEW PROCESS, IT IS RECOMMENDED
 TO REVISE ALL ORIGINAL DRAWINGS AND
 RE-SUBMIT A COMPLETE PACKAGE FOR ALL
 THE TRADES INVOLVED.
  
 -IMPORTANT: PLEASE RETURN REVIEWED SETS
 AFTER CORRECTIONS ARE DONE IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-09-14 Cont ID  
Sent By jgomez Date 2000-09-14 Time 21:17 Rev Time 3.50
Received By jgomez Date 2000-09-14 Time 21:16 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
  
 1-STAIRWAY CONSTRUCTION:
 -REVISE STRUCTURAL DRAWINGS TO MATCH
 ARCHITECT'S LAYOUT.
 -PROVIDE COMPLETE CONSTRUCTION INFO.
 REGARDING THE RAILINGS AND GUARDRAILS.
  
 2-REVISE ALL ORIGINAL DRAWINGS AS REQ'D
 SEE COOMENTS ON PLANS.
 3-EGRESS WINDOWS AT MASTER BEDROOM NEED
 TO BE REVISED. (2)17X47 WINDOWS DON'T
 PROVIDE THE MIN. WIDTH. SEC 1005.4.4.
  
 NOTES:
 -PROVIDE INFORMATION REQUESTED PRIOR TO
 ANY INSPECTIONS.
 -CONTRACTOR NEEDS TO UPDATE LICENSE.
 -ELECTRICAL, MECHANICAL, PLUMBING AND
 ROOFING CONTRACTORS DIDN'T SIGN THE
 APPLICATION. THEREFORE, THEY NEED TO
 APPLY FOR THEIR OWN PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-08-16 Cont ID  
Sent By jgomez Date 2000-08-16 Time 16:54 Rev Time 3.50
Received By jgomez Date 2000-08-16 Time 16:54 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-SITE PLAN INDICATES SOME WORK TO BE
 DONE ON THE SIDEWALK. COORDINATE WITH
 THE ENGINEERING DEPT. FOR SPECIFIC
 REQUIREMENTS PRIOR TO ANY CONSTRUCTION
 AT 659-8040. BET. 7:00 AM TO 3:00 PM.
 3-CLEARLY INDICATE ON PLANS WHAT'S NEW,
 WHAT IS EXISTING. WHAT IS GOING TO BE
 REPLACED, ETC.
 -PROVIDE MORE DIMENSIONS. EG OPENING
 DIMENSIONS, ETC
 -PROVIDE COMPLETE DOOR AND WINDOW SCHED
 4-REVISE ENERGY CALCULATIONS AS REQUIRED
 -SCOPE OF WORK IS NOT ONLY THE ADDITION
 ON SECOND FLOOR, BUT THE WHOLE HOUSE
 IS GOING TO BE CONSIDERABLY RENOVATED.
 SEC. 600.1.C.1 AND 600.1.C.2 FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
 -OWNER TO SIGN AND DATE THIS FORM TOO.
 5-REVISE DESIGN CERTIFICATION FOR BLDG
 CODE COMPLIANCE FORM:(STRUCTUR'L ENGR)
 -THIS IS A TWO STORY HOUSE. MEAN ROOF
 HEIGHT IS 24'-8" PLUS OR MINUS. REVISE
 THE BASIC VELOCITY PRESSURE AS REQ'D
 6-MASTER BEDROOM AND BEDROOMS #1 AND #2:
 -MUST MEET EGRESS REQUIREMENTS AS PER
 SECTION 1005.4.4 SBC 1997.
 7-AT LEAST ONE COMPLETE BATHROOM ON 1ST
 FLOOR MUST HAVE A DOOR THAT PROVIDES
 29" MINIMUM CLEAR OPENING. SECTION 11
 FLORIDA ACCESSIBILITY CODE FOR BLDG.
 CONSTRUCTION, 1997 EDITION.
 8-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AS PER CITY SAMPLE ATTACHED AND A
 COMPLETE KEY PLAN.
 -PROVIDE A COMPLETE CURRENT PRODUCT
 APPROVAL REPORT AND DRAWINGS AND
 HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHORS TO BE USED ACCORDING TO
 THE MEAN ROOF HEIGHT,DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE
 OR CONCRETE BLOCK).
 9-SPECIFY THE DESIGN PRESSURES THAT
 WERE CALCULATED AT ALL EXTERIOR
 OPENINGS. SECTION 1606 SBC 1997.
 10-NEW STAIR CONSTRUCTION:
 -NEED MORE INFORMATION LIKE DIMENSIONS,
 RISER TREAD RATIO, RAILINGS ECT.
 SEE SECTION 1007 SBC 1997.
 -STAIRS NEED TO BE REVISE TO COMPLY W/
 THE FOLLOWING SECTIONS: 1007.6.2 -
 1007.6.3 - 1007.7 - 1007.8.1 OF SBC/97
 11-PROVIDE SAFETY GLASS AT LIVING ROOM
 AND MASTER BATHRM. SEC 2405.2 SBC 1997
 12-PROVIDE CURRENT PRODUCT APPROVALS FOR
 FLAT ROOF SYSTEM AND BARREL TILE
 (CLEARLY INDICATE SYSTEM AND FASTENING
 TO BE USED).
 13-WINDOWS & DOORS SITE SPECIFIC PRODUCT
 APPROVALS:
 -ENGINEER WHO SIGNED ITEM #10 IS NOT
 THE PROFESSIONAL ENGINEER OF RECORD.
 -ITEMS #9 AND #10: ENGINEERS TO CLEARLY
 PROVIDE NAME, LICENSE NUMBER AND
 ADDRESS AS PER CHAPTER 471 OF FLORIDA
 STATUTES.
 -CLARIFY WHY ITEM #4.1.E.IV DOES NOT
 CONSIDER THE BUCK TO BE STRUCTURAL IF
 THE SPECIFIC INSTALLATION REQUIREMENTS
 SPECIFIES ATTACHMENT OF WINDOW OR DOOR
 TO THIS BUCK.
 -CLEARLY SPECIFY MODEL
 14-PROVIDE HANDRAILS AT STEPS LEADING
 TO POOL DECK. SEC 1007.5 SBC 1997.
 15-CLEARLY SPECIFY SIZES OF CEILING FANS
 AS PER TABLE 6-6 OF FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 16-SEE PLANS FOR ADDITIONAL COMMENTS,
 INCLUDING THOSE BY THE OTHER TRADES.
 17-UPDATE SOIL TEST REPORT. WE ADOPTED
 THE 1997 SBC. SEE SHEET #1 OF REPORT.
  
  
  
  
 NOTE:
  
 PLEASE RETURN REVIEWED SETS AFTER ALL
 REVISIONS/CORRECTIONS ARE DONE IN ORDER
 TO EXPEDITE THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-04-11 Cont ID  
Sent By sgraham Date 2001-04-11 Time 14:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-18 Cont ID  
Sent By gjoyce Date 2000-07-25 Time 07:50 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:0012' WALL NOT ALLOWED