Plan Review Details - Permit 00070686
Plan Review Stops For Permit 00070686
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-10-16 Cont ID  
Sent By hpiskura Date 2000-10-16 Time 09:49 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK REV #2 DATED 9/6/00

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-15 Cont ID  
Sent By hpiskura Date 2000-08-15 Time 09:25 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER W/APPLICATION HHP

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-12-28 Cont ID  
Sent By dpalmer Date 2000-12-28 Time 20:53 Rev Time 0.00
Received By dpalmer Date 2000-12-28 Time 20:53 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE PLANS. NOT ALL BRANCH
 CIRCUIT #`S ON PANEL"C" ARE ON FLOOR
 PLAN. NEED TO PLACE ALL BRANCH CIRUCIT
 #`S ON PLANS TO CORRELATE WITH PANEL
 SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-11-07 Cont ID  
Sent By dpalmer Date 2000-11-07 Time 20:01 Rev Time 0.00
Received By dpalmer Date 2000-11-07 Time 20:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-10-05 Cont ID  
Sent By dpalmer Date 2000-10-05 Time 14:28 Rev Time 0.00
Received By dpalmer Date 2000-10-05 Time 14:28 Sent To  
Notes
2001-01-08 00:00:00*************** NOTE ******************
  
  
 1) PER FL STATUESEC. 471.025 ALL PLANS
 MUST CONTAIN THE RAISED TYPE SEAL ON
 PLANS THAT ARE SUBMITTED FOR RECORD.
 ALSO 61G15-23.002
  
  
 PLEASE ADDRESS THE ABOVE AND SUBMIT PLAN
 -S FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-02 Cont ID  
Sent By dpalmer Date 2000-08-02 Time 19:08 Rev Time 0.00
Received By dpalmer Date 2000-08-02 Time 19:08 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH LOAD
 CALCUATIONS PER 220. PLEASE FIGURE ALL
 CONTINUOUS LOADS AT 125% (LIGHITNG,IT/
 SECURITY ETC) ALSO PLEASE DO NOT LIST AS
 ESTAMATED LOAD.
  
 2)NOTE:PLEASE CALRIFY THE SERVICE. YOU
 ARE SHOWING DELETION OF ATS/GEN/ETC.
 YOU ARE ALSO SHOWING THE 400 AMP PANEL
 AS MLO? WHERE IS MAIN? PLEASE PROVIDE A
 ONE-LINE DIAGRAM OF SERVICE.
  
 3)NOTE: PLEASE PROVIDE ROOF TOP OUTLET
 PER 210-63
  
 4)NOTE: PLEASE SHOW OUTLETS SERVING BATH
 (S) AS GFI/GFI PROTECTED. PER 210-8
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2000-08-15 Cont ID  
Sent By hpiskura Date 2000-08-15 Time 09:26 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-11-09 Cont ID  
Sent By mcarsill Date 2000-11-09 Time 13:25 Rev Time 0.00
Received By mcarsill Date 2000-11-09 Time 13:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-10-03 Cont ID  
Sent By mcarsill Date 2000-09-28 Time 11:34 Rev Time 0.00
Received By mcarsill Date 2000-09-28 Time 11:34 Sent To  
Notes
2001-01-08 00:00:001) EXISTING STORAGE IN EXIT HALLWAY IS
 TO BE REMOVED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By rturnque Date 2000-08-03 Time 14:59 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00THE COMMON PATH OF TRAVEL FROM THE MOST
 REMOTE POINT IN REFERENCED SUITE EXCEEDS
 50 FEET.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-06 Cont ID  
Sent By ndenmark Date 2000-10-06 Time 14:08 Rev Time 0.33
Received By ndenmark Date 2000-10-06 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By cthirben Date 2000-07-25 Time 15:51 Rev Time 1.00
Received By cthirben Date 2000-07-25 Time 15:43 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.DAMPERS REQUIRED AT RATED WALLS AS PER
 1997 SMC 610.1.2.. PROVIDE DETAIL.
 2.AIR BALANCE SCHEDULE REQUIRED AS PER
 1997 SMC 501.2..
 3.PROVIDE OUTSIDE AIR CALCULATION PER
 ASHRAE 62-89.
 4.FCU DATA REQUIRED FOR REVIEW.
 5.FAN SHUT DOWN REQUIRED PER NFPA 90A
 4.4.4.2 & 4.4.4.3..
 6.EXHAUST FANS DETAIL REQUIRED.
 7.FLEX DUCT CONNECTION DETAIL TO BE
 PROVIDED.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-11-21 Cont ID  
Sent By jleech Date 2000-11-21 Time 11:59 Rev Time 0.75
Received By jleech Date 2000-11-21 Time 11:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-10-22 Cont ID  
Sent By pschmitz Date 2000-10-22 Time 08:07 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) PLEASE ADDRESS PREVIOUS COMMENT
 DATED 9-18-00 & 10-05-00 BY T LARGE
 A/C CONDENSATE IS NOT ALLOWED TO
 DISCHARGE TO SANITARY SEWER.
 CONNECT TO DRY WELL,PLANTER,STORM
 DRAINAGE OUT SIDE OF BUILDING.
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-10-05 Cont ID  
Sent By tlarge Date 2000-10-05 Time 17:11 Rev Time 1.00
Received By tlarge Date 2000-10-05 Time 16:33 Sent To  
Notes
2001-01-08 00:00:001)SHT.P1.1-FLAT DRY VENTS ARE NOT
 PERMITTED PER SPC SEC.906.2.1.SEE F-2.
  
 2)WASTE FROM HVAC UNITS SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM.
 CONNECTION TO THE STORM SYSTEM SHALL BE
 INDIRECT AND OUTSIDE THE BUILDING WALLS.
 SPC SEC.804.3.
  
 3)ALL SHEETS SHALL BE SIGNED AND SEALED
 BY THE ENGINEER OF RECORD PER
 FAC 61G15-23.002.,F.S.471.025(1)
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-18 Cont ID  
Sent By tlarge Date 2000-09-18 Time 10:32 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:001)A LAVATORY IS REQD.IN THE ACCESSIBLE
 TOILET STALLS PER FACBC SEC.4.17.3.AND
 THE MIN.WIDTH SHALL BE AS FACBC SEC.
 4.17.3.
  
 2)SUBMIT OCCUPANT LOAD BASED ON
 HABITABLE FLOOR SPACE PER SPC 407.SEE
 SEC/407.1.3. FOR ALLOWED DEDUCTIBLE
 AREAS.
  
 3)THE URINAL SHALL BE INSTALLED AT
 HANDICAP HEIGHT.COMPLY W/FACBC SEC.4.18.
  
 4)WASTE FROM HVAC UNITS SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM.
 CONNECTION TO THE STORM SYSTEM SHALL BE
 INDIRECT OUTSIDE THE BUILDING WALLS.
 SPC SEC.804.3.
  
 5)BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED W/A VACUUM RELIEF LINE
 INSTALLED PER MANUF.RECOMMEND. AND SPC.
  
 6)FLAT DRY VENTS ARE NOT PERMITTED PER
 SPC SEC.906.2.1.SEE MOP SINK
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-05 Cont ID  
Sent By tlarge Date 2000-08-05 Time 12:58 Rev Time 0.75
Received By tlarge Date 2000-08-05 Time 12:32 Sent To  
Notes
2001-01-08 00:00:001)A LAVATORY IS REQD.IN THE ACCESSIBLE
 STALLS PER FACBC SEC.4.1.6(B).SHOW
 LENGTH AND WIDTH OF STALLS.COMPLY W/
 FACBC SEC.4.17.3,(MIN.WIDTH IS 83")AND
 FIG.30.
  
 2)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S RESTROOM PER SPC TABLE 407.
  
 3)URINAL SHALL BE INSTALLED AT HANDICAP
 HEIGHT.COMPLY W/FACBC SEC.4.18.
  
 4)WASTE FROM HVAC UNITS SHALL NOT
 DISCHARGE TO THE SANITARY.CONNECTION TO
 STORM SYSTEM SHALL BE BY INDIRECT OUT-
 SIDE OF BUILDING WALL.
  
 5)BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED W/A VACUUM RELIEF VALVE PER SPC
 507.1.2.

Review Stop Z ZONING
Rev No 1 Status N Date 2000-08-15 Cont ID  
Sent By hpiskura Date 2000-08-15 Time 09:26 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***