| Plan Review Stops For Permit 00070686 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-10-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-10-16 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK REV #2 DATED 9/6/00 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-08-15 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | LETTER W/APPLICATION HHP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2000-12-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-28 |
Time |
20:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-28 |
Time |
20:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE PLANS. NOT ALL BRANCH | | | CIRCUIT #`S ON PANEL"C" ARE ON FLOOR | | | PLAN. NEED TO PLACE ALL BRANCH CIRUCIT | | | #`S ON PLANS TO CORRELATE WITH PANEL | | | SCHEDULE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-11-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-07 |
Time |
20:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-07 |
Time |
20:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-10-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-05 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-05 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** NOTE ****************** | | | | | | | | | 1) PER FL STATUESEC. 471.025 ALL PLANS | | | MUST CONTAIN THE RAISED TYPE SEAL ON | | | PLANS THAT ARE SUBMITTED FOR RECORD. | | | ALSO 61G15-23.002 | | | | | | | | | PLEASE ADDRESS THE ABOVE AND SUBMIT PLAN | | | -S FOR REVIEW.IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-02 |
Time |
19:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-02 |
Time |
19:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH LOAD | | | CALCUATIONS PER 220. PLEASE FIGURE ALL | | | CONTINUOUS LOADS AT 125% (LIGHITNG,IT/ | | | SECURITY ETC) ALSO PLEASE DO NOT LIST AS | | | ESTAMATED LOAD. | | | | | | 2)NOTE:PLEASE CALRIFY THE SERVICE. YOU | | | ARE SHOWING DELETION OF ATS/GEN/ETC. | | | YOU ARE ALSO SHOWING THE 400 AMP PANEL | | | AS MLO? WHERE IS MAIN? PLEASE PROVIDE A | | | ONE-LINE DIAGRAM OF SERVICE. | | | | | | 3)NOTE: PLEASE PROVIDE ROOF TOP OUTLET | | | PER 210-63 | | | | | | 4)NOTE: PLEASE SHOW OUTLETS SERVING BATH | | | (S) AS GFI/GFI PROTECTED. PER 210-8 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-08-15 |
Time |
09:26 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-11-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-09 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-09 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-10-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-28 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-28 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) EXISTING STORAGE IN EXIT HALLWAY IS | | | TO BE REMOVED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-08-03 |
Time |
14:59 |
Rev Time |
0.30 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | THE COMMON PATH OF TRAVEL FROM THE MOST | | | REMOTE POINT IN REFERENCED SUITE EXCEEDS | | | 50 FEET. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-10-06 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-06 |
Time |
14:08 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-10-06 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-25 |
Time |
15:51 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-25 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | 1.DAMPERS REQUIRED AT RATED WALLS AS PER | | | 1997 SMC 610.1.2.. PROVIDE DETAIL. | | | 2.AIR BALANCE SCHEDULE REQUIRED AS PER | | | 1997 SMC 501.2.. | | | 3.PROVIDE OUTSIDE AIR CALCULATION PER | | | ASHRAE 62-89. | | | 4.FCU DATA REQUIRED FOR REVIEW. | | | 5.FAN SHUT DOWN REQUIRED PER NFPA 90A | | | 4.4.4.2 & 4.4.4.3.. | | | 6.EXHAUST FANS DETAIL REQUIRED. | | | 7.FLEX DUCT CONNECTION DETAIL TO BE | | | PROVIDED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-21 |
Time |
11:59 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2000-11-21 |
Time |
11:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-10-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-10-22 |
Time |
08:07 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) PLEASE ADDRESS PREVIOUS COMMENT | | | DATED 9-18-00 & 10-05-00 BY T LARGE | | | A/C CONDENSATE IS NOT ALLOWED TO | | | DISCHARGE TO SANITARY SEWER. | | | CONNECT TO DRY WELL,PLANTER,STORM | | | DRAINAGE OUT SIDE OF BUILDING. | | | END OF COMMENTSPAUL SCHMITZ | | | 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-10-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-05 |
Time |
17:11 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-10-05 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SHT.P1.1-FLAT DRY VENTS ARE NOT | | | PERMITTED PER SPC SEC.906.2.1.SEE F-2. | | | | | | 2)WASTE FROM HVAC UNITS SHALL NOT | | | DISCHARGE TO THE SANITARY SYSTEM. | | | CONNECTION TO THE STORM SYSTEM SHALL BE | | | INDIRECT AND OUTSIDE THE BUILDING WALLS. | | | SPC SEC.804.3. | | | | | | 3)ALL SHEETS SHALL BE SIGNED AND SEALED | | | BY THE ENGINEER OF RECORD PER | | | FAC 61G15-23.002.,F.S.471.025(1) | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-09-18 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-18 |
Time |
10:32 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)A LAVATORY IS REQD.IN THE ACCESSIBLE | | | TOILET STALLS PER FACBC SEC.4.17.3.AND | | | THE MIN.WIDTH SHALL BE AS FACBC SEC. | | | 4.17.3. | | | | | | 2)SUBMIT OCCUPANT LOAD BASED ON | | | HABITABLE FLOOR SPACE PER SPC 407.SEE | | | SEC/407.1.3. FOR ALLOWED DEDUCTIBLE | | | AREAS. | | | | | | 3)THE URINAL SHALL BE INSTALLED AT | | | HANDICAP HEIGHT.COMPLY W/FACBC SEC.4.18. | | | | | | 4)WASTE FROM HVAC UNITS SHALL NOT | | | DISCHARGE TO THE SANITARY SYSTEM. | | | CONNECTION TO THE STORM SYSTEM SHALL BE | | | INDIRECT OUTSIDE THE BUILDING WALLS. | | | SPC SEC.804.3. | | | | | | 5)BOTTOM FED WATER HEATERS SHALL BE | | | EQUIPPED W/A VACUUM RELIEF LINE | | | INSTALLED PER MANUF.RECOMMEND. AND SPC. | | | | | | 6)FLAT DRY VENTS ARE NOT PERMITTED PER | | | SPC SEC.906.2.1.SEE MOP SINK | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-05 |
Time |
12:58 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-08-05 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)A LAVATORY IS REQD.IN THE ACCESSIBLE | | | STALLS PER FACBC SEC.4.1.6(B).SHOW | | | LENGTH AND WIDTH OF STALLS.COMPLY W/ | | | FACBC SEC.4.17.3,(MIN.WIDTH IS 83")AND | | | FIG.30. | | | | | | 2)AN ADDITIONAL LAVATORY IS REQD.IN THE | | | WOMEN'S RESTROOM PER SPC TABLE 407. | | | | | | 3)URINAL SHALL BE INSTALLED AT HANDICAP | | | HEIGHT.COMPLY W/FACBC SEC.4.18. | | | | | | 4)WASTE FROM HVAC UNITS SHALL NOT | | | DISCHARGE TO THE SANITARY.CONNECTION TO | | | STORM SYSTEM SHALL BE BY INDIRECT OUT- | | | SIDE OF BUILDING WALL. | | | | | | 5)BOTTOM FED WATER HEATERS SHALL BE | | | EQUIPPED W/A VACUUM RELIEF VALVE PER SPC | | | 507.1.2. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-08-15 |
Time |
09:26 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|