Plan Review Details - Permit 00070684
Plan Review Stops For Permit 00070684
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-25 Cont ID  
Sent By lsmith Date 2000-07-25 Time 10:20 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-26 Cont ID  
Sent By dpalmer Date 2000-07-26 Time 17:53 Rev Time 0.00
Received By dpalmer Date 2000-07-26 Time 17:52 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE :PLEASE SEE COVER SHEET. YOU SHOW
 1996 NEC AS REFERENCE. PLEASE CHANGE TO
 "99" NEC.
  
 2)NOTE: PLEASE SEE LIGHTING PLAN KEY
 NOTES ON E-1.0. PLEASE CLARIFY NOTES
 1&2.??
  
 3)NOTE: PLEASE NOTE OUTLET SPACING TO
 MEET CITY OF WEST PALM BEACH AMNEDMENTS.
 EVERY 20` OF UNENCUMBERED WALL SPACE.
 210-50
  
 4)NOTE: PLEASESHOW THE GROUNDING ELECT-
 -RODE CONDUCTOR FORM TRANSFORMER TO
 BLD.STEEL. SIZE FROM 250-66.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH INSPECTION IS CALLED
 IN. IF THERE ARE ANY QUESTIONS PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop Z ZONING
Rev No 1 Status P Date 2000-07-25 Cont ID  
Sent By gjoyce Date 2000-07-25 Time 07:37 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***