Plan Review Details - Permit 00070641
Plan Review Stops For Permit 00070641
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-01-11 Cont ID  
Sent By dpalmer Date 2001-01-11 Time 09:08 Rev Time 0.00
Received By dpalmer Date 2001-01-11 Time 09:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-18 Cont ID  
Sent By dpalmer Date 2000-07-18 Time 10:40 Rev Time 0.00
Received By dpalmer Date 2000-07-18 Time 10:40 Sent To  
Notes
2001-01-08 00:00:00***************** PROVISO **************
  
 1)NOTE: PLEASE PROVIDE A REVISED PANEL
 SCHEDULE BEFORE FINAL.
  
 2)NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE ALL BEDROOMS AND IN COMMON AREAS
 AND ON EACH LEVEL OF MULTI-LEVEL UNITS.,
 NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE NOTE THE REQ`MENTS FOR
 210-11-C-3 BATH(S) CIRCUIT(S)MUST BE 20A
 AND #12 AWG.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372