| Plan Review Stops For Permit 00070635 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-01-24 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-01-24 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-24 00:00:00 | BUILDING COMMENTS | | | PROVISO----------------- | | | -------- | | | BUILDING COMMENTS | | | ------------------- | | | | | | SUBMIT PRODUCT TESTING FOR ALL EXTERIOR | | | DOORS, GLAZING AND ROOF COVER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-11-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-11-01 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SAME AS MARTINEZ NO CHANGE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-08-16 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING REVIEW COMMENTS | | | -------------------------- | | | | | | 1]EACH BUILDING SHALL BE PERMITED SEPER- | | | ATLY,CONTRACTOR SHALL SUBMIT TWO COMP- | | | LETE SETS OF DRAWINGS FOREACHBUIL- | | | ING.PLEASE INCLUDE SIGNED AND SEALED | | | SURVEYS. | | | 2]PROVIDE TEST REPORTS FOR ALL EXTERIOR | | | WINDOWS AND DOORS AND ROOF COVERS.ALL | | | EXTERIOR GLAZING SHALL COMPLY WITH | | | IMPACT RESISTANT TESTING. | | | 3]EXPLAIN SUPERIMPOSED LOADS ON PAGES | | | A9A AND B9,WHICH CODE AND FORMULA WERE | | | USED. | | | | | | | | | PLANS REVIEWED BY: | | | LUIS MARTINEZ | | | 659-8096#8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-08-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-13 |
Time |
19:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-13 |
Time |
19:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-31 |
Time |
18:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-31 |
Time |
18:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-10 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-10 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: YOU ARE SHOWING PARALLELED | | | 600MCM FOR SERVICE BUT ONLY SHOWING | | | 1/0`S FOR NEUTRAL.? | | | NEUTRAL LOAD IS SHOWN ALOT HIGHER THAN | | | THE CONDUCTORS ARE RATED. | | | PLEASE CORRELATE WIRE WITH LOADS SHOWN. | | | PER 310-16 | | | | | | 2)NOTE: PLEASE SUBMIT AND SHOW LOAD | | | CALCULATION FOR HOUSE PANEL TO INCLUDE | | | ALL CONTINUOUS LOADS AT 125% (LIGHTING) | | | ETC. | | | | | | 3)NOTE: YOU HAVE SUBMITTED PLANS SHOWING | | | BRKRS IN PANEL AT 10,000 AIC. PLEASE | | | GIVE AIC RATING OF MAIN. PER110-9 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FORREVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2000-07-20 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-07-20 |
Time |
15:28 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED WITH PROVISOS | | | 1.0 | | | PROVIDE 2 COPIES OF THE LATEST | | | SET OF PLANS TO MANNY GONZALEZ | | | AT PUBLIC UTILITIES 1000 45TH SUITE 15 | | | WEST PALM BEACH, FL 33407 | | | 561 659 8040 EXT. 2306 | | | 2.0 | | | ANY ITEMS INSTALLED IN THE ROW MUST | | | SUBMITTED FOR SHOP DRAWINGS APPROVAL | | | BY MANNY GONZALEZ AT PUBLIC UTILITIES. | | | 3.0 | | | DUMPSTER DOES NOT MEET MINIMUM REQUIRE- | | | MENTS. OUR STANDARD DUMPSTER DETAIL IS | | | BEING EMAILED AS WE SPEAK. | | | 4.0 | | | CALL OUT DUMPSTER AREA ON PLANS TO AVOID | | | CONFLICTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-08-03 |
Time |
14:10 |
Rev Time |
0.35 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-21 |
Time |
12:54 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-10-21 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | A/C CURBS ONLY NO MECH WORK THIS SHELL | | | BUILDING AT THIS TIME |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-07-26 |
Time |
14:01 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-07-26 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | | | | PROVIDE VENTILATION INFORMATION FOR ELEC | | | TRICAL ROOMS PER 1997 403 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-10-15 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-15 |
Time |
09:23 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
2000-10-15 |
Time |
07:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-05 |
Time |
12:01 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
2000-08-05 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SEE ATTACHED FOR REQS.FOR GREASE TRAP. | | | | | | 2)A WATER USE PERMIT IS REQD.FROM SO.FLA | | | WATER MNGMT.DISTRICT FOR THE IRRIGATION | | | SYSTEM PER FLA.STATUTE 373.219.SUBMIT | | | COPY OF PERMIT. | | | | | | 3)SHT.IR-1-SHOW LOCATION OF RAIN SENSOR | | | ON IRRIGATION SYSTEM. | | | | | | 4)1/2 THE AREA OF ANY VERTICAL WALL | | | (PARAPET) WHICH DIVERTS RAIN WATER TO | | | THE ROOF SHALL BE ADDED TO THE ROOF AREA | | | PER SPC SEC.1108.3.SHOW THIS IN YOUR | | | CALCULATIONS. | | | | | | 5)THE ADJUSTMENT IN YOUR CALCULATIONS | | | SHALL BE MADE TO THE SQUARE FOOTAGE | | | LISTED IN TABLES 1108.1 AND 1108.2 OF | | | THE SPC,NOT TO THE SQUARE FOOTAGE OF | | | THE ROOF.RECALCULATE YOUR PIPE SIZES. | | | | | | 6)SIZE OF FUTURE GREASE TRAPS SHALL BE | | | APPROVED BY CITY OF WPB WASTEWATER DIV. | | | CONTACT R.COMPO AT 561-835-7423. |
|
|