Plan Review Details - Permit 00070597
Plan Review Stops For Permit 00070597
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-23 Cont ID  
Sent By drunnels Date 2000-08-23 Time 14:05 Rev Time 1.00
Received By drunnels Date 2000-08-23 Time 14:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-14 Cont ID  
Sent By drunnels Date 2000-08-14 Time 11:31 Rev Time 1.00
Received By drunnels Date 2000-08-14 Time 11:30 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PLANS AND
 APPLICIATION. FIRE SPRINKLER PERMIT TO
 BE ISSUED PRIOR TO BUILDING PERMIT
 ISSURANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By bstaples Date 2000-08-08 Time 11:57 Rev Time 1.00
Received By bstaples Date 2000-07-24 Time 11:58 Sent To  
Notes
2001-01-08 00:00:00 
  
 1.FIRE SPRINKLER PERMIT REQUIRED PRIOR
 TO ISSURANCE OF BUILDING PERMIT.
 2. SUBMIT FLORIDA ENERGY SHEETS SIGNED
 AND SEALED AS REQUIRED.
 3.SIGNS TO REQUIRED TO BE PERMITED UNDER
 ADDITIONAL PERMIT.
 4.SUPPLY DADE COUNTY PRODUCT APPROVAL AS
 NOTED ON SHEET "A-4 NOTE 2" FOR ROLLING
 DOOR AND EXTERIOR GLAZING.
 5.COVER SHEET LIST SHEET "A-7 DETAILS"
 SHEET NOT IN SET.
 7.LEGEND ON SHEET A-1 REFERS TO SHEET
 "A6.01" THIS SHEET NOT IN SET.
 8.SHOW THAT PASSAGE #007 MEETS MINIMUM
 EGRESS CLEARENCE AS REQUIRED IN SECTION
 1003.2 1997 SBC

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 12:43 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-08 Cont ID  
Sent By dpalmer Date 2000-08-08 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2000-08-08 Time 09:45 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ***************
  
 1)NOTE: PLEASE SUBMIT A REVISED LOAD
 CALCULATIONS SHOWINGALL CONTINUOUS
 LOADS AT 125%. THIS IS TO INCLUDE LOADS
 ON BOTH PANELS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH.
  
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By dpalmer Date 2000-07-24 Time 06:41 Rev Time 0.00
Received By dpalmer Date 2000-07-24 Time 06:41 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO ****************
  
 1)NOTE ;PLEASE SHOW LOAD CALCULATIONS!
 NO CLCALCULATIONS SUBMITTED.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%
 (LIGHTING) ETC. PER ART 220
  
 2)NOTE: PLEASE INDICATE THE REQ`D SHOW
 WINDOW OUTLET. PER 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS.
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-23 Cont ID  
Sent By mcarsill Date 2000-08-23 Time 14:03 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-11 Cont ID  
Sent By mcarsill Date 2000-08-11 Time 12:50 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) FIRE SPRINKLER PLANS IN DRAWING
 APPEAR TO BE SATISFACTORY.
 2) NO FIRE ALARM EQUIPMENT SHOWN ON
 POWER PLAN. HOW IS THE BASE BUILDING
 FIRE ALARM SYSTEM HEARD IN TENANT
 SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By mcarsill Date 2000-07-26 Time 13:29 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER SYSTEM DRAWINGS
 OR HYDRAULIC CALCULATIONS PROVIDED WITH
 DRAWINGS.
 2) INTERIOR FINISH SHALL BE CLASS A OR
 B.
 3) STREET ADDRESS PLANNED FOR BELOW
 STORE NAME TO COMPLY WITH CITY CODE,
 ADDRESSES.
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 5) WHEN BUILDINGS FIRE ALARM SYSTEM
 IS ACTIVATED HOW IS IT HEARD IN SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-09-13 Cont ID  
Sent By ndenmark Date 2000-09-13 Time 11:31 Rev Time 0.25
Received By ndenmark Date 2000-09-13 Time 11:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-07 Cont ID  
Sent By cthirben Date 2000-08-07 Time 07:27 Rev Time 1.00
Received By cthirben Date 2000-08-07 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-18 Cont ID  
Sent By cthirben Date 2000-07-18 Time 11:05 Rev Time 0.00
Received By cthirben Date 2000-08-04 Time 16:12 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1. PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 2. FLEX DUCT CONNECTION DETAIL.
 3. REQUIRES ENERGY EFFIECIENCY RATING OF
 AHU PER FL. ENERGY EFFFICIENCY CODE.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-09 Cont ID  
Sent By tlarge Date 2000-09-09 Time 06:04 Rev Time 0.25
Received By tlarge Date 2000-09-09 Time 05:50 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 15:33 Rev Time 0.50
Received By tlarge Date 2000-08-17 Time 15:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-14 Cont ID  
Sent By tlarge Date 2000-08-09 Time 18:15 Rev Time 0.50
Received By tlarge Date 2000-08-09 Time 18:14 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT ARCHITECTURAL PLANS FOR REVIEW.
 SHOW DIMENSIONS (LXW)OF TOILET ROOMS.
 COMPLY W/FACBC SEC.4.16.
  
 2)SUBMIT OCCUPANT LOAD OF SPACE BASED ON
 SQUARE FEET OF HABITABLE FLOOR SPACE.SEE
 SPC SEC.407.1.3.FOR ALLOWED DEDUCTIBLE
 AREAS.
  
 3)A DRINKING FOUNTAIN SHALL BE INSTALLED
 PER TABLE 407 OF SPC.THE CODE DOESN'T
 ALLOW FOR A SUBSTITUTION.DRINKING FOUN-
 TAIN SHALL COMPLY W/FACBC SEC.4.1.3.(10)
 (A).PROVISIONS SHALL BE MADE FOR PEOPLE
 WHO HAVE TROUBLE BENDING AND STOOPING.
  
 4)WATER CLOSETS NOT PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 5)SUBMIT COMPLETE SETS OF PLANS FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-20 Cont ID  
Sent By pschmitz Date 2000-07-20 Time 10:45 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT A-1 DRINKING FOUNTAIN IS REQ.
 SPC 94 TAB 407, ALSO TO COMPLY WITH
 FACBC SEC4.1.3. (10) (A). PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
 END OF COMMENTS