| Plan Review Stops For Permit 00070571 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-05 |
Time |
07:35 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-05 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | STOREFRONT UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-21 |
Time |
12:29 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-21 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. FLORIDA ENERGY SHEETS MUST BE SIGNED | | | BY OWNER/AGENT | | | 2.SUBMIT FIRE SPRINKLER PLANS AND PERMIT | | | APPLICATION. | | | 3. PLANS MUST BE SEALED AND SIGNED BY | | | ARCHITECT | | | | | | | | | "PROVISO" | | | STOREFRONT UNDER SEPERATE PERMIT | | | SIGNS UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-20 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-07-20 |
Time |
15:03 |
Rev Time |
4.00 |
| Received By |
fknapp |
Date |
2000-07-20 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | ***************UNSAT******************** | | | | | | 1)PROVIDE COMPLETED FLORIDA ENERGY | | | SHEETS WITH REQUIRED SEAL AND SIGNATURES | | | | | | 2)FIRE SPRINKLER CONTRACTOR MUST SECURE | | | PERMIT PRIOR TO ISSUANCE OF THE BUILDING | | | PERMIT. | | | | | | 3)PROVIDE CURRENT COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS FOR IMPACT | | | RESISTANT WINDOWS AND DOORS. | | | | | | 4)PROVIDE LIFE SAFETY PLAN THAT SHOWS | | | CONTINUATION OF REAR EXIT FROM TENNANTS. | | | | | | 5)KEY PLAN IS NOT CORRECT TO PLAN OF | | | CITY PLACE. | | | | | | 6)SHEET A.07 REFERENCES A-15 WHICH IS | | | NOT SUPPLIED. | | | | | | 7)SECOND SHEET A.01 REFERENCES DOORS AND | | | TOILETS. IS THIS SHEET MISNUMBERED? | | | | | | 8)ALL WOOD BUCKS, HEADERS, BLOCKING, ETC | | | IN PARTITIONS, TO BE APPROVED FIRE | | | RETARDANT TREATED LUMBER. | | | | | | 9)PROVIDE FIRE RATING ON FOAM BOARD ON | | | SHEET A-03 FOR ASSEMBLY OCCUPANCY. | | | | | | 10)PROVIDE LETTER FROM SPECIAL INSPECTOR | | | THAT WORK IS READY TO BEGIN. | | | | | | 11)SEPARATE PERMIT IS REQUIRED FOR SIGNS | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8392 | | | | | | FRANK KNAPP | | | BUILDING PLAN REVIEW | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-28 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-28 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-21 |
Time |
21:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-21 |
Time |
21:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE FIRST SET OF NOTES. | | | PLEASE "SHOW" LOAD CALCULATIONS. EG | | | SQ. FT AND THE BREAKDOWN FOR LOADS AT | | | 125%. PLEASE SHOW BEFORE AND AFTER. | | | | | | 2)NOTE: PLEASE MAKE MINOR CORRECTION FOR | | | TOTAL KVA ON "K1" | | | | | | 3)NOTE: PLEASE MAKE CORRECTION FOR PANEL | | | REF. AS "H2A" SHOULD BE "H1A" | | | | | | 4)NOTE: PLEASE SEE SHEET E 3.1 THERE IS | | | A NOTE FOR TRANSFORMER TO SEE E-01?? | | | IS THIS THE NOTE/ DETAIL ON E5-1? | | | PLEASE CALRIFY. | | | | | | 5)NOTE: PLEASE SEE "K1" NOTE ADDED LOAD | | | EXCEEDS LOAD SHOWN ON "K2" FOR TOTAL | | | LOAD. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW, | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-19 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-19 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE INDIACATE ALL BRANCH | | | CIRCUIT #`S ON PLANS FOR ALL. | | | | | | 2)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | A/CCONDENSING UNITS. | | | | | | 3)NOTE: PLEASE NOTE THE REQ`MENT FOR | | | OUTLET SPACING FOR LOCAL CODES. 210-50 | | | | | | 4)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED.??? | | | PLEASE SUBMIT LOAD CALCS. | | | PLEASE SUBMIT PANEL SCHEDULE FOR PANEL | | | "KDP" NOT SHOWN?? PLEASE SUBMIT THE AIC | | | RATINGS FOR PANEL "KDP" AND SUBMIT | | | RATING FOR MAIN DISCONNECT. MAINS/PANELS | | | MUST BE RATED FOR THE AVAILABLE FAULT | | | CURRENT PER 110-9 | | | PLEASENOTE THAT ALL LOAD CALCULATIONS | | | ARE TO BE SHOWN. ALLCONTINUOUS LOADS | | | ARE TO BE FIGURED AND SHOWN AT 125% | | | (LIGHTING ) ETC. | | | | | | 5)NOTE: PLEASE SEE PLANS AND SEE THAT | | | YOU ARE SHOWING TWO DIFFERENT VOLTAGES | | | COMING FROM "KDP" ???? PLEASE SHOW HOW | | | THIS IS BEING DONE. TRANSFORMER??? | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-01 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) LETTER ATTACHED TO THE PLANS FROM | | | ARCHITECT JOSE M. ARENAL INDICATING THAT | | | THE WAIT STATION # 2 IS BEING REMOVED. | | | 2) FIRE ALARM DEVICES SHOWN ON PLANS | | | REQUIRE SEPARATE PLANS AND PERMIT. | | | 3) ADDITIONAL EMERGENCY LIGHTING | | | EQUIPMENT NEEDED IN SEATING AREA. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-18 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) SERVICE STATION NUMBER # 2 IS TO | | | BE RELOCATED AWAY FROM EXIT DOOR | | | LEADING TO STAIRS. NFPA 101, SECTION | | | 5-1.7.3 REQUIRES THAT MEANS OF EGRESS | | | SHALL BE FREE OF OBSTRUCTIONS WHICH | | | WOULD PREVENT ITS USE. | | | 2) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 3) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 4) SUBMIT COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON PLANS. A SEPARATE PLAN AND | | | PERMIT REQUIRED. | | | 5) PLEASE INDICATE WHERE EMERGENCY | | | LIGHTING FIXTURES ARE LOCATED IN | | | THE SEATING AREA. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-07-26 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) FIRE SPRINKLER DRAWING DOES NOT SEEM | | | TO INDICATE COMPLETE COVERAGE. ENTIRE | | | SPACE TO BE PROTECTED BY FIRE SPRINKLERS | | | INCLUDING COOLERS, FREEZERS, BATHROOMS, | | | ELECTRICAL, JANITOR CLOSETS. NO | | | HYDRAULIC CALCULATIONS PROVIDED. | | | 2) IDENTIFY MAIN EXIT CAPABLE OF | | | EXITING AT LEAST 50 PERCENT OF THE | | | OCCUPANT LOAD. | | | 3) ALL DOORS USED FOR EXITING TO BE | | | EQUIPPED WITH APPROVED PANIC HARDWARE. | | | FIRE DOORS USED FOR EXITING TO BE | | | EQUIPPED WITH APPROVED FIRE EXIT | | | HARDWARE. | | | 4) INTERIOR FINISH SHALL BE CLASS A OR | | | B IN EXITS. OTHER AREAS CLASS A,B, OR | | | C. | | | 5) PROVIDE COMPLETE SHOP DRAWINGS FOR | | | THE HOOD, DUCT AND EXTINGUISHING SYSTEM. | | | WET CHEMICAL FIRE EXTINGUISHING SYSTEMS | | | ARE ONLY SYSTEMS ALLOWED. | | | 6) DUCT SMOKE DETECTOR(S) REQUIRED IN | | | HVAC SYSTEMS OVER 2000 CFM. WHEN | | | ACTIVATED, HVAC SYSTEMS SHALL SHUT | | | DOWN. | | | 7) NATURAL GAS INSTALLATION TO COMPLY | | | WITH NFPA 54. | | | 8) PROVIDE DETAILS ON EXIT STAIR USED | | | FOR EXITING. | | | 9) IDENTIFY ANY WAITING AREAS PLANNED | | | FOR USE BY THE SPACE. | | | 10) PROVIDE FLAMESPREAD INFORMATION | | | ON FOAM RUBBER BOOTH MATERIALS. | | | 11) EXPLAIN SERVICE STATION TWO AND | | | HOW IT DOES NOT INTERFERE WITH | | | EXITING. | | | 12) WHERE IS THE FIRE ALARM EQUIPMENT | | | LOCATED. | | | 13) OCCUPANT LOAD TO BE DETERMINED | | | BY THIS OFFICE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-21 |
Time |
13:51 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-21 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISIONS ACCEPTED ADDRESSING ORIGINAL | | | REVIEW COMMENTS REVISIONS DATED 8/17/00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-18 |
Time |
12:26 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-18 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE DAMPER DETAIL AND LOCATION. | | | 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89. | | | 4.REQUIRE SUPPLY AIR DIFFUSER SCHEDULE. | | | 5.REQUIRE EXHAUST FANS DETAIL FOR BATH- | | | ROOMS. | | | 6.REQUIRE EER RATING FOR AHU PER FLORIDA | | | ENERGY EFFICIENCY CODE. | | | 7.PROVIDE INFORMATION ON THE AHU ON PLAN | | | 8.PROVIDE RETURN AIR SCHEDULE. | | | ***NOTES*** | | | SEPERATE PERMIT IS REQUIRED FOR HOOD, | | | WALK-IN COOLERS FIRE SUPPRESSION SYSTEM, | | | FUEL. | | | PROVIDE INFORMATION ON THE EXHAUST FANS | | | FOR HOODS. | | | PROVIDE OUTSIDE AIR AND EXHAUST CLEAR- | | | ANCES FOR HOODS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-01 |
Time |
16:24 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
2000-09-01 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | 1)CALCULATIONS FOR THE OCCUPANT LOAD | | | SHALL BE PREPARED,SIGNED,DATED AND | | | SEALED BY THE DESIGN PROFESSIONAL OF | | | RECORD AND SUBMITTED TO THIS DEPARTMENT | | | FOR REVIEW.COUNTYWIDE AMENDMENT TO SPC | | | SEC.104.2.3. | | | | | | 2)A SEPARATE GAS PERMIT AND REVISED | | | SIGNED AND SEALED DRAWINGS BY THE DESIGN | | | PROFESSIONAL SHALL BE SUBMITTED.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.104.2.3. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-08-26 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-26 |
Time |
06:03 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-26 |
Time |
06:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)THE SIZE OF THE SUPPLY LINES TO SOME | | | OF THE PIECES OF EQUIPMENT DOESN'T | | | COMPLY W/SGC TABLE 305.4(A).IF YOU ARE | | | USING A DIFFERENT SIZING TABLE SUBMIT | | | A COPY OF THE TABLE BEING USED.SEE THE | | | ATTACHED LIST FOR ANY ADDITIONAL REQS. | | | | | | 2)THE CALCULATIONS FOR THE OCCUPANT LOAD | | | HAS BEEN FAXED TO THIS OFFICE AND | | | APPROVED W/A PROVISO THAT 2 COPIES OF | | | THOSE CALCULATIONS SIGNED,DATED AND | | | SEALED BY THE DESIGN PROFESSIONAL SHALL | | | BE SUBMITTED TO THIS DEPARTMENT.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.104.2.1.,SPC | | | SEC.407.3.2. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-21 |
Time |
19:24 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-08-21 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)AN ADDITIONAL WATER CLOSET OR URINAL | | | IS REQD.IN THE MALE RESTROOM AND A WATER | | | CLOSET IS REQD.IN THE FEMALE RESTROOM | | | PER SPC TABLE 407 BASED ON THE OCCUPANT | | | LOAD OF 199 PERSONS. | | | | | | 2)CLARIFY THE REDUCTION OF THE GAS | | | SUPPLY LINES FROM 1"TO 3/4" FOR EACH | | | PIECE OF EQUIPMENT.THE PIPE SHALL REMAIN | | | FULL SIZE UP TO THE GAS VALVE.SGC 305.4 | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-19 |
Time |
15:02 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT P2.1 DISHWASHER #63, DISPOSAL | | | #68,RUN TO SANITARY SEWER, LOCAL | | | ORDINANCE REGIONAL SEWER TREATMENT PLANT | | | (2) SHT P0.1 ICE MACHINE #22, SEPERATE | | | DRAINS ON ICE BIN & CONDENSER UNIT. | | | BACKFLOW ORDINANCE #2853-95. | | | (3) SHT P1.1 GREASE WASTE ,COMMON SYSTEM | | | PROVIDED BY OWNER. | | | (4) SHTP5.1 GREASE WASTE ISOMETRIC, | | | ALL INDIRECT WASTE TO FLOOR SINKS. | | | SPC 94 SEC 807. | | | (5) SHT P6.1 GAS ISOMETRIC, ADD UNION | | | DOWN STREAM OF MANUAL SHUT OFF. | | | NFPA 54 SEC 5.5.4 | | | END OF COMMENTS |
|
|