Plan Review Details - Permit 00070571
Plan Review Stops For Permit 00070571
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-05 Cont ID  
Sent By drunnels Date 2000-09-05 Time 07:35 Rev Time 1.00
Received By drunnels Date 2000-09-05 Time 07:35 Sent To  
Notes
2001-01-08 00:00:00STOREFRONT UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By drunnels Date 2000-08-21 Time 12:29 Rev Time 1.00
Received By drunnels Date 2000-08-21 Time 12:28 Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS MUST BE SIGNED
 BY OWNER/AGENT
 2.SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION.
 3. PLANS MUST BE SEALED AND SIGNED BY
 ARCHITECT
  
  
 "PROVISO"
 STOREFRONT UNDER SEPERATE PERMIT
 SIGNS UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-20 Cont ID  
Sent By fknapp Date 2000-07-20 Time 15:03 Rev Time 4.00
Received By fknapp Date 2000-07-20 Time 15:03 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 ***************UNSAT********************
  
 1)PROVIDE COMPLETED FLORIDA ENERGY
 SHEETS WITH REQUIRED SEAL AND SIGNATURES
  
 2)FIRE SPRINKLER CONTRACTOR MUST SECURE
 PERMIT PRIOR TO ISSUANCE OF THE BUILDING
 PERMIT.
  
 3)PROVIDE CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR IMPACT
 RESISTANT WINDOWS AND DOORS.
  
 4)PROVIDE LIFE SAFETY PLAN THAT SHOWS
 CONTINUATION OF REAR EXIT FROM TENNANTS.
  
 5)KEY PLAN IS NOT CORRECT TO PLAN OF
 CITY PLACE.
  
 6)SHEET A.07 REFERENCES A-15 WHICH IS
 NOT SUPPLIED.
  
 7)SECOND SHEET A.01 REFERENCES DOORS AND
 TOILETS. IS THIS SHEET MISNUMBERED?
  
 8)ALL WOOD BUCKS, HEADERS, BLOCKING, ETC
 IN PARTITIONS, TO BE APPROVED FIRE
 RETARDANT TREATED LUMBER.
  
 9)PROVIDE FIRE RATING ON FOAM BOARD ON
 SHEET A-03 FOR ASSEMBLY OCCUPANCY.
  
 10)PROVIDE LETTER FROM SPECIAL INSPECTOR
 THAT WORK IS READY TO BEGIN.
  
 11)SEPARATE PERMIT IS REQUIRED FOR SIGNS
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8392
  
 FRANK KNAPP
 BUILDING PLAN REVIEW
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-28 Cont ID  
Sent By dpalmer Date 2000-08-28 Time 09:35 Rev Time 0.00
Received By dpalmer Date 2000-08-28 Time 09:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 21:17 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 21:17 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE FIRST SET OF NOTES.
 PLEASE "SHOW" LOAD CALCULATIONS. EG
 SQ. FT AND THE BREAKDOWN FOR LOADS AT
 125%. PLEASE SHOW BEFORE AND AFTER.
  
 2)NOTE: PLEASE MAKE MINOR CORRECTION FOR
 TOTAL KVA ON "K1"
  
 3)NOTE: PLEASE MAKE CORRECTION FOR PANEL
 REF. AS "H2A" SHOULD BE "H1A"
  
 4)NOTE: PLEASE SEE SHEET E 3.1 THERE IS
 A NOTE FOR TRANSFORMER TO SEE E-01??
 IS THIS THE NOTE/ DETAIL ON E5-1?
 PLEASE CALRIFY.
  
 5)NOTE: PLEASE SEE "K1" NOTE ADDED LOAD
 EXCEEDS LOAD SHOWN ON "K2" FOR TOTAL
 LOAD.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW,
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-19 Cont ID  
Sent By dpalmer Date 2000-07-19 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2000-07-19 Time 12:56 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE INDIACATE ALL BRANCH
 CIRCUIT #`S ON PLANS FOR ALL.
  
 2)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/CCONDENSING UNITS.
  
 3)NOTE: PLEASE NOTE THE REQ`MENT FOR
 OUTLET SPACING FOR LOCAL CODES. 210-50
  
 4)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED.???
 PLEASE SUBMIT LOAD CALCS.
 PLEASE SUBMIT PANEL SCHEDULE FOR PANEL
 "KDP" NOT SHOWN?? PLEASE SUBMIT THE AIC
 RATINGS FOR PANEL "KDP" AND SUBMIT
 RATING FOR MAIN DISCONNECT. MAINS/PANELS
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110-9
 PLEASENOTE THAT ALL LOAD CALCULATIONS
 ARE TO BE SHOWN. ALLCONTINUOUS LOADS
 ARE TO BE FIGURED AND SHOWN AT 125%
 (LIGHTING ) ETC.
  
 5)NOTE: PLEASE SEE PLANS AND SEE THAT
 YOU ARE SHOWING TWO DIFFERENT VOLTAGES
 COMING FROM "KDP" ???? PLEASE SHOW HOW
 THIS IS BEING DONE. TRANSFORMER???
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-09-01 Cont ID  
Sent By mcarsill Date 2000-09-01 Time 10:48 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) LETTER ATTACHED TO THE PLANS FROM
 ARCHITECT JOSE M. ARENAL INDICATING THAT
 THE WAIT STATION # 2 IS BEING REMOVED.
 2) FIRE ALARM DEVICES SHOWN ON PLANS
 REQUIRE SEPARATE PLANS AND PERMIT.
 3) ADDITIONAL EMERGENCY LIGHTING
 EQUIPMENT NEEDED IN SEATING AREA.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-18 Cont ID  
Sent By mcarsill Date 2000-08-18 Time 08:08 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) SERVICE STATION NUMBER # 2 IS TO
 BE RELOCATED AWAY FROM EXIT DOOR
 LEADING TO STAIRS. NFPA 101, SECTION
 5-1.7.3 REQUIRES THAT MEANS OF EGRESS
 SHALL BE FREE OF OBSTRUCTIONS WHICH
 WOULD PREVENT ITS USE.
 2) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 3) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 4) SUBMIT COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON PLANS. A SEPARATE PLAN AND
 PERMIT REQUIRED.
 5) PLEASE INDICATE WHERE EMERGENCY
 LIGHTING FIXTURES ARE LOCATED IN
 THE SEATING AREA.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By mcarsill Date 2000-07-26 Time 15:46 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) FIRE SPRINKLER DRAWING DOES NOT SEEM
 TO INDICATE COMPLETE COVERAGE. ENTIRE
 SPACE TO BE PROTECTED BY FIRE SPRINKLERS
 INCLUDING COOLERS, FREEZERS, BATHROOMS,
 ELECTRICAL, JANITOR CLOSETS. NO
 HYDRAULIC CALCULATIONS PROVIDED.
 2) IDENTIFY MAIN EXIT CAPABLE OF
 EXITING AT LEAST 50 PERCENT OF THE
 OCCUPANT LOAD.
 3) ALL DOORS USED FOR EXITING TO BE
 EQUIPPED WITH APPROVED PANIC HARDWARE.
 FIRE DOORS USED FOR EXITING TO BE
 EQUIPPED WITH APPROVED FIRE EXIT
 HARDWARE.
 4) INTERIOR FINISH SHALL BE CLASS A OR
 B IN EXITS. OTHER AREAS CLASS A,B, OR
 C.
 5) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE HOOD, DUCT AND EXTINGUISHING SYSTEM.
 WET CHEMICAL FIRE EXTINGUISHING SYSTEMS
 ARE ONLY SYSTEMS ALLOWED.
 6) DUCT SMOKE DETECTOR(S) REQUIRED IN
 HVAC SYSTEMS OVER 2000 CFM. WHEN
 ACTIVATED, HVAC SYSTEMS SHALL SHUT
 DOWN.
 7) NATURAL GAS INSTALLATION TO COMPLY
 WITH NFPA 54.
 8) PROVIDE DETAILS ON EXIT STAIR USED
 FOR EXITING.
 9) IDENTIFY ANY WAITING AREAS PLANNED
 FOR USE BY THE SPACE.
 10) PROVIDE FLAMESPREAD INFORMATION
 ON FOAM RUBBER BOOTH MATERIALS.
 11) EXPLAIN SERVICE STATION TWO AND
 HOW IT DOES NOT INTERFERE WITH
 EXITING.
 12) WHERE IS THE FIRE ALARM EQUIPMENT
 LOCATED.
 13) OCCUPANT LOAD TO BE DETERMINED
 BY THIS OFFICE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By ndenmark Date 2000-08-21 Time 13:51 Rev Time 0.33
Received By ndenmark Date 2000-08-21 Time 13:51 Sent To  
Notes
2001-01-08 00:00:00REVISIONS ACCEPTED ADDRESSING ORIGINAL
 REVIEW COMMENTS REVISIONS DATED 8/17/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-18 Cont ID  
Sent By cthirben Date 2000-07-18 Time 12:26 Rev Time 1.00
Received By cthirben Date 2000-07-18 Time 12:06 Sent To  
Notes
2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE DAMPER DETAIL AND LOCATION.
 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 3.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89.
 4.REQUIRE SUPPLY AIR DIFFUSER SCHEDULE.
 5.REQUIRE EXHAUST FANS DETAIL FOR BATH-
 ROOMS.
 6.REQUIRE EER RATING FOR AHU PER FLORIDA
 ENERGY EFFICIENCY CODE.
 7.PROVIDE INFORMATION ON THE AHU ON PLAN
 8.PROVIDE RETURN AIR SCHEDULE.
 ***NOTES***
 SEPERATE PERMIT IS REQUIRED FOR HOOD,
 WALK-IN COOLERS FIRE SUPPRESSION SYSTEM,
 FUEL.
 PROVIDE INFORMATION ON THE EXHAUST FANS
 FOR HOODS.
 PROVIDE OUTSIDE AIR AND EXHAUST CLEAR-
 ANCES FOR HOODS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-01 Cont ID  
Sent By tlarge Date 2000-09-01 Time 16:24 Rev Time 1.25
Received By tlarge Date 2000-09-01 Time 16:16 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 1)CALCULATIONS FOR THE OCCUPANT LOAD
 SHALL BE PREPARED,SIGNED,DATED AND
 SEALED BY THE DESIGN PROFESSIONAL OF
 RECORD AND SUBMITTED TO THIS DEPARTMENT
 FOR REVIEW.COUNTYWIDE AMENDMENT TO SPC
 SEC.104.2.3.
  
 2)A SEPARATE GAS PERMIT AND REVISED
 SIGNED AND SEALED DRAWINGS BY THE DESIGN
 PROFESSIONAL SHALL BE SUBMITTED.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-26 Cont ID  
Sent By tlarge Date 2000-08-26 Time 06:03 Rev Time 0.50
Received By tlarge Date 2000-08-26 Time 06:03 Sent To  
Notes
2001-01-08 00:00:001)THE SIZE OF THE SUPPLY LINES TO SOME
 OF THE PIECES OF EQUIPMENT DOESN'T
 COMPLY W/SGC TABLE 305.4(A).IF YOU ARE
 USING A DIFFERENT SIZING TABLE SUBMIT
 A COPY OF THE TABLE BEING USED.SEE THE
 ATTACHED LIST FOR ANY ADDITIONAL REQS.
  
 2)THE CALCULATIONS FOR THE OCCUPANT LOAD
 HAS BEEN FAXED TO THIS OFFICE AND
 APPROVED W/A PROVISO THAT 2 COPIES OF
 THOSE CALCULATIONS SIGNED,DATED AND
 SEALED BY THE DESIGN PROFESSIONAL SHALL
 BE SUBMITTED TO THIS DEPARTMENT.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.,SPC
 SEC.407.3.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By tlarge Date 2000-08-21 Time 19:24 Rev Time 1.00
Received By tlarge Date 2000-08-21 Time 18:41 Sent To  
Notes
2001-01-08 00:00:001)AN ADDITIONAL WATER CLOSET OR URINAL
 IS REQD.IN THE MALE RESTROOM AND A WATER
 CLOSET IS REQD.IN THE FEMALE RESTROOM
 PER SPC TABLE 407 BASED ON THE OCCUPANT
 LOAD OF 199 PERSONS.
  
 2)CLARIFY THE REDUCTION OF THE GAS
 SUPPLY LINES FROM 1"TO 3/4" FOR EACH
 PIECE OF EQUIPMENT.THE PIPE SHALL REMAIN
 FULL SIZE UP TO THE GAS VALVE.SGC 305.4
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-19 Cont ID  
Sent By pschmitz Date 2000-07-19 Time 15:02 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT P2.1 DISHWASHER #63, DISPOSAL
 #68,RUN TO SANITARY SEWER, LOCAL
 ORDINANCE REGIONAL SEWER TREATMENT PLANT
 (2) SHT P0.1 ICE MACHINE #22, SEPERATE
 DRAINS ON ICE BIN & CONDENSER UNIT.
 BACKFLOW ORDINANCE #2853-95.
 (3) SHT P1.1 GREASE WASTE ,COMMON SYSTEM
 PROVIDED BY OWNER.
 (4) SHTP5.1 GREASE WASTE ISOMETRIC,
 ALL INDIRECT WASTE TO FLOOR SINKS.
 SPC 94 SEC 807.
 (5) SHT P6.1 GAS ISOMETRIC, ADD UNION
 DOWN STREAM OF MANUAL SHUT OFF.
 NFPA 54 SEC 5.5.4
 END OF COMMENTS