Plan Review Details - Permit 00070557
Plan Review Stops For Permit 00070557
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-12 Cont ID  
Sent By drunnels Date 2000-09-12 Time 15:24 Rev Time 1.00
Received By drunnels Date 2000-09-12 Time 15:24 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
 STOREFRONT UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-05 Cont ID  
Sent By drunnels Date 2000-09-05 Time 11:52 Rev Time 1.00
Received By drunnels Date 2000-09-05 Time 11:52 Sent To  
Notes
2001-01-08 00:00:00REVIEW REVISION REC. 8/30/00
 1. PRODUCT APPROVAL: DOOR ON UNIT IS 3'
 AND NEW DOOR IS 6' WIDE. PROVIDE
 INFORMATION SHOWING CODE COMPLIANCE FOR
 REVISED WINDOW SYSTEM. MUST MEET METRO
 DADE COUNTY OR SBC, SSTD 12-97.
  
  
  
 NOTE ITEMS 1& WHERE REQUESTED ON
 PRIOR REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-18 Cont ID  
Sent By fknapp Date 2000-07-18 Time 14:44 Rev Time 2.00
Received By fknapp Date 2000-07-18 Time 14:38 Sent To  
Notes
2001-01-08 00:00:00 
 **************REVIEW NOTES**************
  
 SBC 104.2.2
  
 1)PROVIDE OWNER/AGENT SIGNATURE ON
 ENERGY CALCULATIONS.
  
 2)PROVIDE 2 COMPLETE COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR STORE
 FRONT AND DOOR TO BE USED.
  
 3)FIRE SPRINKLER CONTRACTOR MUST SECURE
 PERMIT PRIOR TO ISSUANCE OF THE BUILDING
 PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-01 Cont ID  
Sent By dpalmer Date 2000-09-01 Time 14:54 Rev Time 0.00
Received By dpalmer Date 2000-09-01 Time 14:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By dpalmer Date 2000-07-24 Time 05:51 Rev Time 0.00
Received By dpalmer Date 2000-07-24 Time 05:51 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW LOAD CALCULATION
 GIVING BREAKDOWN OF TRACK LIGHTING PER
 220-12
  
 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 FOR TRANSFORMER AND POINT OF ATTACHEMENT
  
 3)NOTE: PLEASE SHOW RECEPT IN BATH AS
 GFI.210-8
  
 4)NOTE: PLEASE SEE LOCAL CODE FOR OUTLET
 SPACING IN STOCK ROOM, AND TENANT SPACE.
 210-50. EVERY 20` OF WALL SPACE.
  
 5)NOTE: PLEASE SHOW THE REQ`D OUTLETS
 FOR SHOW WINDOWS 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-25 Cont ID  
Sent By mcarsill Date 2000-07-25 Time 13:57 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL BE CLASS A OR B.
 2) MOBILE DISPLAY CABINET CANNOT BLOCK
 EXIT ACCESS OR EXIT DOOR.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-09-12 Cont ID  
Sent By ndenmark Date 2000-09-12 Time 15:05 Rev Time 0.33
Received By ndenmark Date 2000-09-12 Time 15:00 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. DUCT SMOKE DETECTOR TO SENSE RETURN
 AIR CONDITION PRIOR TO ANY MIXING OF
 OUTSIDE AIR
 2. OUTSIDE AIR DUCT TO BE INCREASED TO
 7" FORM 6" AND VOLUME DAMPER TO BE 135
 NOT 80 PER D. ROMCKE ENG.
 3.NEW REVISION TO FOLLOW SHOWING THESE
 CHANGES ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-08-31 Cont ID  
Sent By ndenmark Date 2000-08-31 Time 14:22 Rev Time 1.00
Received By ndenmark Date 2000-08-31 Time 14:22 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 1. BATHROOM EXHAUST FAN TO BE INTERLOCK
 W/ AHU OR ON ALL THE TIME-NOT TIED TO
 LIGHT SWITCH
 2. OUTSIDE AIR CALCULATION DOES NOT MEET
 ASHRAE 62-89 SQ.FT. X .30
 3. DUCT SMOKE DETECTOR TO BE INSTALLED
 IN RETURN AIR PRIOR TO ANY MIXING OF
 OUTSIDE AIR PER 1997 SMC

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-15 Cont ID  
Sent By cthirben Date 2000-07-15 Time 07:46 Rev Time 1.00
Received By pschmitz Date 2000-07-15 Time 07:31 Sent To  
Notes
2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE FIRE DAMPER DETAIL SMC 610.6.
 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 3.PROVIDE ENERGY EFFICIENCY RATING OF
 AHU PER FLORIDA ENERGY EFFICIENCY CODE
 4.REQUIRE DUCT MATERIAL SCHEDULE.
 5.FLEX DUCT CONNECTION DETAIL REQUIRED.
 NOTE:
 FAN SHUT-DOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION BY BUILDING FIRE
 ALARM SYSTEM OR TIED TO HORN AND
 STROBE PER NFPA 90A 4.4.4.2 OR 4.4.4.3

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-20 Cont ID  
Sent By tlarge Date 2000-10-20 Time 16:47 Rev Time 0.33
Received By tlarge Date 2000-10-20 Time 16:47 Sent To  
Notes
2001-01-08 00:00:00DELETE D.F.-INSTALL BOTTLED WATER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-30 Cont ID  
Sent By tlarge Date 2000-08-30 Time 18:19 Rev Time 0.33
Received By tlarge Date 2000-08-30 Time 18:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-15 Cont ID  
Sent By pschmitz Date 2000-07-15 Time 09:50 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT A-2 REST RM TO COMPLY WITH SPC
 1994 SEC 407.2.2 READLY ACCESSIBLE,
 NOT THRU A STOCK RM.
 (2) SHT A-2 MIN. 1 DRINKING FOUNTAIN IS
 REQUIRED PER SPC TAB 407. D/F SHALL
 COMPLY WITH FACBC SEC4.1.3.(10) (A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
 (3) 2 SETS OF SIGNED AND SEALED
 DRAWINGS REQUIRED, FOR PLAN REVIEW.
 END OF COMMENTS