| Plan Review Stops For Permit 00070557 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-12 |
Time |
15:24 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-12 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO *************** | | | STOREFRONT UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-05 |
Time |
11:52 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-05 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVIEW REVISION REC. 8/30/00 | | | 1. PRODUCT APPROVAL: DOOR ON UNIT IS 3' | | | AND NEW DOOR IS 6' WIDE. PROVIDE | | | INFORMATION SHOWING CODE COMPLIANCE FOR | | | REVISED WINDOW SYSTEM. MUST MEET METRO | | | DADE COUNTY OR SBC, SSTD 12-97. | | | | | | | | | | | | NOTE ITEMS 1& WHERE REQUESTED ON | | | PRIOR REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-07-18 |
Time |
14:44 |
Rev Time |
2.00 |
| Received By |
fknapp |
Date |
2000-07-18 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | **************REVIEW NOTES************** | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE OWNER/AGENT SIGNATURE ON | | | ENERGY CALCULATIONS. | | | | | | 2)PROVIDE 2 COMPLETE COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS FOR STORE | | | FRONT AND DOOR TO BE USED. | | | | | | 3)FIRE SPRINKLER CONTRACTOR MUST SECURE | | | PERMIT PRIOR TO ISSUANCE OF THE BUILDING | | | PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-01 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-01 |
Time |
14:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-24 |
Time |
05:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-24 |
Time |
05:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW LOAD CALCULATION | | | GIVING BREAKDOWN OF TRACK LIGHTING PER | | | 220-12 | | | | | | 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | FOR TRANSFORMER AND POINT OF ATTACHEMENT | | | | | | 3)NOTE: PLEASE SHOW RECEPT IN BATH AS | | | GFI.210-8 | | | | | | 4)NOTE: PLEASE SEE LOCAL CODE FOR OUTLET | | | SPACING IN STOCK ROOM, AND TENANT SPACE. | | | 210-50. EVERY 20` OF WALL SPACE. | | | | | | 5)NOTE: PLEASE SHOW THE REQ`D OUTLETS | | | FOR SHOW WINDOWS 210-62 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-07-25 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH ON WALLS AND CEILINGS | | | SHALL BE CLASS A OR B. | | | 2) MOBILE DISPLAY CABINET CANNOT BLOCK | | | EXIT ACCESS OR EXIT DOOR. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-12 |
Time |
15:05 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-09-12 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. DUCT SMOKE DETECTOR TO SENSE RETURN | | | AIR CONDITION PRIOR TO ANY MIXING OF | | | OUTSIDE AIR | | | 2. OUTSIDE AIR DUCT TO BE INCREASED TO | | | 7" FORM 6" AND VOLUME DAMPER TO BE 135 | | | NOT 80 PER D. ROMCKE ENG. | | | 3.NEW REVISION TO FOLLOW SHOWING THESE | | | CHANGES ON PLAN |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-31 |
Time |
14:22 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-08-31 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | 1. BATHROOM EXHAUST FAN TO BE INTERLOCK | | | W/ AHU OR ON ALL THE TIME-NOT TIED TO | | | LIGHT SWITCH | | | 2. OUTSIDE AIR CALCULATION DOES NOT MEET | | | ASHRAE 62-89 SQ.FT. X .30 | | | 3. DUCT SMOKE DETECTOR TO BE INSTALLED | | | IN RETURN AIR PRIOR TO ANY MIXING OF | | | OUTSIDE AIR PER 1997 SMC |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-15 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-15 |
Time |
07:46 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2000-07-15 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE FIRE DAMPER DETAIL SMC 610.6. | | | 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 3.PROVIDE ENERGY EFFICIENCY RATING OF | | | AHU PER FLORIDA ENERGY EFFICIENCY CODE | | | 4.REQUIRE DUCT MATERIAL SCHEDULE. | | | 5.FLEX DUCT CONNECTION DETAIL REQUIRED. | | | NOTE: | | | FAN SHUT-DOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION BY BUILDING FIRE | | | ALARM SYSTEM OR TIED TO HORN AND | | | STROBE PER NFPA 90A 4.4.4.2 OR 4.4.4.3 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-10-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-20 |
Time |
16:47 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-10-20 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DELETE D.F.-INSTALL BOTTLED WATER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-30 |
Time |
18:19 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-08-30 |
Time |
18:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-15 |
Time |
09:50 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT A-2 REST RM TO COMPLY WITH SPC | | | 1994 SEC 407.2.2 READLY ACCESSIBLE, | | | NOT THRU A STOCK RM. | | | (2) SHT A-2 MIN. 1 DRINKING FOUNTAIN IS | | | REQUIRED PER SPC TAB 407. D/F SHALL | | | COMPLY WITH FACBC SEC4.1.3.(10) (A). | | | PROVISIONS SHALL BE MADE FOR PEOPLE WHO | | | HAVE TROUBLE BENDING OR STOOPING. | | | (3) 2 SETS OF SIGNED AND SEALED | | | DRAWINGS REQUIRED, FOR PLAN REVIEW. | | | END OF COMMENTS |
|
|