Plan Review Details - Permit 00070544
Plan Review Stops For Permit 00070544
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-26 Cont ID  
Sent By dpalmer Date 2000-07-26 Time 20:55 Rev Time 0.00
Received By dpalmer Date 2000-07-26 Time 20:54 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE:PLEASE NOTE THE REQ`D SMOKE
 DETECTOR PER NFPA-72 2-2.1.1.1 REQ`D
 DOWNSTAIRS
  
 2)NOTE: PLEASE REVISE PANEL SCHEDULE AND
 LIST THE REQ`D DEDICATED BATH(S) CIRCUIT
 PER 210-11-C-3/210-52D
  
 3)NOTE: PLEASE NOTE AND SHOW ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. PER 210-8-A-6
  
 4)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 MAIN/PANEL. ALL EQUIPMENT MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER
 110-9 OF THE NEC.
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMTION
 FOR REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE AREN
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2000-09-22 Cont ID  
Sent By jgomez Date 2000-09-22 Time 08:46 Rev Time 0.25
Received By jgomez Date 2000-09-22 Time 08:46 Sent To  
Notes
2001-01-08 00:00:00AS PER PHONE CONVERSATION WITH JIM LEWIS
 THE CONTRACTOR: MECHANICAL PERMIT TO
 BE APPLIED SEPARATELY BY MECHANICAL
 CONTRACTOR. NEED TO ANALIZE EXISTING
 CONDITIONS TO FIGURE OUT ACTUAL EQUIPM'T
 LOCATION AND DUCTWORK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By cthirben Date 2000-07-25 Time 08:20 Rev Time 0.00
Received By cthirben Date 2000-08-08 Time 10:57 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-24 Cont ID  
Sent By pschmitz Date 2000-07-24 Time 06:57 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: SHT.4 PES

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-09-21 Cont ID  
Sent By jgomez Date 2000-09-21 Time 14:58 Rev Time 1.50
Received By jgomez Date 2000-09-21 Time 12:18 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-NO A/C DRAWINGS AND SPECIFICATIONS.
 PROVIDE COMPLETE DRAWINGS AND SPECS
 AND APPLY FOR A SEPARATE MECHANICAL
 PERMIT.
 -PROVIDE ENERGY CALCULATIONS AND MANUAL
 "J" CALCULATIONS.
 2-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
 3-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR.
 4-SEE COMMENTS ON PLANS AND REVISE
 ORIGINALS AS REQUIRED.
 5-PROVIDE COMPLETE FRAMING DETAILS FOR
 NEW CANOPY AND NEW WINDOW AND DOOR
 OPENINGS. SEC 104.2.2 CITY AMENDMENTS.
  
  
  
  
  
 NOTE: IF YOU HAVE ANY QUESTIONS, PLEASE
 CALL JULIO GOMEZ AT 659-8096 EXT. 8232

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-09-08 Cont ID  
Sent By jgomez Date 2000-09-08 Time 17:03 Rev Time 1.50
Received By jgomez Date 2000-09-08 Time 17:02 Sent To  
Notes
2001-01-08 00:00:00SECOND CHECKLIST:
 1-TAKE DRAWINGS TO PALM BEACH COUNTY.
 THEY WILL VERIFY IF YOU NEED TO PAY
 IMPACT FEES OR NOT. THEY WILL STAMP
 THE DRAWINGS AND GIVE YOU A RECEIPT.
 2-WINDOWS AT SECOND FLOOR BEDROOMS DON'T
 COMPLY WITH THE MINIMUM EGRESS
 REQUIREMENTS ON SECTION 1005.4.4 OF
 SBC 1997.
 3-PROVIDE 2 COPIES OF PRODUCT APPROVALS.
 -CLEARLY SPECIFY/HIGHLIGHT IF USING
 WINDOWS WITH MISSILE IMPACT GLAZING OR
 NOT. PRODUCT APPROVAL HAS BOTH OPTIONS
 -PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR.
 NOTE:ENTRY DOOR SHOWS GLASS. HOW IS IT
 PROTECTED FROM MISSILE IMPACTS.
 4-SEE COMMENTS ON PLANS AND REVISE/
 UPDATE DRAWINGS AS REQUIRED. PROVIDE
 CLARIFICATIONS AS REQUESTED.
 5-PROVIDE LINTEL SCHEDULE AT ALL NEW
 OPENINGS. SEC 104.2.2 CITY AMENDMENTS.
 6-PROVIDE SAFETY GLASS AT MASTER BATHRM.
 SECTION 2405.2 SBC 1997.
 7-PROVIDE ENERGY CALCULATIONS AND MANUAL
 J CALCULATIONS.
 -PROVIDE A/C DRAWINGS.
  
  
  
  
  
 NOTE:
 -PLEASE RETURN REVIEWED SETS AFTER
 CORRECTIONS ARE DONE IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-08-07 Cont ID  
Sent By jgomez Date 2000-08-07 Time 16:50 Rev Time 2.00
Received By jgomez Date 2000-08-07 Time 16:50 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-TAKE DRAWINGS TO THE PALM BEACH COUNTY
 TO VERIFY IF YOU NEED TO PAY IMPACT
 FEES. THEY WILL STAMP DRAWINGS & GIVE
 YOU A RECEIPT.
 2-WILL NEED A NOTICE OF COMMENCEMT TO
 BE FILED AT THE COURTHOUSE.
 3-WINDOWS AT SECOND FLOOR BEDROOMS DON'T
 COMPLY WITH EGRESS REQUIREMENTS SECT'N
 1005.4.4 SBC 1997.
 4-SEE COMMENTS BY HISTORIC PRESERVATION
 DIVISION AND REVISE PLANS ACCORDINGLY.
 5-LEGIBLY PROVIDE THE NAME, ADDRESSAND
 LICENSE NUMBER OF ARCHITECT.
 -ARCHITECT TO DATE DRAWINGS AT TIME OF
 SEALING THEM.
 FLORIDA STATUTES CHAPTER 481.
 6-PROVIDE 2 COPIES OF PRODUCT APPROVALS.
 NOTE: SPECIFY IF USING MISSILE IMPACT
 GLAZING WINDOWS AND DOORS OR IF USING
 STORM SHUTTERS.
 7-SEE COMMENTS ON PLANS AND REVISE/
 UPDATE DRAWINGS AS REQUIRED.
 8-PROVIDE LINTEL SCHEDULE AT ALL NEW
 OPENINGS. SEC 104.2.2 CITY AMENDMENTS.
 9-PROVIDE SAFETY GLASS AT SECOND FLOOR
 BATHROOMS. SEC. 2405.2 SBC 1997.
 10-WHERE IS THE ATTIC ACCESS PANEL FOR
 SECOND FLOOR ROOF? SEC 2309.6 SBC 1997
 11-FILL IN THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM.ATTACHED
 12-PROVIDE THE DESIGN PRESSURES
 CALCULATED AT ALL EXTERIOR OPENINGS.
 SECTION 1606 SBC 1997.
 13-PROVIDE A/C DRAWINGS, ENERGY CALCS
 AND MANUAL J CALCULATIONS.
  
  
  
  
 NOTE:
  
 -PLEASE RETURN REVIEWED SET AFTER THE
 CORRECTIONS ARE DONE IN ORDER TO
 EXPEDITE THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-07-20 Cont ID  
Sent By gjoyce Date 2000-07-20 Time 10:02 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***