Plan Review Details - Permit 00070527
Plan Review Stops For Permit 00070527
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-18 Cont ID  
Sent By drunnels Date 2000-08-18 Time 14:09 Rev Time 1.00
Received By drunnels Date 2000-08-18 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-16 Cont ID  
Sent By drunnels Date 2000-08-16 Time 07:19 Rev Time 1.00
Received By drunnels Date 2000-08-16 Time 07:18 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION FROM FIRE CONTRACTOR. FIRE
 SPRINKLER PERMIT TO BE ISSUED PRIOR TO
 ISSURANCE OF BUILDING PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By drunnels Date 2000-08-04 Time 15:48 Rev Time 1.00
Received By drunnels Date 2000-08-04 Time 15:48 Sent To  
Notes
2001-01-08 00:00:001. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT WINDOW GLAZING AND DOORS FOR
 STOREFRONT/METRO DADE COUNTY OR SBCCI
 SSTD12-97. A-6 REF CWPB NOT PALM COUNTY
 2. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
 3. SUMIT FIRE SPRINKLER APPLICATION AND
 PLANS. FIRE SPRINKLER PERMIT TO BE
 ISSUED PROIR TO BUILDING PERMIT BEING
 ISSUED.
 4. ALL WOOD FRAMING AND BLOCKING TO BE
 FIRE RESISTANT TREATED TO COMPLY WITH
 1997 SBC CHAPTER 6&7.
 5. SUBMIT SQ. FT. OF HABITABLE SPACE
 TO ENSURE COMPLIANCE WITH 1997 SBC
 TABLE 407.
 6. CHANGE SWING OF DOOR TO COMPLY WITH
 1997 SBC CHAPTER 10 SCET.1O12.1.2. DOOR
 TO COMPLY WITH FLORIDA HANDICAP CODE.
 7. SHEET A-1 GENERAL NOTES CHANGE 1994
 SBC TO 1997 SBC.
 8. SIGNS TO BE UNTER SEPERATE PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 09:19 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 20:30 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 20:30 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE NOTE AS PER LOCAL CODE
 OUTLET SPACING TO MEET 210-50. EVERY 20`
 OF UNENCUMBERED WALL SPACE.
  
 2)NOTE: PLEASE CHECK 450-13-B FOR TRANS-
 -FORMER INSTALLATION.
  
 3)NOTE: PLEASE LIST BRKR SIZE FOR TRANS-
 -FORMER.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-18 Cont ID  
Sent By mcarsill Date 2000-08-18 Time 14:22 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-15 Cont ID  
Sent By mcarsill Date 2000-08-15 Time 12:49 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS.
 2) BATHROOM DOORS ARE NOT TO INTERFERE
 WITH REQUIRED 44" AISLE LEADING TO REAR
 EXIT.
 3) SUBMIT COMPLETE FIRE ALARM SYSTEM
 PLANS FOR FIRE ALARM EQUIPMENT SHOWN
 ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By mcarsill Date 2000-07-27 Time 15:01 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CLACULATIONS PROVIDED IN DRAWINGS.
 LEGEND ON PAGE E-2 DISPLAYS FIRE
 SPRINKLER HEADS BUT NONE COULD BE
 LOCATED.
 2) EXITING THROUGH STOCKROOM PERMITTED
 IF NOT MORE THAN 50 PERCENT OF EXIT
 ACCESS IS PROVIDED THROUGH STOCKROOM,
 A 44" AISLE IS REQUIRED, THE DOOR
 LEADING TO THE STOCKROOM CANNOT BE
 LOCKED, AND THE 44" AISLE BE MAINTAINED.
 3) DOOR LEADING INTO STOCKROOM NEEDS
 TO BE REVERSED. DOOR SHOULD SWING
 INTO STOCKROOM.
 4) INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL BE CLASS A OR B.
 5) NO INFORMATION PROVIDED ON
 FIRESTOPPING.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-16 Cont ID  
Sent By cthirben Date 2000-08-16 Time 07:42 Rev Time 0.00
Received By cthirben Date 2000-08-16 Time 07:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By cthirben Date 2000-07-24 Time 07:30 Rev Time 1.00
Received By cthirben Date 2000-07-24 Time 07:27 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMNC 501.2..
 2.REQUIRES DETAIL OF DAMPERS AT RATED
 WALLS AND LOCATION WHERE APPLICABLE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-15 Cont ID  
Sent By tlarge Date 2000-08-15 Time 07:56 Rev Time 0.30
Received By tlarge Date 2000-08-15 Time 07:56 Sent To  
Notes
2001-01-08 00:00:00BENCH IN H.C.FITTING ROOM SHALL BE
 LOCATED ALONG WALL W/LONGER DIMENSION.
 FACBC SEC.4.35.4.
  
 A/C CONDENSATE SHALL CONNECT TO COMMON
 SYSTEM.SMC 304.8.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By pschmitz Date 2000-07-27 Time 10:20 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW REF SPC 94
 (1A) SHT A-1 ACCESS TO H/C REST RM'S
 THRU A STORAGE ROOM, IS NOT ACCESSIBLE
 TO THE PUBLIC AS REQUIRED.
 COMPLY W/FACBC 4.1.3 (11)
 (B) 1 DRINKING FOUNTAIN REQ. TAB 407, TO
 COMPLY W/FACBC 4.1.3 (10), PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
 (C) A/C CONDENSATE DRAIN, CONNECT TO
 COMMON SYSTEM FURNISHED BY OWNER.
 NOT TO SANITARY SEWER.
 END OF COMMENTS