Plan Review Details - Permit 00070516
Plan Review Stops For Permit 00070516
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-21 Cont ID  
Sent By drunnels Date 2000-08-21 Time 11:22 Rev Time 1.00
Received By drunnels Date 2000-08-21 Time 11:22 Sent To  
Notes
2001-01-08 00:00:00"PROVISO"
 1. STORE FRONT UNDER SEPERATE PERMIT
 2. SIGNS UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-14 Cont ID  
Sent By bstaples Date 2000-08-14 Time 15:25 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS NOT SIGNED BY
 OWNER/AGENT. SEE PRIOR #1
 2. PRODUCT APPROVAL INFORMATION NOT
 SUBMITTED. SEE PRIOR #2
 3. FIRE SPRINKLER PLAN SUBMITTED,
 CONTRACTOR DID NOT SUBMIT APPLICATION.
 SEE PRIOR #3
  
 PROVISO ON ITEMM #4, SIGNS REQUIRE
 SEPERATE PERMITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By drunnels Date 2000-08-03 Time 09:54 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
 1. SUBMIT FLORIDA ENERGY CALCULATIONS
 SEALED AND SIGNED AS REQUIRED
 2. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT WINDOWS AND DOORS FOR
 STOREFRONT/ METRO DADE COUNTY OR SBCCI
 SSTD12-97
 3. SUBMIT FIRE SPRINKLER APPLICATION AND
 PLANS. FIRE SPRINKLER PERMIT MUST BE
 ISSUED PROIR TO ISSURANSE OF BUILDING
 PERMIT.
 4. SIGNS TO BE UNDER SEPRATE PERMIT
 5.1997 SBC CHAPTERS 6&7 ALL WOOR FRAMING
 TO BE FIRE RESISTANT TREATED
 (EXAMPLE SHEET A-3 SEC 2)
 6. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-12-11 Cont ID  
Sent By dpalmer Date 2000-12-11 Time 21:14 Rev Time 0.00
Received By dpalmer Date 2000-12-11 Time 21:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 19:14 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 19:14 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO ***************
  
 1)NOTE:PLEASE PROVIDE AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. MAINS/
 PANELS. MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT. 110-9
  
 2)NOTE: PLEASE CLARIFY TOTAL LOAD ON
 TRANSFORMER. ?
  
 3)NOTE: PLEASE SUBMIT LOAD CALCUALATIONS
 WITH ALL CONTINUOUS LOADS SHOWN AT 125%
 (LIGHTING ) ETC.
  
 4)NOTE: PLEASE SHOW WINDOW OUTLETS PER
 210-62 LOAD TO BE FIGURED PER 220-12A
  
 5)NOTE: PLEASE SHOW LOAD CALCS FOR TRACK
 LIGHTING PER 220-12B .
  
 6)NOTE: PLEASE CLARIFY CIRCUIT FOR SIGN.
 PER 220-3-B
  
  
 PLEAS SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-18 Cont ID  
Sent By mcarsill Date 2000-08-18 Time 13:20 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-15 Cont ID  
Sent By mcarsill Date 2000-08-15 Time 10:20 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS.
 2) PLEASE SUBMIT FIRE ALARM SYSTEM
 PLANS FOR FIRE ALARM EQUIPMENT SHOWN
 ON DRAWINGS. A SEPARATE PLAN AND PERMIT
 3) MIRROR SHOWN NEAR EXIT DOOR FROM
 SALES AREA NOT PERMITTED. SEE NFPA
 101, SECTION 5-5.2.2

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-02 Cont ID  
Sent By mcarsill Date 2000-08-02 Time 10:28 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH ON WALLS AND
 CEILINGS SHALL BE CLASS A OR B. CURTAINS
 SHOWN HANGING ARE WHAT FLAME SPREAD
 RATING.
 2) NO ILLUMINATED EXIT SIGN SHOWN AT
 DOOR LEADING INTO STOCKROOM FROM
 SALES AREA.
 3) HOW IS THE BASE BUILDING FIRE ALARM
 SYSTEM HEARD IN TENANT SPACE. NO FIRE
 ALARM EQUIPMENT SHOWN ON POWER PLAN.
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 5) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED IN
 DRAWINGS.
 6) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS ARE MET,
 NOT MORE THAN 50 PERCENT OF EXIT ACCESS
 IS PERMITTED THROUGH STOCKROOM, THE DOOR
 LEADING TO STOCKROOM CANNOT BE LOCKED,
 AISLE OF AT LEAST 44" WIDE REQUIRED IN
 STOCKROOM, THIS 44" AISLE TO BE
 MAINTAINED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-20 Cont ID  
Sent By ndenmark Date 2000-12-20 Time 08:33 Rev Time 0.25
Received By ndenmark Date 2000-12-20 Time 08:32 Sent To  
Notes
2001-01-08 00:00:00AS BUILTS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-15 Cont ID  
Sent By cthirben Date 2000-08-15 Time 08:44 Rev Time 1.00
Received By cthirben Date 2000-08-15 Time 08:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By cthirben Date 2000-07-24 Time 08:08 Rev Time 1.00
Received By cthirben Date 2000-07-24 Time 08:01 Sent To  
Notes
2001-01-08 00:00:00DENIED:
  
 PROVIDE AIR BALANCE PER 1997 SMC 501.2..
 PROVIDE DAMPER DETAIL AND LOCATION ON
 PLANS.
 REQUIRE DUCT MATERIAL SCHEDULE.
 GRILLE SCHEDULE TO BE PROVIDED.
 FLEX DUCT CONNECTION DETAIL REQUIRED.
 ENERGY EFFICIENCY RATING OF THE AHU IS
 REQUIRED PER FLORIDA ENERGY EFFICIENCY
 CODE.
 FAN SHUTDOWN IS REQUIRED PER NFPA 90A
 4.4.4.2 & 4.4.4.3...

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-15 Cont ID  
Sent By tlarge Date 2000-08-15 Time 06:22 Rev Time 0.50
Received By tlarge Date 2000-08-15 Time 06:22 Sent To  
Notes
2001-01-08 00:00:00PROVISO:THE DRESSING ROOM DOESN'T
 PROVIDE THE REQD.WHEELCHAIR TURNING
 SPACE PER FACBC SEC.4.2.3.(WHEELCHAIR
 CANNOT UTILIZE ENTIRE SPACE UNDER BENCH
 FOR TURN)THE ROOM DESIGN WILL HAVE TO BE
 REVISED.
  
 2)HANDICAP ACCESSIBLE TOILET ROOMS SHALL
 BE INDELIBLY POSTED FOR THE INTENDED
 USE,BE ON AN ACCESSIBLE ROUTE AND BE
 AVAILABLE TO PATRONS WITHOUT RESTRICTION
 DURING NORMAL OPERATING HOURS.FACBC
 SECS.4.1,4.2,4.3,SPC SEC.407.2.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By pschmitz Date 2000-07-27 Time 06:16 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW REF SPC 94
 (1A)SHT A-1 ACCESS TO H/C REST RM THRU A
 STORAGE ROOM, IS NOT ACCESSIBLE TO THE
 PUBLIC AS REQUIRED,
 COMPLY W/ FACBC 4.1.3 (11).
 (B)DRESSING ROOM TO COMPLY W/FACBC4.35.4
 24"X 48"X 17" BENCH FIXED TO THE WALL.
 (C)SALES & SERVICE COMPLY W/ FACBC
 7.2(1)(I)36"X36" COUNTER AFF.
 (D) I-DRINKING FOUNTAIN REQ. TAB 407, TO
 COMPLY W/FACBC 4.1.3 (10),PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING & STOOPING.
 (2) SHT PL-1 FLOOR DRAINS IN PUBLIC
 REST RM'S, 3" MIN. TRAP, W/ TRAP PRIMRER
 SEC 409.4.1.1
 END OF COMMENTS