| Plan Review Stops For Permit 00070516 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-21 |
Time |
11:22 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-21 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | "PROVISO" | | | 1. STORE FRONT UNDER SEPERATE PERMIT | | | 2. SIGNS UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-08-14 |
Time |
15:25 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. FLORIDA ENERGY SHEETS NOT SIGNED BY | | | OWNER/AGENT. SEE PRIOR #1 | | | 2. PRODUCT APPROVAL INFORMATION NOT | | | SUBMITTED. SEE PRIOR #2 | | | 3. FIRE SPRINKLER PLAN SUBMITTED, | | | CONTRACTOR DID NOT SUBMIT APPLICATION. | | | SEE PRIOR #3 | | | | | | PROVISO ON ITEMM #4, SIGNS REQUIRE | | | SEPERATE PERMITS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-03 |
Time |
09:54 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | | | | 1. SUBMIT FLORIDA ENERGY CALCULATIONS | | | SEALED AND SIGNED AS REQUIRED | | | 2. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT WINDOWS AND DOORS FOR | | | STOREFRONT/ METRO DADE COUNTY OR SBCCI | | | SSTD12-97 | | | 3. SUBMIT FIRE SPRINKLER APPLICATION AND | | | PLANS. FIRE SPRINKLER PERMIT MUST BE | | | ISSUED PROIR TO ISSURANSE OF BUILDING | | | PERMIT. | | | 4. SIGNS TO BE UNDER SEPRATE PERMIT | | | 5.1997 SBC CHAPTERS 6&7 ALL WOOR FRAMING | | | TO BE FIRE RESISTANT TREATED | | | (EXAMPLE SHEET A-3 SEC 2) | | | 6. SUBMIT LETTER FROM SPECIAL INSPECTOR | | | RELEASING SPACE |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-11 |
Time |
21:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-11 |
Time |
21:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-15 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-15 |
Time |
12:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-31 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-31 |
Time |
19:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO *************** | | | | | | 1)NOTE:PLEASE PROVIDE AIC RATINGS FOR | | | ALL EQUIPMENT BEING INSTALLED. MAINS/ | | | PANELS. MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT. 110-9 | | | | | | 2)NOTE: PLEASE CLARIFY TOTAL LOAD ON | | | TRANSFORMER. ? | | | | | | 3)NOTE: PLEASE SUBMIT LOAD CALCUALATIONS | | | WITH ALL CONTINUOUS LOADS SHOWN AT 125% | | | (LIGHTING ) ETC. | | | | | | 4)NOTE: PLEASE SHOW WINDOW OUTLETS PER | | | 210-62 LOAD TO BE FIGURED PER 220-12A | | | | | | 5)NOTE: PLEASE SHOW LOAD CALCS FOR TRACK | | | LIGHTING PER 220-12B . | | | | | | 6)NOTE: PLEASE CLARIFY CIRCUIT FOR SIGN. | | | PER 220-3-B | | | | | | | | | PLEAS SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | CITY OF WEST PALM BEACH | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-08-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-18 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-15 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. | | | 2) PLEASE SUBMIT FIRE ALARM SYSTEM | | | PLANS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON DRAWINGS. A SEPARATE PLAN AND PERMIT | | | 3) MIRROR SHOWN NEAR EXIT DOOR FROM | | | SALES AREA NOT PERMITTED. SEE NFPA | | | 101, SECTION 5-5.2.2 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-02 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH ON WALLS AND | | | CEILINGS SHALL BE CLASS A OR B. CURTAINS | | | SHOWN HANGING ARE WHAT FLAME SPREAD | | | RATING. | | | 2) NO ILLUMINATED EXIT SIGN SHOWN AT | | | DOOR LEADING INTO STOCKROOM FROM | | | SALES AREA. | | | 3) HOW IS THE BASE BUILDING FIRE ALARM | | | SYSTEM HEARD IN TENANT SPACE. NO FIRE | | | ALARM EQUIPMENT SHOWN ON POWER PLAN. | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 5) NO FIRE SPRINKLER DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED IN | | | DRAWINGS. | | | 6) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS ARE MET, | | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | | IS PERMITTED THROUGH STOCKROOM, THE DOOR | | | LEADING TO STOCKROOM CANNOT BE LOCKED, | | | AISLE OF AT LEAST 44" WIDE REQUIRED IN | | | STOCKROOM, THIS 44" AISLE TO BE | | | MAINTAINED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-20 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-20 |
Time |
08:33 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-12-20 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | AS BUILTS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-15 |
Time |
08:44 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-15 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-24 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-24 |
Time |
08:08 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-24 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | | | | PROVIDE AIR BALANCE PER 1997 SMC 501.2.. | | | PROVIDE DAMPER DETAIL AND LOCATION ON | | | PLANS. | | | REQUIRE DUCT MATERIAL SCHEDULE. | | | GRILLE SCHEDULE TO BE PROVIDED. | | | FLEX DUCT CONNECTION DETAIL REQUIRED. | | | ENERGY EFFICIENCY RATING OF THE AHU IS | | | REQUIRED PER FLORIDA ENERGY EFFICIENCY | | | CODE. | | | FAN SHUTDOWN IS REQUIRED PER NFPA 90A | | | 4.4.4.2 & 4.4.4.3... |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-15 |
Time |
06:22 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-15 |
Time |
06:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO:THE DRESSING ROOM DOESN'T | | | PROVIDE THE REQD.WHEELCHAIR TURNING | | | SPACE PER FACBC SEC.4.2.3.(WHEELCHAIR | | | CANNOT UTILIZE ENTIRE SPACE UNDER BENCH | | | FOR TURN)THE ROOM DESIGN WILL HAVE TO BE | | | REVISED. | | | | | | 2)HANDICAP ACCESSIBLE TOILET ROOMS SHALL | | | BE INDELIBLY POSTED FOR THE INTENDED | | | USE,BE ON AN ACCESSIBLE ROUTE AND BE | | | AVAILABLE TO PATRONS WITHOUT RESTRICTION | | | DURING NORMAL OPERATING HOURS.FACBC | | | SECS.4.1,4.2,4.3,SPC SEC.407.2.2. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-27 |
Time |
06:16 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW REF SPC 94 | | | (1A)SHT A-1 ACCESS TO H/C REST RM THRU A | | | STORAGE ROOM, IS NOT ACCESSIBLE TO THE | | | PUBLIC AS REQUIRED, | | | COMPLY W/ FACBC 4.1.3 (11). | | | (B)DRESSING ROOM TO COMPLY W/FACBC4.35.4 | | | 24"X 48"X 17" BENCH FIXED TO THE WALL. | | | (C)SALES & SERVICE COMPLY W/ FACBC | | | 7.2(1)(I)36"X36" COUNTER AFF. | | | (D) I-DRINKING FOUNTAIN REQ. TAB 407, TO | | | COMPLY W/FACBC 4.1.3 (10),PROVISIONS | | | SHALL BE MADE FOR PEOPLE WHO HAVE | | | TROUBLE BENDING & STOOPING. | | | (2) SHT PL-1 FLOOR DRAINS IN PUBLIC | | | REST RM'S, 3" MIN. TRAP, W/ TRAP PRIMRER | | | SEC 409.4.1.1 | | | END OF COMMENTS |
|
|