Plan Review Details - Permit 00070488
Plan Review Stops For Permit 00070488
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-11 Cont ID  
Sent By drunnels Date 2000-09-11 Time 16:34 Rev Time 1.00
Received By drunnels Date 2000-09-11 Time 16:33 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO *****************
  
 STOREFRONT TO BE ISSUED UNDER SEPERATE
 PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-30 Cont ID  
Sent By drunnels Date 2000-08-30 Time 14:55 Rev Time 1.00
Received By drunnels Date 2000-08-30 Time 14:55 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
 STOREFRONT TO BE ISSUED UNDER SEPERATE
 PERMIT
 1.SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By drunnels Date 2000-08-04 Time 14:06 Rev Time 1.00
Received By drunnels Date 2000-08-04 Time 14:05 Sent To  
Notes
2001-01-08 00:00:00 
 1. SUBMIT FLORIDA ENERGY CALICATION
 SHEET SEALED AND SIGNED BY ARCH.AND
 OWNER/AGENT
 2. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR WINDOWS AND DOORS
 FOR STOREFRONT/ METRO DADE COUNTY OR
 SBCCI SSTD12-97
 3. SUBMIT FIRE SPRINKLER APPLICATION/
 FIRE SPRINKLER PERMIT TO BE ISSUED PRIOR
 TO BUILDING PERMIT BEING ISSUED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-24 Cont ID  
Sent By dpalmer Date 2000-07-24 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2000-07-24 Time 16:38 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO **************
  
 NOTE: PLEASE SUBMIT LOAD CALCULAITON TO
 CORRELATE OR CLARIFY LOADS SHOWN. PLEASE
 SHOW WHAT THE LOADS ARE THAT YOU ARE
 ADDING 20% FOR? IS THIS FOR THE 25%
 OF CONTINUOUS LOADS? ARE YOU JUST ADDING
 20% FOR THE ENTIRE PANEL.?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-09-12 Cont ID  
Sent By mcarsill Date 2000-09-12 Time 09:24 Rev Time 0.00
Received By mcarsill Date 2000-09-12 Time 09:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-29 Cont ID  
Sent By mcarsill Date 2000-08-29 Time 08:02 Rev Time 0.00
Received By drunnels Date 2000-08-29 Time 08:02 Sent To  
Notes
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 IN BUILDING DEPARTMENT DATA. SHOULD
 READ 1985 LIFE SAFETY CODE: NFPA 101
 2) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS. NO PERMIT ON FILE FOR
 FIRE SPRINKLER WORK.
 3) PROVIDE FIRE ALARM SYSTEM PLANS FOR
 FIRE ALARM DEVICES SHOWN ON PLANS. A
 SEPARATE PERMIT IS REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By mcarsill Date 2000-08-08 Time 11:08 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) FIRE SPRINKLER SECTION OF PLANS ARE
 NOT ACCEPTABLE. ACCORDING TO THE WATER
 SUPPLY GRAPH, ONLY 1.43 LBS IS AVAILABLE
 BETWEEN SUPPLY AND PRESSURE REQUIRED.
 WHERE DID THE SUPPLY DATA COME FROM.
 2) NO FIRE DAMPERS SHOWN ON PLANS.
 3) EXITING THROUGH STOCKROOM PERMITTED
 ONLY IF THE FOLLOWING CONDITIONS EXIST,
 DOOR LEADING TO STOCKROOM CANNOT BE
 LOCKED, AISLE THROUGH STOCKROOM TO
 BE AT LEAST 44" WIDE, THIS 44" AISLE
 TO BE MAINTAINED, AND EXIT CANNOT
 PROVIDE NO MORE THAN 50 PERCENT OF
 EXIT ACCESS.
 4) PROVIDE PLANS AND PERMIT FOR FIRE
 ALARM EQUIPMENT SHOWN IN SPACE. CUT
 SHEETS NEEDED ON ALL DEVICES.
 5) WHERE IS THE EMERGENCY LIGHTING IN
 THE SALES AREA.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-09-11 Cont ID  
Sent By ndenmark Date 2000-09-11 Time 16:11 Rev Time 0.25
Received By ndenmark Date 2000-09-11 Time 16:11 Sent To  
Notes
2001-01-08 00:00:00PRIOR COMMENTS ADDRESSED BY REVISION
 DATED 9/1/00

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-08-24 Cont ID  
Sent By ndenmark Date 2000-08-24 Time 14:44 Rev Time 0.50
Received By drunnels Date 2000-08-24 Time 14:44 Sent To  
Notes
2001-01-08 00:00:00******************DENIED****************
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3. FLOOR PLAN ON A1 DOES NOT MATCH M1
 DRAWING RE: RATED WALL @ R/A F/D.
 FIRE DAMPER TO BE INSTALLED PER SPECS
 NOT ANGLED IN DUCT AS SHOWN ON M1 FOR
 PROTECTION OF OPENING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-21 Cont ID  
Sent By cthirben Date 2000-07-21 Time 11:00 Rev Time 1.00
Received By cthirben Date 2000-07-21 Time 10:44 Sent To  
Notes
2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 2.REQUIRE EXHAUST FANS DETAILS ON PLANS
 3.ENERGY EFFICIENCY RATING OF AHU IS
 REQUIRED PER FLORIDA ENERGY EFFICIENCY
 CODE.
 4.ENERGY CALCULATIONS NEEDS TO BE SIGNED
 AND SEALED.
 5.INDICATE FIRE/SMOKE DAMPERS WHERE
 APPLICABLE.
 6.SHOW SMOKE DETECTOR ON PLANS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-11 Cont ID  
Sent By tlarge Date 2000-09-11 Time 10:58 Rev Time 0.33
Received By tlarge Date 2000-09-11 Time 10:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-09-08 Cont ID  
Sent By tlarge Date 2000-09-08 Time 18:30 Rev Time 0.50
Received By tlarge Date 2000-09-08 Time 18:22 Sent To  
Notes
2001-01-08 00:00:001)COMPLY W/ALL PREVIOUS COMMENTS.IT
 APPEARS NOTHING HAS BEEN ADDRESSED.
  
 2)SHT.A1.1-TOE CLEARANCE AT H.C.LAV.
 SHALL BE 6" MAX.,NOT 12".FACBC FIG.31.
  
 3)THERE SHALL BE A CLEAR FLOOR SPACE OF
 30"WIDE BY 48"DEEP FOR THE DRINKING
 FOUNTAIN.THE COLUMN SHALL NOT INFRINGE
 UPON THIS CLEAR FLOOR SPACE.FACBC FIG.27
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-25 Cont ID  
Sent By tlarge Date 2000-08-25 Time 16:17 Rev Time 1.00
Received By tlarge Date 2000-08-25 Time 15:01 Sent To  
Notes
2001-01-08 00:00:001)GREASE INTERCEPTOR NOT PERMITTED IN
 FOOD PREP AREA.INTERCEPTOR MAY NOT BE
 REQD.CONTACT ROD COMPO W/CITY OF WPB
 WASTEWATER TREATMENT FACILITY AT (561)-
 835-7423 FOR WAIVER.SUBMIT COPY OF FORM.
  
 2)WATER CLOSETS AND LAVATORIES ARE NOT
 PROPERLY VENTED.COMPLY W/FACBC 901.2.
  
 3)FLOOR CLEANOUT SHALL BE ACCESSIBLE..
 710.2.3,710.3.
  
 4)3-COMP.SINK DRAIN SHALL BE MIN.2 PER
 TABLE 713.1.
  
 5)A SHUT-OFF VALVE IS REQD.ON THE WATER
 SUPPLY BRANCH PER SPC SEC.610.4.2.
  
 6)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 7)OVER 2 FIXTURES ARE SUPLLIED BY 1/2"
 COLD WATER.COMPLY W/COUNTYWIDE AMEND-
 MENTS TO SPC SEC.911.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By tlarge Date 2000-08-03 Time 19:10 Rev Time 1.00
Received By drunnels Date 2000-08-03 Time 18:42 Sent To  
Notes
2001-01-08 00:00:001)TITLE SHEET-INCLUDE SPC 1994 EDITION.
  
 2)DRINKING FOUNTAIN SHALL BE ACCESSIBLE
 TO PATRONS WITHOUT RESTRICTION AND
 COMPLY W/FACBC SEC.4.1.3.(10)(A),4.15.
 SPC 407.2.2.
  
 3)TOILET ROOM SHALL BE LOCATED ON AN
 ACCESSIBLE ROUTE AND ACCESSIBLE ROUTE
 SHALL BE CLEARLY DEFINED ON THE PLANS.
 FACBC 4.1.3(11),4.2.1,4.3.1,4.3.2,(3),
 4.3.3.
  
 4)TOILET ROOM SHALL BE AVAILABLE TO
 PATRONS WITHOUT RESTRICTION DURING
 NORMAL OPERATING HOURS PER SPC SEC.
 407.2.2.
  
 5)PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS AND PROFESSIONAL REGULATION FOR
 REVIEW AND APPROVAL.COUNTYWIDE AMENDMENT
 TO SPC SEC.101.4.7.CALL 954-958-5520.
  
 6)SUBMIT SIGNED,SEALED AND DATED WATER
 AND SANITARY ISOMETRICS FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
 104.2.3..
  
 7)DISCHARGE OF FIXTURES OTHER THAN THE
 TOILET ROOM SHALL BETO A GREASE
 INTERCEPTOR PER SPC 1004.4.
  
 IF YOU HAVE ANY QUESTIONS CALL
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.