| Plan Review Stops For Permit 00070488 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-11 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-11 |
Time |
16:34 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-11 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO ***************** | | | | | | STOREFRONT TO BE ISSUED UNDER SEPERATE | | | PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-30 |
Time |
14:55 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-30 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | STOREFRONT TO BE ISSUED UNDER SEPERATE | | | PERMIT | | | 1.SUBMIT FIRE SPRINKLER PLANS AND | | | PERMIT APPLICATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-04 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-04 |
Time |
14:06 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-04 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | 1. SUBMIT FLORIDA ENERGY CALICATION | | | SHEET SEALED AND SIGNED BY ARCH.AND | | | OWNER/AGENT | | | 2. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT GLAZING FOR WINDOWS AND DOORS | | | FOR STOREFRONT/ METRO DADE COUNTY OR | | | SBCCI SSTD12-97 | | | 3. SUBMIT FIRE SPRINKLER APPLICATION/ | | | FIRE SPRINKLER PERMIT TO BE ISSUED PRIOR | | | TO BUILDING PERMIT BEING ISSUED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-07-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-24 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-24 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** PROVISO ************** | | | | | | NOTE: PLEASE SUBMIT LOAD CALCULAITON TO | | | CORRELATE OR CLARIFY LOADS SHOWN. PLEASE | | | SHOW WHAT THE LOADS ARE THAT YOU ARE | | | ADDING 20% FOR? IS THIS FOR THE 25% | | | OF CONTINUOUS LOADS? ARE YOU JUST ADDING | | | 20% FOR THE ENTIRE PANEL.? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-12 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-12 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-29 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
2000-08-29 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | | IN BUILDING DEPARTMENT DATA. SHOULD | | | READ 1985 LIFE SAFETY CODE: NFPA 101 | | | 2) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. NO PERMIT ON FILE FOR | | | FIRE SPRINKLER WORK. | | | 3) PROVIDE FIRE ALARM SYSTEM PLANS FOR | | | FIRE ALARM DEVICES SHOWN ON PLANS. A | | | SEPARATE PERMIT IS REQUIRED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-08 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) FIRE SPRINKLER SECTION OF PLANS ARE | | | NOT ACCEPTABLE. ACCORDING TO THE WATER | | | SUPPLY GRAPH, ONLY 1.43 LBS IS AVAILABLE | | | BETWEEN SUPPLY AND PRESSURE REQUIRED. | | | WHERE DID THE SUPPLY DATA COME FROM. | | | 2) NO FIRE DAMPERS SHOWN ON PLANS. | | | 3) EXITING THROUGH STOCKROOM PERMITTED | | | ONLY IF THE FOLLOWING CONDITIONS EXIST, | | | DOOR LEADING TO STOCKROOM CANNOT BE | | | LOCKED, AISLE THROUGH STOCKROOM TO | | | BE AT LEAST 44" WIDE, THIS 44" AISLE | | | TO BE MAINTAINED, AND EXIT CANNOT | | | PROVIDE NO MORE THAN 50 PERCENT OF | | | EXIT ACCESS. | | | 4) PROVIDE PLANS AND PERMIT FOR FIRE | | | ALARM EQUIPMENT SHOWN IN SPACE. CUT | | | SHEETS NEEDED ON ALL DEVICES. | | | 5) WHERE IS THE EMERGENCY LIGHTING IN | | | THE SALES AREA. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-11 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-11 |
Time |
16:11 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-09-11 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PRIOR COMMENTS ADDRESSED BY REVISION | | | DATED 9/1/00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-24 |
Time |
14:44 |
Rev Time |
0.50 |
| Received By |
drunnels |
Date |
2000-08-24 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************DENIED**************** | | | | | | 1. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3. FLOOR PLAN ON A1 DOES NOT MATCH M1 | | | DRAWING RE: RATED WALL @ R/A F/D. | | | FIRE DAMPER TO BE INSTALLED PER SPECS | | | NOT ANGLED IN DUCT AS SHOWN ON M1 FOR | | | PROTECTION OF OPENING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-21 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-21 |
Time |
11:00 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-21 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 2.REQUIRE EXHAUST FANS DETAILS ON PLANS | | | 3.ENERGY EFFICIENCY RATING OF AHU IS | | | REQUIRED PER FLORIDA ENERGY EFFICIENCY | | | CODE. | | | 4.ENERGY CALCULATIONS NEEDS TO BE SIGNED | | | AND SEALED. | | | 5.INDICATE FIRE/SMOKE DAMPERS WHERE | | | APPLICABLE. | | | 6.SHOW SMOKE DETECTOR ON PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-09-11 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-11 |
Time |
10:58 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-09-11 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-09-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-08 |
Time |
18:30 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-09-08 |
Time |
18:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)COMPLY W/ALL PREVIOUS COMMENTS.IT | | | APPEARS NOTHING HAS BEEN ADDRESSED. | | | | | | 2)SHT.A1.1-TOE CLEARANCE AT H.C.LAV. | | | SHALL BE 6" MAX.,NOT 12".FACBC FIG.31. | | | | | | 3)THERE SHALL BE A CLEAR FLOOR SPACE OF | | | 30"WIDE BY 48"DEEP FOR THE DRINKING | | | FOUNTAIN.THE COLUMN SHALL NOT INFRINGE | | | UPON THIS CLEAR FLOOR SPACE.FACBC FIG.27 | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-25 |
Time |
16:17 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-08-25 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)GREASE INTERCEPTOR NOT PERMITTED IN | | | FOOD PREP AREA.INTERCEPTOR MAY NOT BE | | | REQD.CONTACT ROD COMPO W/CITY OF WPB | | | WASTEWATER TREATMENT FACILITY AT (561)- | | | 835-7423 FOR WAIVER.SUBMIT COPY OF FORM. | | | | | | 2)WATER CLOSETS AND LAVATORIES ARE NOT | | | PROPERLY VENTED.COMPLY W/FACBC 901.2. | | | | | | 3)FLOOR CLEANOUT SHALL BE ACCESSIBLE.. | | | 710.2.3,710.3. | | | | | | 4)3-COMP.SINK DRAIN SHALL BE MIN.2 PER | | | TABLE 713.1. | | | | | | 5)A SHUT-OFF VALVE IS REQD.ON THE WATER | | | SUPPLY BRANCH PER SPC SEC.610.4.2. | | | | | | 6)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | 7)OVER 2 FIXTURES ARE SUPLLIED BY 1/2" | | | COLD WATER.COMPLY W/COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.911. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-03 |
Time |
19:10 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-03 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)TITLE SHEET-INCLUDE SPC 1994 EDITION. | | | | | | 2)DRINKING FOUNTAIN SHALL BE ACCESSIBLE | | | TO PATRONS WITHOUT RESTRICTION AND | | | COMPLY W/FACBC SEC.4.1.3.(10)(A),4.15. | | | SPC 407.2.2. | | | | | | 3)TOILET ROOM SHALL BE LOCATED ON AN | | | ACCESSIBLE ROUTE AND ACCESSIBLE ROUTE | | | SHALL BE CLEARLY DEFINED ON THE PLANS. | | | FACBC 4.1.3(11),4.2.1,4.3.1,4.3.2,(3), | | | 4.3.3. | | | | | | 4)TOILET ROOM SHALL BE AVAILABLE TO | | | PATRONS WITHOUT RESTRICTION DURING | | | NORMAL OPERATING HOURS PER SPC SEC. | | | 407.2.2. | | | | | | 5)PLANS SHALL BE ROUTED TO DEPT.OF | | | BUSINESS AND PROFESSIONAL REGULATION FOR | | | REVIEW AND APPROVAL.COUNTYWIDE AMENDMENT | | | TO SPC SEC.101.4.7.CALL 954-958-5520. | | | | | | 6)SUBMIT SIGNED,SEALED AND DATED WATER | | | AND SANITARY ISOMETRICS FOR REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | 104.2.3.. | | | | | | 7)DISCHARGE OF FIXTURES OTHER THAN THE | | | TOILET ROOM SHALL BETO A GREASE | | | INTERCEPTOR PER SPC 1004.4. | | | | | | IF YOU HAVE ANY QUESTIONS CALL | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|