| Plan Review Stops For Permit 00070484 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2000-10-02 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-10-02 |
Time |
11:41 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-10-02 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHOP DRAWINGS | | | ALL SHEETS MUST HAVE RAISED SEAL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-05 |
Time |
08:39 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-05 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************NOTE************** | | | STOREFRONT UNDER SEPERATE PERMIT | | | SIGNS UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-29 |
Time |
13:30 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-29 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PREVIOUS ITEMS #1,3& 5 NOT CORRECTED | | | ****************PROVISO************ | | | EXTERIOR SINGS TO BE UNDER SEPERATE | | | PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-07-31 |
Time |
08:23 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | | | | 1. FLORIDA ENERGY EFFICIENCY SHEETS MUST | | | BE SIGNED BY THE OWNER/OWNER AGENT | | | 2. PROVIDE LETTER FROM SPECIAL INSPECTOR | | | 3. FIRE SPRINKLER PERMIT MUST BE ISSURED | | | PRIOR TO ISSURANCE OF BUILDING PERMIT | | | 4. EXTERIOR SIGNS TO BE UNDER SEPERATE | | | PERMIT. | | | 5. POVIDE PRODUCT APPROVAL SHEETS METRO | | | COUNTY OR SBC SSTD FOR EXTERIOR | | | GLAZING6. | | | 6. SHEETS S1.0,S2.0,& S2.1 NOT SEALED OR | | | SIGNED |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-01 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-01 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-21 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-21 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-31 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-31 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE:PLEASE SUBMIT PLANS WHICH REFLECT | | | "99" NEC. | | | | | | 2)NOTE: PLEASE CLARIFY NOTES 1&2 ON | | | SHEET E-1.0 LIGHTING PLAN KEY NOTES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-17 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) ENSURE THAT EMERGENCY LIGHTING | | | EQUIPMENT IS INSTALLED IN SALES AREA. | | | 2) PORTABLE FIRE EXTINGUISHERS | | | REQUIRED THROUGHOUT TENANT SPACE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-08 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) TRAVEL DISTANCE TO EXITS NOTED ON | | | PLANS IS NOT CORRECT. MAXIMUM TRAVEL | | | DISTANCE TO EXITS IS 150 FEET WHEN | | | FIRE SPRINKLERS ARE PRESENT. | | | 2) INTERIOR FINISH TO BE CLASS A OR B. | | | 3) EXITING FROM REAR STOCKROOM IS NOT | | | CLEAR. IN STOCKROOM #2,(116) IS DOOR | | | 16 AN EXIT? ON ELECTRICAL PLANS, NO | | | EXIT SIGN IS SHOWN. | | | 4) DEFINE VOID SPACE SHOWN ADJACENT TO | | | STOCKROOM #2 AND RATED EXIT CORRIDOR. | | | 5) PROVIDE PLANS AND PERMIT FOR FIRE | | | ALARM EQUIPMENT SHOWN ON PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-29 |
Time |
14:57 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-08-29 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | NOTE DUCT SMOKE DETECTOR IF INSTALLED | | | IN RETURN AIR PLENUM TO BE PRIOR TO ANY | | | MIXING OF OUTSIDE AIR | | | NOTE: NO COMBUSTABLES TO BE INSTALLED | | | IN RETURN AIR PLENUM AREA ABOVE CEILING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-14 |
Time |
13:30 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-14 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES: | | | INFORMATION REQUESTED WAS SUBMITTED WITH | | | REVISION... |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-24 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-24 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-08-10 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | 1. FIRE DAMPERS REQUIRED AT RATED WALLS | | | TO BE INDICATED. | | | 2.PROVIDE AN AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2.. | | | 3.REQUIRE AN OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89.. | | | 4.PROVIDE A GRILLE SCHEDULE ON PLANS. | | | 5.REQUIRE AN ENERGY EFFICIENCY RATING | | | AS PER FLORIDA ENERGY EFFICIENCY CODE | | | FOR THE AHU-1. | | | 6.PROVIDE A SMOKE DETECTOR IN RETURN | | | DUCTWORK. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-01 |
Time |
11:06 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-08-31 |
Time |
21:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-29 |
Time |
18:11 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-29 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT A SANITARY RISER THAT COMPLIES | | | W/THE STANDARD PLUMBING CODE. | | | WATER CLOSETS ARE NOT PERMITTED TO BE | | | INSTALLED ON WET VENTS PER COUNTYWIDE | | | AMENDMENTS TO THE SPC SEC.911.1.1. | | | REVISED RISER SHALL BE SIGNED AND SEALED | | | BY THE DESIGN PROFESSIONAL OF RECORD. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-17 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-17 |
Time |
12:16 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-17 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)DOOR FROM JANITOR'S CLOSET CANNOT | | | SWING INTO CLEAR FLOOR SPACE FOR LAV.PER | | | FACBC SEC.4.22.2. | | | | | | 2)OFFICE DOOR SHALL NOT SWING INTO CLEAR | | | FLOOR SPACE REQD.FOR DRINKING FOUNTAIN. | | | FACBC 4.22.2. | | | | | | 3)DRINKINGFOUNTAIN SHALL COMPLY W/ | | | FACBC SEC.4.1.3(10)(A).PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 4)AN ADDITIONAL LAV.IS REQD.IN THE | | | WOMEN'S R.R.PER TABLE 407. | | | | | | 5)WATER CLOSETS ARE NOT PERMITTED ON WET | | | VENT PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.911.1.1. | | | | | | 6)BENCH IN FITTING ROOM SHALL BE LOCATED | | | ALONG WALL W/THE LONGER DIMENSION PER | | | FACBC SEC.4.35.4. | | | | | | 7)RELIEF LINE SHALL DISCHARGE TO EXTER- | | | IOR OR TO PLUMBING FIXTURE.COUNTYWIDE | | | AMENDMENTS 507.8.4. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-21 |
Time |
13:19 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT A-1.0 FITTING RM #106 COMPLY | | | W/ FACBC 4.35, SWING OF DOOR IS IN | | | WHEEL CHAIR RADIUS,SWING DOOR OUT,ALSO | | | SHOW ELEVATION OF BENCH. | | | (2A) SHT P-1.0 SANITARY DIAGRAM, | | | HORIZONTAL DRY VENT NOT PERMITED SPC 94 | | | SEC 914.2 RECOMEND WET VENT SYSTEM. | | | SPC 94 SEC 911. | | | (B) WTR. HTR LOCATION TO BE READLY | | | ACCESSIBLE SPC 94 SEC 501.7,PROVIDE A | | | PERMINAMENT SHIPS LADDER AND WORKING | | | PLATFORM, TO COMPLY. | | | (C) NO CODE, MOP SINK IN PUBLIC REST RM | | | NOT RECOMENDED,PAST PRACTICE, LOCATE | | | MOP SINK IN JANITORS CLOSET. | | | )D) TOILET RM #2 DOOR SWINGS IN TURNING | | | RADIUS OF WHEEL CHAIR,SWING DOOR OUT, OR | | | MOVE LAV, FACBC4.16.2, ANOTHER GOOD | | | REASON TO RELOCATE MOP SINK. | | | (E) SHOW HEIGHT OF H/C WATER CLOSET ON | | | ELEVATIOPN DETAILS,SPC 94 SEC 104.2 | | | (F) SEE OTHER COMMENTS BY CPPR. | | | END OF COMMENTS |
|
|