Plan Review Details - Permit 00070484
Plan Review Stops For Permit 00070484
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2000-10-02 Cont ID  
Sent By drunnels Date 2000-10-02 Time 11:41 Rev Time 1.00
Received By drunnels Date 2000-10-02 Time 11:41 Sent To  
Notes
2001-01-08 00:00:00SHOP DRAWINGS
 ALL SHEETS MUST HAVE RAISED SEAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-05 Cont ID  
Sent By drunnels Date 2000-09-05 Time 08:39 Rev Time 1.00
Received By drunnels Date 2000-09-05 Time 08:39 Sent To  
Notes
2001-01-08 00:00:00*************NOTE**************
 STOREFRONT UNDER SEPERATE PERMIT
 SIGNS UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-29 Cont ID  
Sent By drunnels Date 2000-08-29 Time 13:30 Rev Time 1.00
Received By drunnels Date 2000-08-29 Time 13:30 Sent To  
Notes
2001-01-08 00:00:00PREVIOUS ITEMS #1,3& 5 NOT CORRECTED
 ****************PROVISO************
 EXTERIOR SINGS TO BE UNDER SEPERATE
 PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-31 Cont ID  
Sent By drunnels Date 2000-07-31 Time 08:23 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
 1. FLORIDA ENERGY EFFICIENCY SHEETS MUST
 BE SIGNED BY THE OWNER/OWNER AGENT
 2. PROVIDE LETTER FROM SPECIAL INSPECTOR
 3. FIRE SPRINKLER PERMIT MUST BE ISSURED
 PRIOR TO ISSURANCE OF BUILDING PERMIT
 4. EXTERIOR SIGNS TO BE UNDER SEPERATE
 PERMIT.
 5. POVIDE PRODUCT APPROVAL SHEETS METRO
 COUNTY OR SBC SSTD FOR EXTERIOR
 GLAZING6.
 6. SHEETS S1.0,S2.0,& S2.1 NOT SEALED OR
 SIGNED

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-01 Cont ID  
Sent By dpalmer Date 2000-09-01 Time 12:00 Rev Time 0.00
Received By dpalmer Date 2000-09-01 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 08:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 13:04 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 13:04 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT ***************
  
 1)NOTE:PLEASE SUBMIT PLANS WHICH REFLECT
 "99" NEC.
  
 2)NOTE: PLEASE CLARIFY NOTES 1&2 ON
 SHEET E-1.0 LIGHTING PLAN KEY NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-17 Cont ID  
Sent By mcarsill Date 2000-08-17 Time 13:24 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) ENSURE THAT EMERGENCY LIGHTING
 EQUIPMENT IS INSTALLED IN SALES AREA.
 2) PORTABLE FIRE EXTINGUISHERS
 REQUIRED THROUGHOUT TENANT SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By mcarsill Date 2000-08-08 Time 08:53 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) TRAVEL DISTANCE TO EXITS NOTED ON
 PLANS IS NOT CORRECT. MAXIMUM TRAVEL
 DISTANCE TO EXITS IS 150 FEET WHEN
 FIRE SPRINKLERS ARE PRESENT.
 2) INTERIOR FINISH TO BE CLASS A OR B.
 3) EXITING FROM REAR STOCKROOM IS NOT
 CLEAR. IN STOCKROOM #2,(116) IS DOOR
 16 AN EXIT? ON ELECTRICAL PLANS, NO
 EXIT SIGN IS SHOWN.
 4) DEFINE VOID SPACE SHOWN ADJACENT TO
 STOCKROOM #2 AND RATED EXIT CORRIDOR.
 5) PROVIDE PLANS AND PERMIT FOR FIRE
 ALARM EQUIPMENT SHOWN ON PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-29 Cont ID  
Sent By ndenmark Date 2000-08-29 Time 14:57 Rev Time 0.50
Received By ndenmark Date 2000-08-29 Time 14:55 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 NOTE DUCT SMOKE DETECTOR IF INSTALLED
 IN RETURN AIR PLENUM TO BE PRIOR TO ANY
 MIXING OF OUTSIDE AIR
 NOTE: NO COMBUSTABLES TO BE INSTALLED
 IN RETURN AIR PLENUM AREA ABOVE CEILING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-14 Cont ID  
Sent By cthirben Date 2000-08-14 Time 13:30 Rev Time 1.00
Received By cthirben Date 2000-08-14 Time 13:29 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 INFORMATION REQUESTED WAS SUBMITTED WITH
 REVISION...

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By cthirben Date 2000-07-24 Time 10:34 Rev Time 0.00
Received By cthirben Date 2000-08-10 Time 11:52 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1. FIRE DAMPERS REQUIRED AT RATED WALLS
 TO BE INDICATED.
 2.PROVIDE AN AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2..
 3.REQUIRE AN OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89..
 4.PROVIDE A GRILLE SCHEDULE ON PLANS.
 5.REQUIRE AN ENERGY EFFICIENCY RATING
 AS PER FLORIDA ENERGY EFFICIENCY CODE
 FOR THE AHU-1.
 6.PROVIDE A SMOKE DETECTOR IN RETURN
 DUCTWORK.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-01 Cont ID  
Sent By tlarge Date 2000-09-01 Time 11:06 Rev Time 0.75
Received By tlarge Date 2000-08-31 Time 21:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-29 Cont ID  
Sent By tlarge Date 2000-08-29 Time 18:11 Rev Time 0.50
Received By tlarge Date 2000-08-29 Time 18:01 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT A SANITARY RISER THAT COMPLIES
 W/THE STANDARD PLUMBING CODE.
 WATER CLOSETS ARE NOT PERMITTED TO BE
 INSTALLED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO THE SPC SEC.911.1.1.
 REVISED RISER SHALL BE SIGNED AND SEALED
 BY THE DESIGN PROFESSIONAL OF RECORD.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 12:16 Rev Time 0.50
Received By tlarge Date 2000-08-17 Time 12:16 Sent To  
Notes
2001-01-08 00:00:001)DOOR FROM JANITOR'S CLOSET CANNOT
 SWING INTO CLEAR FLOOR SPACE FOR LAV.PER
 FACBC SEC.4.22.2.
  
 2)OFFICE DOOR SHALL NOT SWING INTO CLEAR
 FLOOR SPACE REQD.FOR DRINKING FOUNTAIN.
 FACBC 4.22.2.
  
 3)DRINKINGFOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 4)AN ADDITIONAL LAV.IS REQD.IN THE
 WOMEN'S R.R.PER TABLE 407.
  
 5)WATER CLOSETS ARE NOT PERMITTED ON WET
 VENT PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 6)BENCH IN FITTING ROOM SHALL BE LOCATED
 ALONG WALL W/THE LONGER DIMENSION PER
 FACBC SEC.4.35.4.
  
 7)RELIEF LINE SHALL DISCHARGE TO EXTER-
 IOR OR TO PLUMBING FIXTURE.COUNTYWIDE
 AMENDMENTS 507.8.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-21 Cont ID  
Sent By pschmitz Date 2000-07-21 Time 13:19 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT A-1.0 FITTING RM #106 COMPLY
 W/ FACBC 4.35, SWING OF DOOR IS IN
 WHEEL CHAIR RADIUS,SWING DOOR OUT,ALSO
 SHOW ELEVATION OF BENCH.
 (2A) SHT P-1.0 SANITARY DIAGRAM,
 HORIZONTAL DRY VENT NOT PERMITED SPC 94
 SEC 914.2 RECOMEND WET VENT SYSTEM.
 SPC 94 SEC 911.
 (B) WTR. HTR LOCATION TO BE READLY
 ACCESSIBLE SPC 94 SEC 501.7,PROVIDE A
 PERMINAMENT SHIPS LADDER AND WORKING
 PLATFORM, TO COMPLY.
 (C) NO CODE, MOP SINK IN PUBLIC REST RM
 NOT RECOMENDED,PAST PRACTICE, LOCATE
 MOP SINK IN JANITORS CLOSET.
 )D) TOILET RM #2 DOOR SWINGS IN TURNING
 RADIUS OF WHEEL CHAIR,SWING DOOR OUT, OR
 MOVE LAV, FACBC4.16.2, ANOTHER GOOD
 REASON TO RELOCATE MOP SINK.
 (E) SHOW HEIGHT OF H/C WATER CLOSET ON
 ELEVATIOPN DETAILS,SPC 94 SEC 104.2
 (F) SEE OTHER COMMENTS BY CPPR.
 END OF COMMENTS