| Plan Review Stops For Permit 00070456 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-22 |
Time |
14:07 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-22 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-21 |
Time |
12:00 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-21 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. SUBMIT FIRE SPRINKLER PLANS AND | | | APPLICATION FOR PERMIT | | | | | | " PROVISO" | | | 1. STORE FRONT UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-07 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-07 |
Time |
10:24 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
2000-08-07 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. FLORIDA ENERGY CALUCATIONS MUST BE | | | SIGNED BY OWNER/AGENT. | | | 2. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT GLAZING FOR STOREFRONT WINDOWS | | | AND DOORS. METRO DADE COUNTY OD SBBCI | | | STTD12-97. | | | 3. SUBMIT FIRE SPRINKLER APPLICATION AND | | | PLANS. FIRE SPRINKLER PERMIT TO BE | | | ISSUED PRIOR TO ISSURANCE OF BUILDING | | | PERMIT. | | | 4.EXISTING FIRE RATED DEMISING WALL- 2HR | | | FIRE RATED SEPERATION REQUIRED- PROVIDE | | | UL NUMBER-NOTE DETAIL 7 ON SHEET A-12 | | | TENANT SIDE SHOWS BEING COMPLETED BY | | | T.G.C. BOTH SIDES TO BE COMPLETED PRIOR | | | TO C.O. BEING ISSUED. | | | 5. SHOW ARANGEMENT AND NUMBER OF EXITS | | | COMPLY WITH 1997 SBC CHAPTER 10 | | | SECTION 1004. | | | 6. SHOW THAT BAR AREA COMPLIES WITH | | | 1997 SBC CHAPTER 10 SECTION 1019.8 | | | STAIRWAY CONSTRUCTION. | | | 7. LIST GOVERNING CODES ON COVER SHEET. | | | 8. BUILDING IS TYPE 2 CONSTRUCTION 1997 | | | SBC ALL WOOD FRAMING SHALL COMPLY WITH | | | CHAPTER 6&7. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-21 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-21 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************PROVISO**************** | | | | | | 1)NOTE: PLEASE NOTE THAT SHEETS E-3 AND | | | E-5 DIFFERS. PLEASE CORRELATE. ONE SHOWN | | | AS MCB AND THE OTHER AS MLO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE FINAL ELECTRICAL INSPEC- | | | -TION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-31 |
Time |
20:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-31 |
Time |
20:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: OUTLET IN WINE ROOM STORAGE TO | | | BE GFI/ GFI PROTECTED PER 210-8-A-8 | | | | | | 2)NOTE : PER 210-63 GFI OUTLET FOR | | | ROOF TOP EQUIPMENT 25`. | | | | | | 3)NOTE: PLEASE NOTE PANEL"A" NEEDS TO BE | | | MCB. REQ`D MAIN ON LOAD SIDE OF TRANS- | | | -FORMER. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-21 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) HOST STATION IS NOT TO BLOCK | | | REQUIRED EXIT DOORS. | | | 2) GAS INSTALLATION TO COMPLY WITH NFPA | | | 54. | | | 3) PLEASE PROVIDE FIRE ALARM DEVICES | | | IN OUTSIDE DINING, (201). | | | 4) RAMPS ARE TO COMPLY WITH BUILDING | | | CODE REQUIREMENTS. | | | 5) PROVIDE COMPLETE SHOP DRAWINGS FOR | | | THE INSTALLATION OF FIRE ALARM DEVICES | | | SHOWN ON PLANS. A SEPARATE PLAN AND | | | PERMIT REQUIRED. CUT SHEETS NEEDED ON | | | ALL DEVICES PLANNED FOR USE. | | | 6) PROVIDE COMPLETE PLANS FOR THE HOOD, | | | DUCT, AND EXTINGUISHING SYSTEM. A | | | SEPARATE PLAN AND PERMIT REQUIRED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-08 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 2) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 3) INTERIOR FINISH ON WALLS AND CEILINGS | | | SHALL BE CLASS A,B OR C. DOCUMENTATION | | | ON FLAME SPREAD RATINGS ARE TO BE | | | SUBMITTED ON DRAPERIES, SEATS AND OTHER | | | ITEMS. | | | 4) FIRE SPRINKLER DRAWING ON PAGE FS-1A | | | DOES NOT SHOW FIRE SPRINKLER PROTECTION | | | IN COOLER OR SHUTTER STORAGE. THE ENTIRE | | | SPACE IS TO BE PROTECTED BY FIRE | | | SPRINKLERS. THIS INCLUDES ALL COOLERS, | | | FREEZERS, STORAGE, MECHANICAL, AND | | | ELECTRICAL ROOMS. | | | 5) WHERE IS THE EMERGENCY LIGHTING FOR | | | THE OUTSIDE DINING AREA (201). | | | 6) ANY CHANGES IN ELEVATIONS LESS THAN | | | 21 INCHES,SHALL BE BY RAMPS. | | | 7) ANY DOOR USED FOR EXITING MUST BE | | | EQUIPPED WITH APPROVED PANIC HARDWARE. | | | FIRE DOORS ARE TO BE EQUIPPED WITH | | | APPROVED FIRE EXIT PANIC HARDWARE. | | | 8) PROVIDE DETAILS ON PIZZA OVEN. | | | 9) PROVIDE COMPLETE HOOD,DUCT AND FIRE | | | EXTINGUISHING PLANS TO BUILDING DEPT. | | | SEPARATE PERMITS REQUIRED. | | | 10) MAIN FIRE EXIT MUST BE CAPABLE OF | | | EXITING AT LEAST 50 PERCENT OF THE | | | OCCUPANT LOAD. | | | 11) NO WAITING SPACE CALCULATIONS | | | INCLUDED IN SEATING TABULATIONS. | | | 12) PROVIDE COMPLETE SHOP DRAWINGS FOR | | | THE INSTALLATION OF FIRE ALARM EQUIPMENT | | | SHOWN ON DRAWINGS. | | | 13) PORTABLE FIRE EXTINGUISHERS REQUIRED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-21 |
Time |
13:40 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-21 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ACCEPTED BY REVISIONS DATED 8/15/00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-21 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-21 |
Time |
14:43 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-21 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | 1.FIRE/SMOKE DAMPERS REQUIRED WHERE DUCT | | | PENETRATES THE RATED WALLS. | | | 2.SEPERATE PERMIT REQUIRED FOR HOODS,GAS | | | WALK-IN COOLER/FREEZER,FIRE SUPPRESSION | | | SYSTEM. | | | 3.ENERGY EFFICIENCY RATING OF AHU,S | | | REQUIRED PER FLORIDA ENERGY EFFICIECY | | | CODE. | | | 4.EXHAUST FANS AND OUTSIDE AIR CLEARANCE | | | PER 1997 SMC 506.1 SHOULD BE 10'(FT). | | | 5.CLEARANCE FROM BOTTOM OF SUPPORT BEAM | | | TO THE TOP OF FINISHED ROOF, THE AHU | | | STAND SHOULD BE 18" HEIGHT, NEEDS DETAIL | | | OF STAND WHICH SHOULD BE SIGN & SEALED. | | | 6.DUCT MATERIAL SCHEDULE REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-19 |
Time |
10:01 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-08-19 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | THE PLUMBING IS APPROVED WITH THE | | | FOLLOWING PROVISOS.THIS INFORMATION MUST | | | BE SUBMITTED PRIOR TO PLUMBING INSPECT- | | | ION. | | | | | | 1)SUBMIT DETAIL OF WATER HEATER VENT. | | | INDICATE TYPE OF VENT(B,L,ETC.),TERM- | | | INATION POINT,LENGTH OF VENT CONNECTOR, | | | COMPLY W/SGC SEC.605.3,607.5,608.3. | | | | | | 2)DRAIN FOR BAR AREA(204)REQUIRES MIN.3" | | | VENT DOWNSTREAM OF ALL FIXTURES.(VENT IS | | | SHOWN ON P-1A BUT NOT ON RISER.) | | | | | | 3)GAS SYSTEM SHALL BE SIZED PER TABLE | | | 305.4(A) OF THE SGC.THERE IS NO TABLE | | | G102.5(1)IN THE GAS CODE OR PLBG.CODE. | | | REVISE TO COMPLY. | | | | | | 4)SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP. | | | EQUIPMENT SHALL BE LISTED.SGC 402.1,501. | | | | | | 5)SUBMIT DETAIL OF GAS MANIFOLD.PLANS | | | NOTE LOCATION IN TRANSFORMER ROOM. | | | MANIFOLD MAY REQUIRE RELOCATION FROM | | | SOURCE OF IGNITION PENDING INFORMATION. | | | | | | 6)DISHWASHER AND GARBAGE DISPOSAL SHALL | | | DISCHARGE TO THE SANITARY.SPC 409.5,, | | | 1004.11& CITY OF WPB ORD. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-29 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-29 |
Time |
11:37 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-07-29 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)THE MINIMUM NUMBER OF REQUIRED | | | SANITARY FACILITIES SHALL COMPLY W/SPC | | | TABLE 407.AN ADDITIONAL WATER CLOSET IS | | | REQUIRED IN THE WOMEN'S RESTROOM. | | | | | | 2)SIZE OF HANDICAP STALLS SHALL COMPLY | | | W/FACBC SEC.4.17.3.(MIN.OF 83"WIDE REQD) | | | | | | 3)SHT.A-12-CLEAR FLOOR SPACE UNDER H.C. | | | LAV.SHALL BE 29"PER FACBC SEC.4.19.2. | | | | | | 4)SEE ATTACHED LIST FOR GAS SYSTEM REQS. | | | | | | 5)SUBMIT DETAIL OF WATER HEATER FLUE. | | | COMPLY W/SGC 1997 EDITION. | | | | | | 6)SHT.P-2-VENT SHALL CONNECT TO STACK | | | VENT NOT 6"WASTE STACK.SPC SEC.901.2, | | | 904.1. | | | | | | 7)DRY VENTS NOT PERMITTED PER SPC 906.2. | | | SEE VENTS BY FIXTURES P-36,P-43-C,P-56, | | | P-85,& H.C.WATER CLOSET IN TOILET ROOM. | | | | | | 8)SIZE ALL SECTIONS OF THE SANITARY | | | DRAIN ,WASTE AND VENT SYSTEM.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 9)SIZE ALL SECTIONS OF THE WATER RISER | | | DIAGRAM.COUNTYWIDE AMENDMENTS TO SPC SEC | | | 104.2.1. | | | | | | 10)FLOOR SINKS AND FLOOR DRAINS ARE NOT | | | PROPERLY VENTED.SPC SEC.901.2.(SEE | | | P-70B,9C,63B,P36,ETC. | | | | | | 11)DISHWASHER AND GARBAGE DISPOSAL SHALL | | | DISCHARGE TO SANITARY.SPC 409.5,1004.11. | | | CITY OF WPB ORDINANCE. | | | | | | 12)GAS SYSTEM SIZING IS NOT TO CODE. | | | COMPLY W/SGC 305.4. | | | | | | 13)POT/SCULLERY SINK SHALL BE STACKED & | | | VENTED.SPC 713.1. | | | | | | 14)WATER CLOSETS NOT PERMITTED ON WET | | | VENTS.RELOCATE VENTS TO COMPLY W/COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.911.1.1. | | | | | | 15)VACUUM RELIEF VALVE REQD.ON C.W.INLET | | | TO GWH. | | | | | | 16)HOT WATER TO RESTROOMS SHALL BE MAX. | | | 110 DEGREES PER FEC SEC.412.1ABCD.2.3.2. | | | | | | 17)RESTAURANT SHALL COMPLY W/FLA.STATUTE | | | 553.141.(POTTY PARITY.) | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE,PLUMBING PLANS EXAMINER. |
|
|