Plan Review Details - Permit 00070456
Plan Review Stops For Permit 00070456
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-22 Cont ID  
Sent By drunnels Date 2000-08-22 Time 14:07 Rev Time 1.00
Received By drunnels Date 2000-08-22 Time 14:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By drunnels Date 2000-08-21 Time 12:00 Rev Time 1.00
Received By drunnels Date 2000-08-21 Time 12:00 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION FOR PERMIT
  
 " PROVISO"
 1. STORE FRONT UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-07 Cont ID  
Sent By drunnels Date 2000-08-07 Time 10:24 Rev Time 1.00
Received By bstaples Date 2000-08-07 Time 10:24 Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY CALUCATIONS MUST BE
 SIGNED BY OWNER/AGENT.
 2. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR STOREFRONT WINDOWS
 AND DOORS. METRO DADE COUNTY OD SBBCI
 STTD12-97.
 3. SUBMIT FIRE SPRINKLER APPLICATION AND
 PLANS. FIRE SPRINKLER PERMIT TO BE
 ISSUED PRIOR TO ISSURANCE OF BUILDING
 PERMIT.
 4.EXISTING FIRE RATED DEMISING WALL- 2HR
 FIRE RATED SEPERATION REQUIRED- PROVIDE
 UL NUMBER-NOTE DETAIL 7 ON SHEET A-12
 TENANT SIDE SHOWS BEING COMPLETED BY
 T.G.C. BOTH SIDES TO BE COMPLETED PRIOR
 TO C.O. BEING ISSUED.
 5. SHOW ARANGEMENT AND NUMBER OF EXITS
 COMPLY WITH 1997 SBC CHAPTER 10
 SECTION 1004.
 6. SHOW THAT BAR AREA COMPLIES WITH
 1997 SBC CHAPTER 10 SECTION 1019.8
 STAIRWAY CONSTRUCTION.
 7. LIST GOVERNING CODES ON COVER SHEET.
 8. BUILDING IS TYPE 2 CONSTRUCTION 1997
 SBC ALL WOOD FRAMING SHALL COMPLY WITH
 CHAPTER 6&7.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 09:37 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO****************
  
 1)NOTE: PLEASE NOTE THAT SHEETS E-3 AND
 E-5 DIFFERS. PLEASE CORRELATE. ONE SHOWN
 AS MCB AND THE OTHER AS MLO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL INSPEC-
 -TION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 20:43 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 20:43 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: OUTLET IN WINE ROOM STORAGE TO
 BE GFI/ GFI PROTECTED PER 210-8-A-8
  
 2)NOTE : PER 210-63 GFI OUTLET FOR
 ROOF TOP EQUIPMENT 25`.
  
 3)NOTE: PLEASE NOTE PANEL"A" NEEDS TO BE
 MCB. REQ`D MAIN ON LOAD SIDE OF TRANS-
 -FORMER.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By mcarsill Date 2000-08-21 Time 08:01 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) HOST STATION IS NOT TO BLOCK
 REQUIRED EXIT DOORS.
 2) GAS INSTALLATION TO COMPLY WITH NFPA
 54.
 3) PLEASE PROVIDE FIRE ALARM DEVICES
 IN OUTSIDE DINING, (201).
 4) RAMPS ARE TO COMPLY WITH BUILDING
 CODE REQUIREMENTS.
 5) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF FIRE ALARM DEVICES
 SHOWN ON PLANS. A SEPARATE PLAN AND
 PERMIT REQUIRED. CUT SHEETS NEEDED ON
 ALL DEVICES PLANNED FOR USE.
 6) PROVIDE COMPLETE PLANS FOR THE HOOD,
 DUCT, AND EXTINGUISHING SYSTEM. A
 SEPARATE PLAN AND PERMIT REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By mcarsill Date 2000-08-08 Time 11:47 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 2) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 3) INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL BE CLASS A,B OR C. DOCUMENTATION
 ON FLAME SPREAD RATINGS ARE TO BE
 SUBMITTED ON DRAPERIES, SEATS AND OTHER
 ITEMS.
 4) FIRE SPRINKLER DRAWING ON PAGE FS-1A
 DOES NOT SHOW FIRE SPRINKLER PROTECTION
 IN COOLER OR SHUTTER STORAGE. THE ENTIRE
 SPACE IS TO BE PROTECTED BY FIRE
 SPRINKLERS. THIS INCLUDES ALL COOLERS,
 FREEZERS, STORAGE, MECHANICAL, AND
 ELECTRICAL ROOMS.
 5) WHERE IS THE EMERGENCY LIGHTING FOR
 THE OUTSIDE DINING AREA (201).
 6) ANY CHANGES IN ELEVATIONS LESS THAN
 21 INCHES,SHALL BE BY RAMPS.
 7) ANY DOOR USED FOR EXITING MUST BE
 EQUIPPED WITH APPROVED PANIC HARDWARE.
 FIRE DOORS ARE TO BE EQUIPPED WITH
 APPROVED FIRE EXIT PANIC HARDWARE.
 8) PROVIDE DETAILS ON PIZZA OVEN.
 9) PROVIDE COMPLETE HOOD,DUCT AND FIRE
 EXTINGUISHING PLANS TO BUILDING DEPT.
 SEPARATE PERMITS REQUIRED.
 10) MAIN FIRE EXIT MUST BE CAPABLE OF
 EXITING AT LEAST 50 PERCENT OF THE
 OCCUPANT LOAD.
 11) NO WAITING SPACE CALCULATIONS
 INCLUDED IN SEATING TABULATIONS.
 12) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF FIRE ALARM EQUIPMENT
 SHOWN ON DRAWINGS.
 13) PORTABLE FIRE EXTINGUISHERS REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By ndenmark Date 2000-08-21 Time 13:40 Rev Time 0.33
Received By ndenmark Date 2000-08-21 Time 13:40 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED BY REVISIONS DATED 8/15/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-21 Cont ID  
Sent By cthirben Date 2000-07-21 Time 14:43 Rev Time 1.00
Received By cthirben Date 2000-07-21 Time 14:14 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.FIRE/SMOKE DAMPERS REQUIRED WHERE DUCT
 PENETRATES THE RATED WALLS.
 2.SEPERATE PERMIT REQUIRED FOR HOODS,GAS
 WALK-IN COOLER/FREEZER,FIRE SUPPRESSION
 SYSTEM.
 3.ENERGY EFFICIENCY RATING OF AHU,S
 REQUIRED PER FLORIDA ENERGY EFFICIECY
 CODE.
 4.EXHAUST FANS AND OUTSIDE AIR CLEARANCE
 PER 1997 SMC 506.1 SHOULD BE 10'(FT).
 5.CLEARANCE FROM BOTTOM OF SUPPORT BEAM
 TO THE TOP OF FINISHED ROOF, THE AHU
 STAND SHOULD BE 18" HEIGHT, NEEDS DETAIL
 OF STAND WHICH SHOULD BE SIGN & SEALED.
 6.DUCT MATERIAL SCHEDULE REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-19 Cont ID  
Sent By tlarge Date 2000-08-19 Time 10:01 Rev Time 2.00
Received By tlarge Date 2000-08-19 Time 09:04 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 THE PLUMBING IS APPROVED WITH THE
 FOLLOWING PROVISOS.THIS INFORMATION MUST
 BE SUBMITTED PRIOR TO PLUMBING INSPECT-
 ION.
  
 1)SUBMIT DETAIL OF WATER HEATER VENT.
 INDICATE TYPE OF VENT(B,L,ETC.),TERM-
 INATION POINT,LENGTH OF VENT CONNECTOR,
 COMPLY W/SGC SEC.605.3,607.5,608.3.
  
 2)DRAIN FOR BAR AREA(204)REQUIRES MIN.3"
 VENT DOWNSTREAM OF ALL FIXTURES.(VENT IS
 SHOWN ON P-1A BUT NOT ON RISER.)
  
 3)GAS SYSTEM SHALL BE SIZED PER TABLE
 305.4(A) OF THE SGC.THERE IS NO TABLE
 G102.5(1)IN THE GAS CODE OR PLBG.CODE.
 REVISE TO COMPLY.
  
 4)SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 EQUIPMENT SHALL BE LISTED.SGC 402.1,501.
  
 5)SUBMIT DETAIL OF GAS MANIFOLD.PLANS
 NOTE LOCATION IN TRANSFORMER ROOM.
 MANIFOLD MAY REQUIRE RELOCATION FROM
 SOURCE OF IGNITION PENDING INFORMATION.
  
 6)DISHWASHER AND GARBAGE DISPOSAL SHALL
 DISCHARGE TO THE SANITARY.SPC 409.5,,
 1004.11& CITY OF WPB ORD.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-29 Cont ID  
Sent By tlarge Date 2000-07-29 Time 11:37 Rev Time 2.00
Received By tlarge Date 2000-07-29 Time 10:46 Sent To  
Notes
2001-01-08 00:00:001)THE MINIMUM NUMBER OF REQUIRED
 SANITARY FACILITIES SHALL COMPLY W/SPC
 TABLE 407.AN ADDITIONAL WATER CLOSET IS
 REQUIRED IN THE WOMEN'S RESTROOM.
  
 2)SIZE OF HANDICAP STALLS SHALL COMPLY
 W/FACBC SEC.4.17.3.(MIN.OF 83"WIDE REQD)
  
 3)SHT.A-12-CLEAR FLOOR SPACE UNDER H.C.
 LAV.SHALL BE 29"PER FACBC SEC.4.19.2.
  
 4)SEE ATTACHED LIST FOR GAS SYSTEM REQS.
  
 5)SUBMIT DETAIL OF WATER HEATER FLUE.
 COMPLY W/SGC 1997 EDITION.
  
 6)SHT.P-2-VENT SHALL CONNECT TO STACK
 VENT NOT 6"WASTE STACK.SPC SEC.901.2,
 904.1.
  
 7)DRY VENTS NOT PERMITTED PER SPC 906.2.
 SEE VENTS BY FIXTURES P-36,P-43-C,P-56,
 P-85,& H.C.WATER CLOSET IN TOILET ROOM.
  
 8)SIZE ALL SECTIONS OF THE SANITARY
 DRAIN ,WASTE AND VENT SYSTEM.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 9)SIZE ALL SECTIONS OF THE WATER RISER
 DIAGRAM.COUNTYWIDE AMENDMENTS TO SPC SEC
 104.2.1.
  
 10)FLOOR SINKS AND FLOOR DRAINS ARE NOT
 PROPERLY VENTED.SPC SEC.901.2.(SEE
 P-70B,9C,63B,P36,ETC.
  
 11)DISHWASHER AND GARBAGE DISPOSAL SHALL
 DISCHARGE TO SANITARY.SPC 409.5,1004.11.
 CITY OF WPB ORDINANCE.
  
 12)GAS SYSTEM SIZING IS NOT TO CODE.
 COMPLY W/SGC 305.4.
  
 13)POT/SCULLERY SINK SHALL BE STACKED &
 VENTED.SPC 713.1.
  
 14)WATER CLOSETS NOT PERMITTED ON WET
 VENTS.RELOCATE VENTS TO COMPLY W/COUNTY-
 WIDE AMENDMENTS TO SPC SEC.911.1.1.
  
 15)VACUUM RELIEF VALVE REQD.ON C.W.INLET
 TO GWH.
  
 16)HOT WATER TO RESTROOMS SHALL BE MAX.
 110 DEGREES PER FEC SEC.412.1ABCD.2.3.2.
  
 17)RESTAURANT SHALL COMPLY W/FLA.STATUTE
 553.141.(POTTY PARITY.)
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.