Plan Review Details - Permit 00070448
Plan Review Stops For Permit 00070448
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By drunnels Date 2000-08-02 Time 17:04 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
 PRODUCT APPROVAL FOR IMPACT RESISTANT
 WINDOW RECEIVED 8-2-00, WINDOW PROVISO
 REMOVED FROM THIS PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By drunnels Date 2000-08-01 Time 14:49 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
 PROVISO
 PROVIDE PRODUCT APPROVAL FOR WINDOWS
 PER METRO DADE COUNTY OR SBCCI SSTD12-97
 SEPERATE PERMIT REQUIRED FOR STOREFRONT
  
 NOTE: ALL 1 HOUR FIRE RATED TENANT
 ASSEMBLIES (UL# U465) SHALL BE COMPLETED
 PRIOR TO ISSURANCE OF C.O.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-28 Cont ID  
Sent By dpalmer Date 2000-09-28 Time 18:52 Rev Time 0.00
Received By dpalmer Date 2000-09-28 Time 18:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 15:57 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 15:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-02 Cont ID  
Sent By mcarsill Date 2000-08-02 Time 08:45 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON DRAWINGS.
 2) FITTING ROOM AND BATHROOM DOORS
 CANNOT INTERFERE WITH ACCESS TO EXIT
 DOOR LEADING INTO STOCKROOM.
 3) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST,
 NOT MORE THAN 50 PERCENT OF EXIT ACCESS
 IS THROUGH STOCKROOM, THE DOOR LEADING
 TO STOCKROOM CANNOT BE LOCKED, AISLE
 OF AT LEAST 44" WIDE BE PRESENT WITHIN
 STOCKROOM, THIS 44" AISLE BE MAINTAINED.
 4) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By ndenmark Date 2000-08-01 Time 15:34 Rev Time 0.33
Received By ndenmark Date 2000-08-01 Time 15:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-22 Cont ID  
Sent By tlarge Date 2000-09-22 Time 12:45 Rev Time 0.30
Received By tlarge Date 2000-09-22 Time 12:45 Sent To  
Notes
2001-01-08 00:00:00INSTALL POINT OF USE WATER HEATER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-02 Cont ID  
Sent By tlarge Date 2000-08-02 Time 16:18 Rev Time 0.50
Received By tlarge Date 2000-08-02 Time 16:17 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 CLEARLY SHOW LOCATION OF H.C.DRESSING
 ROOM ON PLAN.ARCHITECTURAL AND PLUMBING
 PLANS DON'T CORRELATE.COMPLY W/FACBC
 SEC.4.35.4.BENCH SHALL BE LOCATED ON
 WALL WITH LONGER DIMENSION.
  
 2)HANDICAP DRINKING FOUNTAIN SHALL BE
 ON AN ACCESSIBLE ROUTE AND AVAILABLE TO
 PATRONS WITHOUT RESTRICTION.ACCESSIBLE
 ROUTE SHALL BE CLEARLY DEFINED ON THE
 PLANS.FACBC SEC.4.2,4.3,SPC 407.2.2.