Plan Review Details - Permit 00070350
Plan Review Stops For Permit 00070350
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2000-09-11 Cont ID  
Sent By drunnels Date 2000-09-11 Time 09:50 Rev Time 1.00
Received By drunnels Date 2000-09-11 Time 09:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2000-09-06 Cont ID  
Sent By drunnels Date 2000-09-06 Time 12:57 Rev Time 1.00
Received By drunnels Date 2000-09-06 Time 12:57 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-08-18 Cont ID  
Sent By drunnels Date 2000-08-18 Time 10:43 Rev Time 1.00
Received By drunnels Date 2000-08-18 Time 10:43 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
 1.PROVIDE PRODUCT APPROVAL SHEETS ON
 HURRICANE SHUTTERS THAT ARE LEGIBLE,
 PROVIDE DETAIL SHOWING HOW SHUTTERS ARE
 TO BE SECURED IN STORAGE AND THAT WALLS
 ARE CAPABLE OF CARRYING THE LOADS
 IMPOSED, ALSO NEED MORE DETAILS ON
 INSTULATION (HOW & WHO) FOR APPROVAL
 BY BUILDING OFFICIAL
 2.PROVIDE FLORIDA ENERGY SHEETS SIGNED
 AND SEALED BY ENG. & OWNER/AGENT
 3.SUBMIT FIRE SPRINKLER PLANS AND
 APPLICATION FOR PERMIT.
 4.SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
  
 NOTE: SIGNS UNDER SERPERATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-07-28 Cont ID  
Sent By drunnels Date 2000-07-28 Time 11:07 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
 1. PROVIDE SIGNED AND SEALED FLORIDA
 ENERGY SHEETS, 1997 EDITION
 2. FIRE SPRINKLER PERMIT REQUIRED PRIOR
 TO ISSURANCE OF BUILDING PERMIT.
 3. EXTERIOR SIGNS REQUIRE SEPRATE PERMIT
 4. SUBMIT APPROVAL FROM SPECIAL
 INSPECTOR.
 5. EXTERIOR GLAZING: PROVIDE PRODUCT
 APPROVAL SHEETS, METRO DADE COUNTY
 OR SBC 1997 SSTD 12-97
 6. ALL WOOD FRAMING TO BE FIRE RETARDANT
 LUMBER AS PER SBC 1997 CHAPTERS 6&7
 7. HANDICAP FITTING ROOM: DOOR SHALL NOT
 SWING INTO TURNING RADIUS, FLORIDA
 ADA SECTION 4.35.2
 8. PAGE 1: PROJECT DATA CODE REQUIREMENT
 REVISE NEC 1996 TO NEC 1999.
 9. TENTANT SEPERATION TO MEET SBC 1997
 TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS.( BOTH SIDES MUST BE
 COMPLETED PRIOR TO C.O.)
 10. SHUTTERS ARE INDICATED ON DETAIL14
 SHEET 7, PROVIDE PRODUCT APPROVAL
 INFORMATION SHEETS,INDICATE AREA OF
 STORAGE, SHOULD SHUTTERS BE STORED ON
 END SHUTTERS SHALL BE DESIGNED FOR
 ADDITIONAL LOADING; PROVIDE LETTER
 FROM TENTANT AS WHO WILL INSTALL AND
 TIME NEED TO INSTALL FOR APPROVAL OF
 BUILDING OFFICAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-28 Cont ID  
Sent By dpalmer Date 2000-08-28 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2000-08-28 Time 11:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 18:37 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 18:37 Sent To  
Notes
2001-01-08 00:00:00*********** UNSAT ************
  
 AS PER CONVERSATION WITH ENGINEER PLANS
 FOR ELECTRICAL WILL BE CHANGING AGAIN
 PER LANDLORD.8/21 DV PALMER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By dpalmer Date 2000-07-25 Time 15:37 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 18:30 Sent To  
Notes
2001-01-08 00:00:00************ UNSAT ********************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%
 (LIGHTING) AND INCULDE SHOW WINDOW AND
 TRACK LIGHTING LOADS PER 220-12(A,B)
  
 2)NOTE:PLEASE NOTE THAT YOU SHOW GROUND-
 -ING ELECTRODE REF. ART 250-26, PLEASE
 SIZE PER ART 250-66
  
 3)NOTE: PLEASE SUBMIT SOME CLARIFICATION
 ON HVAC UNIT LOAD? YOU SHOW 2992VA WHERE
 IS THIS LOAD COMING FROM.?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTION
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-09-12 Cont ID  
Sent By mcarsill Date 2000-09-12 Time 09:58 Rev Time 0.00
Received By mcarsill Date 2000-09-12 Time 09:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-17 Cont ID  
Sent By mcarsill Date 2000-08-17 Time 16:36 Rev Time 0.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. HOW IS THE BASE BUILDING FIRE
 ALARM SYSTEM HEARD WITHIN THE SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By mcarsill Date 2000-07-27 Time 12:52 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) SPRINKLER HEADS SHOWN BUT NO PIPING
 OR HYDRAULIC CALCULATIONS PROVIDED. SOME
 AREAS APPEAR TO BE NOT PROPERLY
 PROTECTED BY FIRE SPRINKLERS.
 2) TRANSFORMER IN REAR OF STORE SHOULD
 BE RELOCATED. ALTHOUGH 44" WIDTH IS
 CODE ALLOWABLE, THE TRANSFORMER BECOMES
 A PERMANENT OBSTACLE.
 3) HOW IS THE BASE BUILDING FIRE ALARM
 SYSTEM HEARD IN TENANT SPACE WHEN
 ACTIVATED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By ndenmark Date 2000-08-21 Time 14:12 Rev Time 0.33
Received By ndenmark Date 2000-08-21 Time 14:12 Sent To  
Notes
2001-01-08 00:00:00PROVISO::::::::
  
 1. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TIED TO BUILDING FIRE ALARM OR
 HORN AND STROBE PER NFPA 90A 4-4.4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By cthirben Date 2000-07-24 Time 09:40 Rev Time 1.00
Received By cthirben Date 2000-07-24 Time 09:22 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 2.PROVIDE ENERGY EFFICIENCY RATING OF
 THE AIR AHU AS PER FLORIDA ENERGY
 EFFICIENCY CODE.
 3.PROVIDE AN AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2..
 4.REQUIRED FIRE AT RATED WALLS WHERE
 APPLICABLE.
 5.REQUIRED AHU , DUCTWORK AND DIFFUSER
 MOUNTING DETAIL ON PLANS.
 6.PROVIDE DUCT MATERIAL SCHEDULE.
 7.EXHAUST FANS SCHEDULE REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 18:22 Rev Time 0.33
Received By tlarge Date 2000-08-17 Time 18:18 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 THE BENCH IN THE HANDICAP FITTING ROOM
 SHALL BE FIXED ALONG THE WALL WITH THE
 LONGER DIMENSION PER FACBC SEC.4.35.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 P[LUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-26 Cont ID  
Sent By pschmitz Date 2000-07-26 Time 12:59 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***